EL232 XCPD Installation Manual

 

3.3.1

Loss of Signal Display

 

Press the Reset switch to enter new values into the
E L 2 3 2   X P C D ,   o r   t u r n   o ff   t h e   p ow e r,   o r   wa i t
approximately 30 seconds and the EL232 XPCD will
reset itself. 

The following tables illustrate switch settings for the
loss of signal display.

3.4

Serial Data Output

The EL232 XPCD comes standard with an active 20
mA current loop transmitter which echoes the serial
data received by the EL232 XPCD. This data is
echoed as a 20 mA loop regardless of whether the
input source was RS232 or current loop.

The output is active and supplies current from a
voltage source of approximately 8 VDC. The current
transmitter is an HP-4100 and can transmit data
cleanly at 9600 baud. The HP-4100 supplies mark
currents of >12 mA and space currents of <2 mA.

Certain scale industry remote displays and printers use
darlington type optocouplers as input devices.
Unbiased 4N33 type opto isolators can be turned on
by 2 mA. These are not true current loop receivers. If
a device which the EL232 XPCD is transmitting to
cannot properly receive the data, change the 4N33 to a
4N25 opto isolators and the problem will normally
disappear.

Figure 3-10 illustrates how to connect the current loop
output of the EL232 XPCD.

Figure 3-10. 20 mA Active Current Loop Output

You can check the current loop output with a simple
jumper connected between pin J2-3and J2-4. The
LED on the CPU should flash on and off when data is
transmitted.

Note:

 When using a passive current loop input, the serial

output is not available. Consult the factory for additional
information. 

Indicator

Indicator Type

SW1-3

SW1-4

SW1-5

SW1-6

Condec

On

On

On

On

General Freedom

Off

On

On

On

Electro 560

On 

Off

On

On

A n D

Off 

Off

On

On

WI-110, WI-120

On

On 

Off

On

Toledo

Off

On

Off

On

Flexweigh

On

Off

Off

On

Analogic

Off

Off

Off

On

Masstron

On

On

On

Off

Fairbanks

Off

On

On

Off

Streeter Richardson

On

Off

On

Off

Cardinal 738

Off

Off

On

Off

Generic

Off

Off

Off

Off

Table 3-3. Indicator Switch Settings

Loss of Signal Display

Display

SW1-7

Last data

Off

- - - - - - 

On

Table 3-4. Loss of Signal Display

Input Signal Type

Interface

SW1-8

RS232

On

20 mA

Off

Table 3-5. Input Signal Type

GND

PRINT

K4

K3

K2

K1

+5V

CL4 IN-

CL4 IN+

CL3 IN-

CL3 IN+

CL2 IN-

CL2 IN+

CL1 IN (-)

CL(+) OUT

J2

CL(-) OUT

CL1 IN (+)

RS-232 (+)

RS-232 (-)

Содержание EL232 XPCD

Страница 1: ...16942 EL232 XPCD Explosion Proof Remote Display Installation Manual To be the best by every measure...

Страница 2: ......

Страница 3: ...t 14 3 2 Serial Data Input 14 3 2 1 RS232 C 14 3 2 2 20 mA Active Current Loop Input 15 3 2 3 20 mA Passive Current Loop Input 16 3 3 Configuration of the EL232 XPCD 17 3 3 1 Loss of Signal Display 18...

Страница 4: ...2 ES232 XPCD Installation Manual...

Страница 5: ...in this manual Improper specification installation or service of this equipment could result in personal injury or property damage Read all of the manual prior to installation Do not assume that all h...

Страница 6: ...DOUS AREA High temperature gases Cooling from conduction of heat along the threads There must be a minimum of five full threads of engagement of a 2 A 2 B fit for a Group C enclosure Group B increases...

Страница 7: ...that enclosure s rating Explosion HAZARDOUS AREA High temperature gases Cooling from expansion of gas Boyle s Gas Law The distance from the boundary of the inside of the enclosure to the gasket is kn...

Страница 8: ...4 EL232 XPCD Installation Manual...

