TECHNICAL DATA

 

2.1

TECHNICAL DATA

2.2

OVERALL DIMENSIONS

2.3

WORKING FIELD  

 

(as EN 267)

TYPE

399 T1

 

Output  - Thermal power

13.5

 

 

26.1 kg/h

-

160

 

 

309.5 kW

Fuel

Light oil, viscosity  4 –

 

 

 

6 mm

 

2

 

/s at  20 °C

Electrical supply

Single phase, 

 

~

 

50Hz 230 V 

 

±

 

 10%

Motor

Run current

2.1 A

2730 rpm

286 rad/s

Capacitor

 

µ

 

F

Ignition transformer

Secondary

8 kV

16 mA

Pump

Pressure:

8

 

 

15 bar

Absorbed electrical power

0.47 kW

247

155

300

213

160

190

12,5

36

285

345

11

99

99

127

45°

45°

D5390

ø

 

125

0

Fuel output – kg/h

150

170

190

Thermal power –  kW

4

3

2

1

Pressure in comb

ustion

c

hamber – mbar

D6230

12

210

230

14

16

18

20

270

22

24

26

250

290

310

Содержание RG3 393T1

Страница 1: ...e gebruiks en onderhoudsvoorschriften Montage und Bedienungsanleitung O l Gebl sebrenner Br leur fioul Light oil burner Stookoliebrander CODE MODELL MODELE MODEL TYP TYPE 3739950 RG5S 399 T1 D F GB NL...

Страница 2: ...ng 5 4 WORKING 6 4 1 Combustion adjustment 6 4 2 Recommended nozzles 6 4 3 Combustion head setting 7 4 4 Electrodes adjustment 7 4 5 Pump pressure and air output 7 4 6 Burner start up cycle 8 5 MAINTE...

Страница 3: ...cal supply Single phase 50Hz 230V 10 Motor Run current 2 1A 2730 rpm 286 rad s Capacitor 8 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 8 15 bar Absorbed electrical power 0 47 kW 247 155...

Страница 4: ...sing screws 5 and if necessary the nuts 2 interposing the insulating gasket 4 see fig 2 After installation ensure that burner is lightly inclined as in fig 5 3 2 FUEL SUPPLY The burner is designed to...

Страница 5: ...8 it is sufficient to loosen the suction gauge connection 6 fig 7 and wait until oil flows out On the systems in fig 9 and 10 start the burner and wait for the priming Should lock out occur prior to...

Страница 6: ...UTRAL WITH PHASE 7 pin plug 7 pole socket Black White Capacitor Main switch T6A Motor Blue Oil valve Hour counter 230V 0 1A max Limit thermostat Remote lock out signal 230V 0 5A max Ignition electrode...

Страница 7: ...inen type S Danfoss type S TO FIT NOZZLE CARRY OUT THE FOLLOW ING ACTIONS see fig 12 Remove nozzle holder assembly 1 after loosing screws 2 and nut 3 remove the small cables 4 from the control box and...

Страница 8: ...ure automatically brought to the air flow required for the big flame SETTING FOR THE LOW IGNITION FLAME See fig 14 ADJUSTMENT OF AIR SHUTTER Unloosen the screw 8 by approximately one full turn in this...

Страница 9: ...ve consumption of fuel and consequent pollution Before carrying out any cleaning or control always first switch off the electrical supply to the burner acting on the main switch of the system THE BASI...

Страница 10: ...the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner doesn t start when the limit thermostat closes Lack of electrical supply Check presence of voltage in the L1 N clam...

Отзывы: