Faults - Probable causes - Solutions
241
0
0
Actuator does not move, i.e. no position feedback.
Channel
Direction:
P 2 =
backward,
forward
If this indication is shown, the monitoring of fault 271 is damaged.
251
0
0
Actuator cannot find reference position
Channel
Direction:
0 backward
1 forward
Check the flap's smooth-running to reference position.
261
Unlimited
3
Actuator returns invalid position (difference to target position too
large)
Channel
271
Unlimited
3
Actuator feedback remains constantly for too long, even when ac-
tuator has moved
Channel
281
1
1
Feedback signal of at least 1 actuator is incorrect
Channel
To identify the actuator’s direction of rotation two pulse form sig-
nals, offset 90 degrees, are returned by the actuator.
If fault 281 occurs, these signals are not identified correctly.
Cause of error:
–
back lash
–
actuator 0,8 Nm: external torque clockwise >0.2 Nm
–
actuator 9 Nm: external torque clockwise >1 Nm
291
Optional
3
Actuator does not reach the final position, because of mixed- up de-
tection.
Channel
Actuators are mixed up while reconnecting. The test for recognising
this fault is described in the manual of the BT300 - print no.
DLT1201.
At least one actuator does not reach it's test position:
–
2 actuators are mixed up
–
another problem inhibits the actuator to reach it's test position
320
1
1
Open broken wire at firing rate input
321
1
1
Open broken wire at feedback channel: channel
Channel
351
1
1
Invalid fuel change while burner is running
352
Optional
3
Invalid combination of fuel signals (no signals)
353
Optional
3
Invalid combination of fuel signals (several signals)
360
0
0
Air deficiency causes a fault shut-down by O
2
trim.
362
0
0
Fault shut-down due to a missing burner maintenance
363
1
1
Smallest valid O
2
value decided
371
0
0
Output for internal firing rate is defective
372
0
0
Difference of the burner firing rate values between main processor
and watchdog processor is too large
381
0
0
Deviation between main processor and watchdog controller is too
large
Correction
channel
391
0
0
Curve set has changed during programming
393
0
0
Emergency shut-down activated
394
0
0
Burner ON/OFF signal from the user interface turned off unexpect-
edly
451
1
1
Being operating mode for ignition not all channels are in ignition po-
sition
Channel
600
0
0
Program monitoring time (FAT) exceeded
Indication
number
601
0
0
Failure during leakage test: gas pressure still active
602
0
0
Failure during leakage test: no gas pressure detected
603
0
0
Manual venting of the gas line required
606
0
0
CPI/POC signal in unexpected state
Fault
code
TRD
P301=0
P328>0
EN67
P301=2
P328>0
Description D1
D2
Содержание 20171510
Страница 2: ...Original instructions...
Страница 51: ...49 20171652 GB Appendix Electrical panel layout 0 1 1 1 1 2 3 4 3 3 4 3 5 2 6 6 6 7 6 8 6 6 6 6 6 6 6 6 6 6 7 6...
Страница 52: ...20171652 50 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01...
Страница 53: ...51 20171652 GB Appendix Electrical panel layout...
Страница 54: ...20171652 52 GB Appendix Electrical panel layout 0 1 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2...
Страница 55: ...53 20171652 GB Appendix Electrical panel layout 0 0 0 12 3456 7 12 3456 7...
Страница 56: ...20171652 54 GB Appendix Electrical panel layout 01 2 30 3 1 2 0 40 20 22 2 3 5 636 078 40 9 025 7 5...