background image

34

34

G

B

OPEN BUTTON (COM-OPEN)

The button controls the opening movement when the gate is stationary. If activated while closing, it reopens the gate.

CLOCK FUNCTION OF OPEN BUTTON

If you want the Clock Function must request T2 24V with firmware 02.

ATTENTION:  A  CLOCK  CONNECTED  TO  T2  24V  with  fw  03  or  more  ACTIVATES  THE  OPENING 

MOVEMENT OF THE GATE WITHOUT HAVING THE PROTECTION OF THE SAFETY DEVICES!

This function is useful during peak hours, when vehicle traffic is slow (e.g. entry/exit of workers, emergencies in 

parking or residential areas and, temporarily, for moving operations).

CLOCK FUNCTION APPLICATION

It is necessary to request a T2 24V control panel with firmware 02.

 By connecting a switch and/or a daily/weekly 

clock (instead of or in parallel to the open button N.O. “COM-OPEN”), you can open and keep the automation open 

for as long as the switch is pressed or the clock remains active. Command functions are inoperative with open 

automation. Releasing the switch or at the preset time, the automation closes immediately.

CLOSE BUTTON (COM-CLOSE)

Controls the closing movement when the gate is stationary.

REMOTE CONTROL

If DIP6 ON =>

   It cyclically performs the commands open-stop-close-stop-open etc.

If DIP6 OFF =>

  Opens the gate when closed. There is no effect if activated while opening. If activated when gate is 

open, the gate closes. If activated while closing, the gate reopens.

PEDESTRIAN OPEN BUTTON (COM-PED.BUTT.)

Partial opening and closing control.

During pedestrian opening, pausing or closing, you can control the opening of any command linked to the T2 24V 

board. With DIP 6 you can choose the operation mode of the pedestrian push button.

If DIP6 ON =>

   It cyclically performs the commands open-stop-close-stop-open etc.

If DIP6 OFF =>

  Opens the gate when closed. There is no effect if activated while opening. If activated when gate is 

open, the gate closes. If activated while closing, the gate reopens.

 

ELECTRIC LOCK (LOCK)

Set DIP 8 to ON to enable control of the electric lock when opening.

ELECTRIC LOCK PULSE RELEASE IN OPENING

Set DIP 9 to ON to enable the electric lock pulse release when opening (provided DIP 8 is ON).

If a command to open the gate is given when the gate is closed, the closing movement is performed for 0.5 seconds 

and the electric lock is simultaneously activated (followed by a 0.5 second pause and then the opening of the gate).

ELECTRIC LOCK PULSE ENGAGEMENT

Set DIP 10 to ON to enable the pulse engagement of the electric lock when closing. Upon closing, motors are 

activated for 0.5 seconds at full voltage to ensure lock engagement. 

EASY MOTOR RELEASE

Set DIP 11 to ON to enable easy manual release (provided that DIP 10 is ON), upon closing a reverse motion with a 

fixed time of 0.2 seconds occurs to facilitate manual release.

O

PERATION OF SAFETY ACCESSORIES

PHOTOCELL (COM-PHOT)

DIP 4 OFF =>  

if an obstacle is placed in range of the photocells when the gate is closed, the gate does not open. 

During  operation,  photocells  work  when  opening  (by  starting  the  opening  movement  only  after 

the obstacle is removed) and closing (by starting the reverse movement only after the obstacle is 

removed).

DIP 4 ON =>   

if an obstacle is placed in range of the photocells when the gate is closed and the command to open is 

given, the gate opens (the photocells do not work while opening). Photocells work only during closing 

(with reverse motion restored after a second, even if they are still engaged).

CONTROL OF IMMEDIATE CLOSING AFTER MOVEMENT IN FRONT OF PHOTOCELLS

DIP 16 ON and DIP 4 OFF =>   

if photocells are engaged during opening, the gate stops and the gate only closes one 

second after the photocells are disengaged.

DIP 16 ON and DIP 4 ON =>   

if  photocells  are  engaged  during  opening,  the  gate  continues  to  open.  Upon 

disengagement of the photocells, the gate stops and reverses closing motion after a 

one second pause.

 

 If  total  opening  is  reached  (end  of  opening  time),  immediate  closing  is 

deactivated  and  automatic  time  closing  is  activated  (if  TCA  trimmer  is 

activated and LED DL6 is on). If during closing there is a rapid movement (e.g. 

pedestrian) the gate will open again for two seconds and then close once again.

