(1) The control box 1) is equipped with a disk 2) that rotates during the starting phase and is visible from the lower side of control box. When the burner does not start,
or locks out, because of a fault, the colour which appears in correspondence with index 3) signals the kind of inconvenience.
COLOUR (1)
FAULT
PROBABLE CAUSE
SUGGESTED REMEDY
The burner does not start
1
- No electrical power supply . . . . . . . . . . . . . . . . . . . . . . . . . Close all switches - Check connections
2
- A limiter or safety control device is open. . . . . . . . . . . . . . . Adjust or replace
3
- Control box lock-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset control box
4
- Control box fuses blown . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
5
- Erroneous electrical connections . . . . . . . . . . . . . . . . . . . . Check connections
6
- Defective control box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
7
- No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Open the manual valves between meter and
train
8
- Mains gas pressure insufficient. . . . . . . . . . . . . . . . . . . . . . Contact your GAS COMPANY
9
- Minimum gas pressure switch fails to close . . . . . . . . . . . . Adjust or replace
10 - Defective motor remote control switch . . . . . . . . . . . . . . . . Replace
11 - Defective electrical motor . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
12 - Motor protection tripped . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset thermal cut-out when third phase is re-
connected
The disk 2) keeps on rotating
13 - Air pressure switch in operating position . . . . . . . . . . . . . . Adjust or replace
BLUE
The burner starts and then locks
out
14 - Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace control box
Air pressure switch inoperative due to
insufficient air pressure:
15 - Air pressure switch adjusted badly . . . . . . . . . . . . . . . . . . . Adjust or replace
16 - Pressure switch pressure point pipe blocked . . . . . . . . . . . Clean
17 - Head wrongly adjusted . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust
18 - High negative draft in chamber . . . . . . . . . . . . . . . . . . . . . . Connect air pressure switch to fan suction inlet
19 - Fault in flame detection circuit. . . . . . . . . . . . . . . . . . . . . . . Replace control box
20 - VS and VR gas valves unconnected or with interrupted coilCheck connections or replace coil
YELLOW
After pre-purge and safety time,
the burner goes to lock-out and
the flame does not appear
21 - The solenoid VR allows little gas through . . . . . . . . . . . . . . Increase
22 - Solenoid valves VR or VS fail to open . . . . . . . . . . . . . . . . . Renew the coil or rectifier panel
23 - Gas pressure too low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Increase pressure at governor
24 - Ignition electrode wrongly adjusted. . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p.14
25 - Electrode grounded due to broken insulation . . . . . . . . . . . Replace
26 - High voltage cable defective . . . . . . . . . . . . . . . . . . . . . . . . Replace
27 - High voltage cable deformed by high temperature . . . . . . . Replace and protect
28 - Ignition transformer defective . . . . . . . . . . . . . . . . . . . . . . . Replace
29 - Erroneous valve or transformer electrical connections . . . . Check
30 - Control box defective. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
31 - A cock down-line of the gas train is closed . . . . . . . . . . . . . Open
32 - Air in pipework. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bleed air
YELLOW
The burner goes to lock-out right
after flame appearance
33 - The solenoid VR allows little gas through . . . . . . . . . . . . . . Increase
34 - Ionisation probe wrongly adjusted. . . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p. 14
35 - Faulty electrical connections for probe . . . . . . . . . . . . . . . . Repeat connection
36 - Insufficient ionisation (less than 5 mA) . . . . . . . . . . . . . . . . Check probe position
37 - Probe grounded . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Withdraw or replace cable
38 - Burner poorly grounded . . . . . . . . . . . . . . . . . . . . . . . . . . . Check grounding
39 - Phase and neutral wires inverted . . . . . . . . . . . . . . . . . . . . Correct by inverting
40 - Defective control box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
The burner repeats the starting
cycle without lock out
41 - Mains gas pressure is near the value to which the . . . . . . . Reduce operating pressure
min. gas pressure switch gas is adjusted. The
of minimum gas pressure
repeated drop in pressure which follows valve
switch.
opening causes temporary opening of the pressure
Replace gas filter
switch itself, the valve immediately closes and the
burner comes to a halt. Pressure increases again, the
pressure switch closes again and the firing cycle is
repeated. The sequence repeats endlessly.
Ignition with pulsation
42 - Poorly adjusted head. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust, see page 17
43 - Ignition electrode wrongly adjusted. . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p.14
44 - Poorly adjusted fan air gate: too much air . . . . . . . . . . . . . Adjust
45 - Output during ignition phase is too high . . . . . . . . . . . . . . . Reduce
RED
GREEN
The burner does not pass to 2nd
stage
46 - Remote control device TR does not close. . . . . . . . . . . . . . Adjust or replace
47 - Defective control box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
48 - Servomotor faulty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
Burner locks out at transition
between 1st and 2nd stage or
between 2nd and 1st stage
49 - Too much air or too little gas . . . . . . . . . . . . . . . . . . . . . . . . Adjust air and gas
During operation, the burner stops
in lock out
50 - Probe or ionisation cable grounded . . . . . . . . . . . . . . . . . . Replace worn parts
51 - Fault on air pressure switch . . . . . . . . . . . . . . . . . . . . . . . . Replace
Lock out when burner stops
52 - Flame remains in combustion head . . . . . . . . . . . . . . . . . . Eliminate persistence of flame
or flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . or replace control box
Burner stops with air gate valve
open
53 - Servomotor faulty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace