Pag. 78 a 83
0MLMHTK65RUENUB
UPS models
65 kVA
80 kVA
100 kVA
125 kVA
INVERTER
Rated power Pf 0.9 (kVA) inductive
65
80
100
125
Active power Pf 1 (kW)
58.5
72
90
112.5
Power derating (kVA/kW) for Pf =0.8/0.9
capacitive
0.85/0.89
Rated voltage
480Vac 3-phase + N
Rated frequency
60Hz
Voltage range adjustment
+5% -10%
Voltage variation [Static]
± 1%
Voltage variation [Dynamic]
± 5%
Recovery time within ± 1%
20ms
Conforms to standard EN 62040-3, class 1
Crest Factor (Ipeak/Irms)
3:1
Voltage distortion [THD] with linear load
1% (typical), 2% (max)
Voltage distortion [THD] with non linear load
< 3%
frequency synchronization with the bypass mains
(from inverter)
± 2% (adjustable from ± 1% to ± 6% from control panel)
frequency synchronization without the bypass
mains (free-running variation)
± 0.05%
Slew - rate variation
1Hz/sec
Voltage unbalance ratio with balanced and
unbalanced load
≤
1%
Phase angle deviation with balanced and
unbalanced load
120 ± 1 °el
Overload with reference to the rated power:
Three phase
110% for 60min, 125% for 10min, 150% for 1min
Single phase
200% for 7 second
Short circuit current
Phase / Phase
180% for 1 second with current limiting
Phase / Neutral
300% for 1 second with current limiting
Inverter efficiency (%)
95%
Normal mode AC/AC efficiency
93%
Normal mode heat rejection (BTU/Hr)
15,033
18,500
23,120
28,900
UPS models
65 kVA
80 kVA
100 kVA
125 kVA
BYPASS
Rated voltage
480Vac 3-phase + N
Rated voltage range
± 15% (adjustable from ± 10% to ± 25% from control panel)
Rated frequency
60Hz
Frequency range
± 2% (adjustable up to ± 6% from control panel)
Switching onto bypass with synchronized
Inverter (UPS in “Normal Mode”)
~ 0ms
Switching onto bypass with Inverter out of sync
(UPS in “Normal Mode”)
20ms
Switching from bypass to Inverter (UPS in
“Stand-by On mode”)
from 2 to 5ms
Delay in transfer onto Inverter after switching
onto bypass
4 sec
Power overload capacity of the bypass line (kVA)
110 % for 60 minutes, 125 % for 10 minutes, 150 % for 1 minute
Short circuit capacity of the bypass line (x rated
current)
1 second
500 ms
200 ms
100 ms
10 ms
20
23
26
30
40
15
18
21
22
30
12
15
17
18
25
10
12
14
15
20