DIP 12 OFF => 

 

immediate closing after movement in front of the photocells is deactivated.

N.B.:

 Please check photocell operation at least every six months.

EDGE (SAFETY STRIP) (COM-EDGE)

If engaged during opening, reverses the motion when closing.

If engaged when closing, reverses the motion when opening.

If it remains engaged again, it performs a further reversal after 2 seconds, then performs an additional short reversal 

and then gives the sensor failure or engaged alarm (N.O. contact).

If the sensor remains engaged (N.O. contact) no movement is allowed. 

If not used, jump the terminals COM-EDGE.

MONITORING OF SAFETY SENSORS (A+ TEST A-)

Sensors can be monitored through the A+ TEST input and DIP 12 ON.

The monitoring consists of a functional test of the sensor run after every full gate opening.

Closing the gate is therefore permitted only if the sensors have passed the functional test after each opening.

CAUTION:

 MONITORING OF THE SENSOR INPUT CAN BE ACTIVATED WITH DIP 12 ON OR DEACTIVATED 

WITH  DIP  12  OFF.  IN  FACT,  THE  FUNCTIONAL  TESTING  OF  SENSORS  IS  ‘POSSIBLE  ONLY  IF  THESE 

DEVICES HAVE THEIR OWN POWER SUPPLY.

A MECHANICAL SENSOR CAN NOT BE MONITORED, SO DIP 12 SHOULD BE SET TO OFF.

SENSOR AUTOTEST ALARM (DIP 12 ON)

If the sensor fails the monitoring test after opening, an alarm is displayed by the blinker lighting up. Gate closure 

is not allowed in this condition. Normal operation can be restored only by repairing the sensor and pressing one of 

the activated controls.

STOP BUTTON (COM-STOP)

The STOP button stops the gate during any operation.

If held when the gate is fully open (or partially when using the pedestrian control) automatic closing is temporarily 

deactivated (if activated by the TCA trimmer and LED DL6 on). It is therefore necessary to use a new command to 

make it close.

The automatic closing function is reactivated on the next cycle (if activated by the TCA trimmer and LED DL6 on).

POWER SENSOR ALARM

The T2 24V control panel has automatic sensors that make the movement of the gate reverse in case of impact 

against  objects  or  persons  in  accordance  with  the  current  EN  standards  (always  use  the  right  tool  to  ensure 

compliance with the values imposed by the standard), without special adjustments on the control panel, as it operates 

using special internal software. If the power sensor is used in opening or closing (only in high-speed) and then again, 

in the opposite direction, the gate stops and then reverses for 1 second. 

The alarm status will be displayed by the blinker which will remain active for one minute, during which time you can 

restore gate operation by pressing any command button.

FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING

If the safety edge fails or remains engaged for more than 5 seconds, or if photocell fails or remain engaded for more 

than 60 seconds,  the open, close, k button and pedestrian commands will work only in dead man mode.

The signal that this mode has been activated is given by the blinking of the programming led.

With the blinking of the programming led, the opening and closing operation are allowed only with the command 

button pressed and held. The radio commands and that of automatic closing, will be excluded, since their use in this 

mode, is not allowed by the norms.

Once the failing safety device is repaired,  in automatic after 1 second, all standard commands that were selected, 

such as step by step, automatic mode, radio commands and automatic closing start functioning again.

Note 1:

  during this functioning in dead man mode, in case of damage to the safety strips (or photocells) the photocells 

(or safety strips) still work by interrupting the operation in progress.

Note 2:

  the stop command is not to be considered a safety command that can be bypassed in this mode. Therefore, 

when pressed or damaged, it will not allow any movement of the gate.

The dead-man operation is only an emergency operation which must be activated for a very short period and 

with the complete installation at sight so to have a secure and safe control of the system. As soon as possible 

however, the failing safety devices must be repaired and activated.

BLINKER

N.B.:

 This control panel can power ONLY BLINKERS ON A (ACG7061) CIRCUIT with lamps up to 24V and 20W.

PRE-BLINKING

DIP 5 - OFF => the motor and blinker begin simultaneously.

DIP 5 - ON => the blinker begins 3 seconds before the motor.

GATE OPEN WARNING LIGHT (COM-SIGNAL)

Signals when the gate is open, partially open or not closed completely. Turns off only when the gate is completely 

closed. This signal is active during programming. 

