Recommended cable lugs
Bolt Size
Wire
Thomas & Betts Connectors
5/16
6 AWG
54136
4 AWG
54140
1/0
54109
2/0
54110
4/0
54112
250 kcmil
54172
3/8
2/0
54160
300 kcmil
54114
400 kcmil
54116
cables
are
to
be
connected
to
the
field
terminals
through
Listed
cable
lugs
suitable
for
cable
size.
When
using
crimp
type
lugs,
follow
the
manufacturer’s
instructions
for
both
crimp
tool
and
lug
Per NEC article 300-20(2), all three-phase conductors must be run in the same conduit. Neutral and ground must be
run in the same conduit as the phase conductors.
Conduit is to be sized to accommodate one neutral conductor the same size as the phase conductor and one ground
conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.
Conduit sizes can be chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, THW-2.