Pag. 66 a 83
0MLMHTK65RUENUB
1.1.33.4
RATED OUTPUT VOLTAGE.
Press the following sequence of keys to access the menu: 3, 5, 436215, 2
Keys 7 and 8 can be used to decrease or increase the rated output voltage.
The value displayed is the voltage between phase and neutral "Vln". The value set modifies the operation of the
inverter, during normal operation. The new output value voltage also changes the reference value for the acceptable
range of the voltage at the bypass line input.
1.1.33.5 BATTERY
Press the following sequence of keys to access the menu: 3, 5, 436215, 3
Battery: Type=1 Capacity=15Ah
Adjustment: 2-/3+ 5/6=-/+10 7=-,8=+
On initial installation the rated capacity value of the connected battery must be inserted; this value is usually printed
on the battery container.
battery capacity
It is important to insert the correct battery capacity value, since this value is used by the system logic to
calculate the backup time.
If not set otherwise, this value is assumed to be equal to the UPS power. e.g. at 100kVA the value set by
default is 100Ah .
Battery type = for high intensity discharge batteries change from value 1 (normally pre-set for normal
batteries) to value 2; value 3 is to be used for vented batteries.
Cyclical battery recharging (factory-set :
Select type 1 or 2 and then press key 4 to display the pre-set voltage values:
Ac=xxx, Vbat.: min=xxx, Cyc.ON, max=xxx
Bat.type(1) 2=Cycl.->OFF,
Select type 0 and then press key 4 to modify the voltage values reset by keys 3,4 and 7,8.
Ac=xxx, Vbat.: min=xxx, Cyc.ON, max=xxx
Bat.type(0) 2=Cy., 3-/4+, 7-/8+
b
Value set
Modify values
capacity
Code present
Battery type
a
End of discharge
l
Modify
charge type
maximum recharge current
value (function of value of
battery capacity)
Battery type
Cyclical charge ON
Charge voltage