N.B.: 

Max 3 W. If push buttons or lamps are in excess, the control 

panel processes will be endangered and possibly halt operation.

 

OPERATION AFTER A BLACK-OUT (WITHOUT BATTERIES)

When the power supply comes back the DL1 led turns on and remains on for all the time the gate stays open. The led 

will turn off only once the gate is completely closed. It is recommended to fully open the gate. Let the gate close by 

itself or with automatic closing, or wait until the blinker stops flashing before commanding it to close.

This will allow the gate to realign. If, motors were released and moved from the normal position when closed during 

the blackout, the first movement after power returns must be complete.

If the black out occurs when the gate is still moving or when the gate is open and the first command sent after the 

black out is a closing command, the closing of the gate will be carried out with a total delay between the two gate 

leaves. Therefore, first the leaf M2 will close completely; once it is off, M1 will start closing. This separate movement 

of the two gate leaves is done to avoid their incorrect overlapping.

T

ECHNICAL SPECIFICATIONS

- Temperature range 

0 ÷ 55°C

- Humidity 

 <95% without condensation

- Voltage 

230V~ ± 10%   (120V/60Hz upon request)

- Frequency 

50/60 Hz

Содержание PRINCE 24V

Страница 1: ...31 a richiesta on request Peso max anta Poids maxi battant Max leaf weight Max Torgewicht Peso max hoja 250 kg 550 lbs Spinta Pouss e Thrust Schubkraft Empuje 100 kg 220 lbs Spinta max Pouss e maxi Ma...

Страница 2: ...e Operating speed Power supply Nominal Motor capacity Max Motor capacity blocked Nominal Power absorbed Max Power absorbed blocked Nominal Thrust force Max Thrust force blocked Normative cycles Daily...

Страница 3: ...ning in the gate frame and the side wall EMERGENCY MANUAL RELEASE This applies only if the unit is not equipped with back up batteries In case of a black out the gate can be pulled open after the oper...

Страница 4: ...1 2 90 L Min Max A max T sec COL ANT B C D E 110 0 100 100 765 90 13 5 S2 X A 20 100 100 765 90 13 5 S2 Y A 40 100 100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100...

Страница 5: ...r A in the needed position by tightening the 8mA screw with a n 13 key To obtain the desired closing limit you must adjust the stopper B OPTIONAL in the needed position and tighten it as for stopper A...

Страница 6: ...ELLS STEP BY STEP COMMON COMMON 24Vdc 0 8A 15 for ACCESSORY SUPPLY 24Vdc 0 8A 15 for AUTOTEST SAFETY STRIPS BLINKER 24Vdc 20W LED R 2 2K 1 4W ELECTRIC LOCK PEDESTRIAN SAFETY STRIPS POWER SUPPLY 230Vac...

Страница 7: ...t clockwise increases the speed Adjustment is performed to determine the correct speed at the end of opening and closing according to the gate or when there is friction that might cause the system to...

Страница 8: ...button M1 stops 5 Press the PROG button M1 closes At the same time LED DL1 stops flashing indicating exit from the programming procedure Safety and other gate commands now operate normally inversions...

Страница 9: ...the sensor run after every full gate opening Closing the gate is therefore permitted only if the sensors have passed the functional test after each opening CAUTION MONITORING OF THE SENSOR INPUT CAN B...

Страница 10: ...STOP During functioning with personnel present with DIP 1 at ON check that during opening of M1 and M2 the green DL2 and DL4 LEDS switch on and that during closing of M1 and M2 the red DL3 and DL5 LE...

Страница 11: ...WIRELESS SYSTEM with connector 12 30V ac dc code ACG6094 with terminal block 12 30V ac dc code ACG6099 NOVA Wi Fi PHOTOCELLS WITHOUT WIRES code ACG8037 PAIR OF COLUMS NOVA code ACG8039 TOUCH Wi Fi ST...

Страница 12: ...posteriore Boccola vite senza fine Vite s fine Mot PRINCE EPIC MBT 24V Supporto motore 24V 230W Codice Denominazione Particolare CPL1163 CPL1164 CPL1165 CPL1167 CRS62042R CTC1116 CTC1253 CTC1269 CVA11...

Страница 13: ...ervice area it may be possible to book a local technician to look at your installation Wait times will vary dependent on local workloads The cost is a service fee which includes the first half hour an...

Отзывы: