5.3.2 Draining Both Cooling Circuits
Do not drain the system before the unit has been switched off and disconnected from
the power supply!
Do not allow the water/glycol solution to get into the sewer system!
Prior to opening the fill and drain valves make sure that the emerging cooling
medium can be disposed of in a way that no damage to the unit and the connected
components can occur!
5. Assembly
ENGLISH
Step
Primary Circuit
Secondary Circuit
1
2
3
Connect suitable transparent hoses to the fill
and drain valves (1) &( 4) and submerge them
in a canister.
Caution:
The water/glycol solution must not be disposed
of in the sewer system!
Connect suitable transparent hoses to the fill
and drain valves (1) &( 4) and submerge them
in a canister.
4
5
Carefully open the screwed connections (6)
once no more liquid emerges.
Caution:
Do not open the connections completely until
the circuit has been completely drained.
Carefully open the screwed connections (7)
once no more liquid emerges.
Caution:
Do not open the connections completely until
the circuit has been completely drained.
6
7
8
The hose connections can now be removed from the unit.
Caution:
It is possible that minor residues of the cooling medium are still present in the system!
Close ball valve (2)
Turn off cooling system using the main switch and take proper lock-out measures.
Open the fill and drain valves (1) & (4)
Once no more liquid emerges at the fill and drain valves (1) & (4), re-close the ball valves (2) &
(3) just like all the other fill and drain valves.