25
454107.66.01-02_GB
01.07.2015
Translation of the Original
Code
Description
Item
F01
alarm motor protection compressor 1
Q2
F02
alarm motor protection compressor 2
Q3
F03
B11
F04
B10
F05
alarm motor protection secondary pump
Q4
F06
alarm motor protection primary pump
Q5
F07
alarm motor protection glycol fans
Q1
F08
alarm thermostat relay glycol fans
M4/ M5
F11
warning - temp. sec. out of tolerance
B1
F12
warning - temp. sec. out of tolerance
B1
F14
alarm - temp. sec. - shutdown system
B1
F16
alarm - temp. sec. - shutdown system
B1
F15
alarm - temp. sec. - shutdown system
B1
F17
sensor defect - temperature secondary water out
B1
F27
sensor defect - temperature secondary water in
B2
F31
warning - temp. prim. out of tolerance
B3
F32
warning - temp. prim. out of tolerance
B3
F34
alarm - temp. prim. - shutdown system
B3
F36
alarm - temp. prim. - shutdown system
B3
F35
alarm - temp. prim. - shutdown system
B3
F37
sensor defect - temp. primary glycol inlet
B3
F47
error - identification cooling type
B4
F51
warning - pressure sec. out of tolerance
B5
F52
warning - pressure sec. out of tolerance
B5
F54
alarm - pressure sec. - shutdown system
B5
F55
alarm - pressure sec. - shutdown system
B5
F57
sensor defect - pressure sec.
B5
F71
warning - pressure prim. out of tolerance
B7
F72
warning - pressure prim. out of tolerance
B7
F74
alarm - pressure prim. - shutdown system
B7
F75
alarm - pressure prim. - shutdown system
B7
F77
sensor defect - pressure prim.
B7
Error Codes on Sisplay Controller Board:
9. Malfunctions / Troubleshooting
ENGLISH
HP alarm
LP alarm