4.11.4 Gas pressure
Tab. L indicates the pressure drop of the combustion head and
the gas butterfly valve depending on the operating output of the
burner.
The values shown in Tab. L refer to:
–
Natural gas G 20 NCV 9.45 kWh/Sm
3
(8.2 Mcal/Sm
3
)
Column 1
Load loss at combustion head.
Gas pressure measured at the test point 1)(Fig. 25), with:
•
combustion chamber at 0 mbar;
•
burner working at maximum output;
Column 2
Pressure loss at gas butterfly valve 2)(Fig. 25) with maximum
opening: 90°.
To know the approximate output at which the burner is operating
at its maximum:
–
Subtract the combustion chamber pressure from the gas
pressure measured at test point 1)(Fig. 25).
–
Find, in the Tab. L relating to the burner concerned, column
1, the pressure value closest to the result you want.
–
Read the corresponding output on the left.
Example with natural gas G 20 for RS 68/E FGR:
Maximum output operation
Gas pressure at test point 1)(Fig. 25)
=
15.0 mbar
Pressure in combustion chamber
=
3.0 mbar
15.0 - 3.0
=
12.0 mbar
A maximum output of 800 kW shown in Tab. L corresponds to
12.0 mbar pressure, column 1.
This value serves as a rough guide; the effective output must be
measured at the gas meter.
To know the required gas pressure at test point 1)(Fig. 25), set
the maximum output required from the burner operation, then:
–
find the nearest output value in the Tab. L for the burner in
question.
–
Read, on the right (column 1) the socket pressure 1)(Fig. 25).
–
Add this value to the estimated pressure in the combustion
chamber.
Example with natural gas G 20 for RS 68/E FGR:
Required burner maximum output operation: 800 kW
Gas pressure at output of 800 kW
=
12.0 mbar
Pressure in combustion chamber
=
3.0 mbar
12.0 + 3.0
=
15.0 mbar
pressure required at test point 1)(Fig. 25).
Tab. L
kW
1
p (mbar)
2
p (mbar)
RS
6
8
/E
F
G
R
350
1.8
0.5
400
2.8
0.6
450
3.8
0.7
500
4.8
0.7
550
5.8
0.8
600
6.8
0.9
650
7.8
1.0
700
8.8
1.1
750
10.4
1.1
800
12.0
1.2
880
13.8
1.3
RS 1
20/E
FGR
595
4.1
0.8
650
5.3
0.9
700
6.5
1.0
750
7.7
1.0
800
8.9
1.1
850
10.1
1.2
900
11.5
1.3
950
13.1
1.4
1000
14.6
1.4
1050
16.2
1.5
1180
19.0
1.6
WARNING
The heat output and gas pressure data in the
head refer to operation with gas butterfly valve
fully open (90°).
Fig. 25
S8716
Содержание 20171510
Страница 2: ...Original instructions...
Страница 51: ...49 20171652 GB Appendix Electrical panel layout 0 1 1 1 1 2 3 4 3 3 4 3 5 2 6 6 6 7 6 8 6 6 6 6 6 6 6 6 6 6 7 6...
Страница 52: ...20171652 50 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01...
Страница 53: ...51 20171652 GB Appendix Electrical panel layout...
Страница 54: ...20171652 52 GB Appendix Electrical panel layout 0 1 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2...
Страница 55: ...53 20171652 GB Appendix Electrical panel layout 0 0 0 12 3456 7 12 3456 7...
Страница 56: ...20171652 54 GB Appendix Electrical panel layout 01 2 30 3 1 2 0 40 20 22 2 3 5 636 078 40 9 025 7 5...