Installation
5.4
Operating position
5.5
Removal of the locking screws from the shutter
5.6
Preparing the boiler
5.6.1
Boring the boiler plate
Pierce the closing plate of the combustion chamber, as in Fig. 14.
The position of the threaded holes can be marked using the ther-
mal insulation screen supplied with the burner.
5.6.2
Blast tube length
The length of the blast tube must be selected according to the in-
dications provided by the manufacturer of the boiler, and in any
case it must be greater than the thickness of the boiler door com-
plete with its refractory.
For boilers with front flue passes 1)(Fig. 15 on page 18) or flame
inversion chamber, a protection in refractory material 5) must be
inserted between the boiler fettling 2) and the flame funnel 4).
This protection must not compromise the extraction of the blast
tube.
For boilers with a water-cooled front-piece, a refractory lining 2)-
5)(Fig. 15 on page 18) is not necessary, unless expressly re-
quested by the boiler manufacturer.
Tab. H
WARNING
The burner is designed to operate only in
positions
1
,
2
,
3
and
4
Installation
1
is preferable, as it is the only
one that allows the maintenance operations
as described in this manual.
Installations
2
,
3
and
4
permit operation but
make maintenance and inspection of the
combustion head more difficult.
DANGER
Any other position could compromise the cor-
rect operation of the appliance.
Installation
5
is prohibited for safety reasons.
Fig. 12
2
3
4
5
1
D7739
WARNING
Remove the screws and the nuts 1)-2)(Fig. 13),
before installing the burner on the boiler.
Replace them with the screws 3) M12 X 16 sup-
plied with the burner.
1
2
1
2
3
3
Fig. 13
D12015
mm
D1
DF
RS 810/M BLU
400
495
M18
Fig. 14
Ø
45
45
D F
D 1
20149117
Содержание 20155875
Страница 2: ...Translation of the original instructions...
Страница 43: ...41 20163413 GB Appendix Electrical panel layout...
Страница 44: ...20163413 42 GB Appendix Electrical panel layout 0 0 1 0 1 2 0 3 0 1 0 1 1 0 0 0 0 0 40 4 4 0 0 1 2 0 1...
Страница 45: ...43 20163413 GB Appendix Electrical panel layout 0...
Страница 47: ...45 20163413 GB Appendix Electrical panel layout 0 0 1 2 2 2 2 2 2 2 0 0 2 0 2 0 1 2...
Страница 48: ...20163413 46 GB Appendix Electrical panel layout 0 1 2 1 3 4 56 4 6 4 6 5 4 786 9 3 1 2 78 0 0 2 2 2...