GB

4.

WORKING

4.1

COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and
testing must be carried out observing the instruction manual of the boiler, including verification of the CO and
CO

2

 concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.

To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the setting of
the combustion head, and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 267).
They refer to 12.5% CO

2

 at sea level and with light oil and room temperature of 20 °C. 

4.2

RECOMMENDED NOZZLES:  

 

  

 

 

Monarch type  R
Delavan type W 

(up to  3,00 GPH)

Delavan type B 

(over   3,00 GPH)

Steinen type S;

Danfoss 

type 

S.

TO FIT NOZZLE CARRY OUT THE FOLLOW-
ING ACTIONS, (see fig. 12)

Remove nozzle-holder assembly (1) after
loosing screws (2) and nut (3), remove the
small cables (4) from the control box and the
photoresistance (5).

Withdraw the small cables (4) from the elec-
trodes, remove the diffuser disc-holder as-
sembly (8) from the nozzle-holder assembly
(1) after loosing screw (3, fig. 13, page 7).

Screw the nozzle (9) correctly and tighten it as
shown in fig. 12.

Attention
During the reassembly of the nozzle-holder as-
sembly screw the nut (3) as shown in the figure
below. 

Nozzle

Start delaying 

device pressure

Pump

pressure

Burner

output

Combustion

head

adjustment

Air damper adjustment

Low-flame

High-flame

Low-flame

High-flame

GPH

Angle

bar

bar

kg/h ± 4%

Set-point

Set-point

Set-point

3.00

60°

9

15

13.5

0

0.4

1.3

3.50

60°

9

15

15.7

0

0.5

2.0

4.00

60°

9

15

18.0

2

0.7

2.5

4.50

60°

9

15

20.2

4

0.8

3.0

5.00

60°

9

15

22.4

6

0.9

3.7

5.50

60°

9

15

24.7

8

1.1

5.8

6.00

60°

9

14

26.0

10

1.3

6.0

SW1007

Fig. 12

3

TIGHTEN WITHOUT MOVING 
BACKWARDS TO THE END

D5684

Содержание RG3 393T1

Страница 1: ...e gebruiks en onderhoudsvoorschriften Montage und Bedienungsanleitung O l Gebl sebrenner Br leur fioul Light oil burner Stookoliebrander CODE MODELL MODELE MODEL TYP TYPE 3739950 RG5S 399 T1 D F GB NL...

Страница 2: ...ng 5 4 WORKING 6 4 1 Combustion adjustment 6 4 2 Recommended nozzles 6 4 3 Combustion head setting 7 4 4 Electrodes adjustment 7 4 5 Pump pressure and air output 7 4 6 Burner start up cycle 8 5 MAINTE...

Страница 3: ...cal supply Single phase 50Hz 230V 10 Motor Run current 2 1A 2730 rpm 286 rad s Capacitor 8 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 8 15 bar Absorbed electrical power 0 47 kW 247 155...

Страница 4: ...sing screws 5 and if necessary the nuts 2 interposing the insulating gasket 4 see fig 2 After installation ensure that burner is lightly inclined as in fig 5 3 2 FUEL SUPPLY The burner is designed to...

Страница 5: ...8 it is sufficient to loosen the suction gauge connection 6 fig 7 and wait until oil flows out On the systems in fig 9 and 10 start the burner and wait for the priming Should lock out occur prior to...

Страница 6: ...UTRAL WITH PHASE 7 pin plug 7 pole socket Black White Capacitor Main switch T6A Motor Blue Oil valve Hour counter 230V 0 1A max Limit thermostat Remote lock out signal 230V 0 5A max Ignition electrode...

Страница 7: ...inen type S Danfoss type S TO FIT NOZZLE CARRY OUT THE FOLLOW ING ACTIONS see fig 12 Remove nozzle holder assembly 1 after loosing screws 2 and nut 3 remove the small cables 4 from the control box and...

Страница 8: ...ure automatically brought to the air flow required for the big flame SETTING FOR THE LOW IGNITION FLAME See fig 14 ADJUSTMENT OF AIR SHUTTER Unloosen the screw 8 by approximately one full turn in this...

Страница 9: ...ve consumption of fuel and consequent pollution Before carrying out any cleaning or control always first switch off the electrical supply to the burner acting on the main switch of the system THE BASI...

Страница 10: ...the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner doesn t start when the limit thermostat closes Lack of electrical supply Check presence of voltage in the L1 N clam...

Отзывы: