27
20162733
GB
Installation
5.12.4 Gas pressure
Tab. L indicates the minimum pressure drops along the gas sup-
ply line, depending on the maximum burner output.
The values shown in Tab. L refer to:
–
Natural gas G 20 NCV 9.45 kWh/Sm
3
(8.2 Mcal/Sm
3
)
Column 1
Combustion head pressure drop.
Gas pressure measured at the test point P1)(Fig. 22), with:
•
Combustion chamber at 0 mbar;
•
Burner working at maximum output;
•
Combustion head adjusted as in page 22.
Column 2
Pressure loss at gas butterfly valve 14)(Fig. 4 on page 13) with
maximum opening: 90°.
Calculate the approximate maximum output of the burner in this
way:
–
subtract the combustion chamber pressure from the gas
pressure measured at test point P1)(Fig. 22).
–
Find, in the table Tab. L related to the burner concerned, the
pressure value closest to the result of the subtraction.
–
Read the corresponding output on the left.
Example RS 410/EV FGR with G20 natural gas:
Maximum output operation
Gas pressure at test point P1)(Fig. 22)
= 25.0 mbar
Pressure in combustion chamber
=
5 mbar
25.0 - 5
= 20.0 mbar
A pressure of 20.0 mbar, column 1, corresponds in the table Tab.
L to an output of 2745 kW.
This value serves as a rough guide; the effective output must be
measured at the gas meter.
To calculate the required gas pressure at test point P1)(Fig. 22),
set the MAX output required from the burner operation:
–
find the nearest output value in the table Tab. L for the burner
in question.
–
Read, on the right (column 1), the pressure at the test point
P1)(Fig. 22).
–
Add this value to the estimated pressure in the combustion
chamber.
Example for RS 410/EV FGR with G20 natural gas:
Required burner maximum output operation: 2745 kW
Gas pressure at an output of 2745 kW
= 20.0 mbar
Pressure in combustion chamber
=
5 mbar
20.0 + 5
= 25.0 mbar
Pressure required at test point P1)(Fig. 22).
Tab. L
WARNING
The heat output and gas pressure data in the
head refer to operation with gas butterfly valve
fully open (90°).
kW
1
p (mbar)
2
p (mbar)
G 20
RS 410/EV FGR
595
2
0.3
953
4
0.5
1312
6
0.7
1670
9
1
2028
12
1.3
2387
15
1.7
2745
20
2.2
3103
25
2.7
3462
31
3.3
3820
38
4
RS 51
0/EV FGR
660
3
0
1120
6
0.1
1580
9
0.3
2040
13
0.5
2500
18
0.9
2960
24
1.4
3420
31
2.1
3880
39
3
4340
49
4.1
4800
60
5.4
RS 6
10/EV F
G
R
912
2
0
1461
4
0
2009
6
0.1
2558
10
0.3
3107
14
0.8
3655
19
1.6
4204
25
2.4
4753
32
3.2
5301
40
4
5850
49
4.6
Содержание 20162652
Страница 2: ...Translation of the original instructions...
Страница 45: ...43 20162733 GB Appendix Electrical panel layout...
Страница 46: ...20162733 44 GB Appendix Electrical panel layout 0 1 1 2 1 2 3 1 4 1 2 1 2 2 1 1 1 1 1 51 5 5 1 1 2 3 1 2...
Страница 48: ...20162733 46 GB Appendix Electrical panel layout...
Страница 49: ...47 20162733 GB Appendix Electrical panel layout...
Страница 50: ...20162733 48 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 0 0 0 1 0...
Страница 51: ...49 20162733 GB Appendix Electrical panel layout 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Страница 52: ...20162733 50 GB Appendix Electrical panel layout 0 1 0 1 0 2 0 3 0 0 0 0 0 10 1 0 40 4 4 1 0 0 2 0 5...
Страница 55: ...53 20162733 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3...
Страница 57: ......
Страница 58: ......
Страница 59: ......