Страница 9: ...323 4316 Weightronix WI 110 and WI 120 Toledo indicators with High speed data format Flex weigh DWM 4 Analogic AN5315 AN5316 AN5322 Masstron M 2500 and M 5000 Fairbanks 90 164 series Streeter Richards...

Страница 10: ...display digits and five LED annunciators Figure 1 1 EL232 XPCD Front Panel CLASS I DIVISION 2 GROUP C D CLASS II DIVISION 1 GROUP E F G TO PREVENT IGNITION OF HAZ ATMOS DISCONNECT O RE O PENING KEEP...

Страница 11: ...the enclosure It is recommended to shelter the outdoor installation by a shelter roof enclosure or covering Moist environments can also be controlled by the use of desiccants Contact your local dealer...

Страница 12: ...ain relief fitting to avoid pulling the wires out of the sealoff fittings in an accident Doing so would open a flame path to the enclosure and defeat its purpose Note The inside of an explosion proof...

Страница 13: ...he explosion proof enclosure is allowed to vent internal pressure appropriately the outer insulation must be removed back to the point ahead of entry into the safe area Multi conductor cables will pas...

Страница 14: ...amp with a blunt stick to expel any air bubbles Install and tighten filling opening cover Fittings requiring more than 16 oz of cement must be filled from a single mixture of cement and water Do not p...

Страница 15: ...ems Connect the black wire AC Hot to terminal strip J1 3 on the CPU board located in the bottom of the enclosure shown below Figure 2 3 J1 Location on CPU Board Connect the neutral wire white to termi...

Страница 16: ...lectrical way that data is transmitted The EL232 XPCD can read the data transmission strings sent by 12 of the more popular scale indicator families as shown in Table 3 1 It cannot read data from indi...

Страница 17: ...oop or RS232 using S3 10000100 1200 to 9600 See Figure 3 4 Generic smart receiver N A RS232 or current loop 1200 to 9600 Can receive serial data in a wide variety of intuitive formats Use when all els...

Страница 18: ...e connects the ground planes of the sending and receiving instruments RS232 should never be run more than 50 feet It may work but it may not work well or all the time Long RS232 data cables can act as...

Страница 19: ...current loop means that the instrument which sends the data also supplies the voltage to power the loop This voltage can be as small as 5 VDC to as much as 24 VDC When the loop goes through an optoco...

Страница 20: ...n external power supply or receiver This voltage can be a small as 5 VDC to as much as 24 VDC When the loop goes through an optocoupler a drop occurs This drop is about 2 VDC A current loop can power...

Страница 21: ...able indicators The power must be off when these values are changed If the power is on press the Reset switch on the CPU board to enter the new values see Figure 3 9 Figure 3 9 Reset Switch Location J...

Страница 22: ...transmitting to cannot properly receive the data change the 4N33 to a 4N25 opto isolators and the problem will normally disappear Figure 3 10 illustrates how to connect the current loop output of the...

Страница 23: ...ng The EL232 XPCD next shows the current baud rate setting it had read from switch SW1 The display shows bAUd12 for 1200 baud bAUd24 for 2400 baud bAUd48 for 4800 baud or bAUd96 for 9600 baud 4 4 Inpu...

Страница 24: ...SW1 07 is open the last value received is displayed continuously If this switch is closed the display again shows until readable data is again received This can be used to alert the operator that dat...

Страница 25: ...indicator incompatability mis wiring and mis programming both in the indicator and in the EL232 XPCD setup Double check the output of the meter and make sure something is being transmitted Use an osc...

Страница 26: ...ately 25 lb 11 3 kg Baud Rate 1200 2400 4800 and 9600 Interfaces 20 mA and RS232 standard The EL232 XPCD can communicate as shipped with twelve of the most common scale indicator families currently av...

Страница 27: ...accident misuse neglect alteration improper installation improper repair or improper testing RLWS shall be the sole judge of all alleged non conformities Such equipment has not been modified altered...

Страница 28: ......

Страница 29: ......

Страница 30: ...230 W Coleman St Rice Lake WI 54868 USA U S 800 472 6703 Canada Mexico 800 321 6703 International 715 234 9171 www ricelake com mobile m ricelake com 2011 Rice Lake Weighing Systems PN 16942 06 11...

Отзывы: