25
20162733
GB
Installation
5.12
Gas pressures
5.12.1 Gas feeding line
Key (Fig. 18 - Fig. 19 - Fig. 20 - Fig. 21)
1
Gas input pipe
2
Manual valve
3
Vibration damping joint
4
Pressure gauge with push-button cock
5
Filter
6A Includes:
– Filter
– working valve
– safety valve
– pressure adjuster
6B Includes
– working valve
– safety valve
– pressure adjuster
6C Includes
– safety valve
– working valve
6D Includes:
– safety valve
– working valve
7
Minimum gas pressure switch
8
Leak detection control, provided as an accessory or integrat-
ed, based on the gas train code. In compliance with the EN
676 standard, the leak detection control is compulsory for
burners with maximum outputs over 1200 kW.
9
Gasket, for "flanged" versions only
10 Pressure adjuster
11 Train-Burner adaptor, supplied separately
P2 Upstream pressure of valves/adjuster
P3 Upstream pressure of the filter
L
Gas train, supplied separately
L1 The responsibility of the installer
Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure the fuel interception tap is closed be-
fore performing any operation on the burner.
WARNING
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING
For applications according to the Pressure Equip-
ment Directive PED 2014/68/EU, the installer is
required to provide:
–
suitable means for draining and venting as de-
fined in clause K.10 of DIN EN 676;
–
valve proving system as defined in clause K.
14.4 of DIN EN 676.
L1
L
6A
P2
7
4
P3
3
2
1
8
Fig. 18
D11854
MBC "threaded"
L
L1
P2 6B
7
9
8
4
P3
3
2
1
5
11
Fig. 19
D11855
MBC “flanged”-VGD
L
L1
5
6C
P2
7
3
2
1
8
10
11
9
Fig. 20
D11856
DMV "flanged or threaded"
L
L1
5
6D
P2
7
3
2
1
8
10
11
9
Fig. 21
D11857
CB "flanged or threaded"
Содержание 20162652
Страница 2: ...Translation of the original instructions...
Страница 45: ...43 20162733 GB Appendix Electrical panel layout...
Страница 46: ...20162733 44 GB Appendix Electrical panel layout 0 1 1 2 1 2 3 1 4 1 2 1 2 2 1 1 1 1 1 51 5 5 1 1 2 3 1 2...
Страница 48: ...20162733 46 GB Appendix Electrical panel layout...
Страница 49: ...47 20162733 GB Appendix Electrical panel layout...
Страница 50: ...20162733 48 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 0 0 0 1 0...
Страница 51: ...49 20162733 GB Appendix Electrical panel layout 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Страница 52: ...20162733 50 GB Appendix Electrical panel layout 0 1 0 1 0 2 0 3 0 0 0 0 0 10 1 0 40 4 4 1 0 0 2 0 5...
Страница 55: ...53 20162733 GB Appendix Electrical panel layout 0 1 1 1 1 1 2 2 2 0 2 2 2 2 2 2 2 2 2 2 2 0 2 3...
Страница 57: ......
Страница 58: ......
Страница 59: ......