FAULTS / SOLUTIONS

Here below you can find some causes and the possible solutions for some problems that could cause a fail-
ure to start or a bad working of the burner.

A  fault usually makes  the  lock-out  lamp  light  which  is  situated  inside the reset button of the control box
(3, fig. 1, page 1).

When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the
burner functions correctly, the lock-out can be attributed to a temporary fault.
If however the lock out continues the cause must be determined and the solution found. 

WARNING

The manufacturer cannot accept responsibility for any damage to persons, animals or property due to error
in installation or in the burner adjustment, or due to improper or unreasonable use or non observance of the
technical instruction enclosed with the burner, or due to the intervention of unqualified personnel.

FAULTS

POSSIBLE CAUSES

SOLUTION

The burner doesn’t
start when the limit
thermostat closes.

Lack of electrical supply.

Check presence of voltage in the 
L1 - N clamps of the 7 pin plug.

Check the conditions of the fuses.

Check that safety thermostat is not 
lock out.

The photoresistance sees false light.

Eliminate the light.

Start thermostats are faulty.

Replace them.

The connections in the control box 
are wrongly inserted.

Check and connect completely all the
plugs.

Burner runs normal-
ly in the prepurge
and ignition cycle
and locks out after 5
seconds ca.

The photoresistance is dirty.

Clear it.

The photoresistance is defective.

Change it.

Flame moves away or fails.

Check pressure and output of the fuel.

Check air output.

Change nozzle.

Check the coil of solenoid valve.

Burner starts with an
ignition delay.

The ignition electrodes are wrongly 
positioned.

Adjust them according to the
instructions of this manual.

Air output is too high.

Set the air output according to the 
instructions of this manual.

Nozzle dirty or worn.

Replace it.

Содержание RG3 393T1

Страница 1: ...e gebruiks en onderhoudsvoorschriften Montage und Bedienungsanleitung O l Gebl sebrenner Br leur fioul Light oil burner Stookoliebrander CODE MODELL MODELE MODEL TYP TYPE 3739950 RG5S 399 T1 D F GB NL...

Страница 2: ...ng 5 4 WORKING 6 4 1 Combustion adjustment 6 4 2 Recommended nozzles 6 4 3 Combustion head setting 7 4 4 Electrodes adjustment 7 4 5 Pump pressure and air output 7 4 6 Burner start up cycle 8 5 MAINTE...

Страница 3: ...cal supply Single phase 50Hz 230V 10 Motor Run current 2 1A 2730 rpm 286 rad s Capacitor 8 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 8 15 bar Absorbed electrical power 0 47 kW 247 155...

Страница 4: ...sing screws 5 and if necessary the nuts 2 interposing the insulating gasket 4 see fig 2 After installation ensure that burner is lightly inclined as in fig 5 3 2 FUEL SUPPLY The burner is designed to...

Страница 5: ...8 it is sufficient to loosen the suction gauge connection 6 fig 7 and wait until oil flows out On the systems in fig 9 and 10 start the burner and wait for the priming Should lock out occur prior to...

Страница 6: ...UTRAL WITH PHASE 7 pin plug 7 pole socket Black White Capacitor Main switch T6A Motor Blue Oil valve Hour counter 230V 0 1A max Limit thermostat Remote lock out signal 230V 0 5A max Ignition electrode...

Страница 7: ...inen type S Danfoss type S TO FIT NOZZLE CARRY OUT THE FOLLOW ING ACTIONS see fig 12 Remove nozzle holder assembly 1 after loosing screws 2 and nut 3 remove the small cables 4 from the control box and...

Страница 8: ...ure automatically brought to the air flow required for the big flame SETTING FOR THE LOW IGNITION FLAME See fig 14 ADJUSTMENT OF AIR SHUTTER Unloosen the screw 8 by approximately one full turn in this...

Страница 9: ...ve consumption of fuel and consequent pollution Before carrying out any cleaning or control always first switch off the electrical supply to the burner acting on the main switch of the system THE BASI...

Страница 10: ...the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner doesn t start when the limit thermostat closes Lack of electrical supply Check presence of voltage in the L1 N clam...

Отзывы: