MOTOR DIRECTION OF ROTATION CONTROL
This control facilitates installation of the system and allows further checks to be
performed.
1 - Switch DIP 1 to ON. Led DL7 starts blinking.
2 - Depress and maintain the pushbutton PROG (movement is obtained with the presence
of the operator, open-stop-close-stop-open-etc) => RED LEDS DL9 and DL10 lit and
the gate leaves close with a fixed timing difference of 4 sec. In case of misfunctioning
release the button and change over the two wires of affected motor.
3 - Depress and maintain the pushbutton PROG => GREEN LEDS DL8 e DL11 lit and the
gate leaves open with a fixed timing difference of 2 sec.
4 - Set the mechanical stop devices for opening (installed on the actuator).
5 -
ONLY IF INSTALLING ACTUATORS WITHOUT ENCODER, PERFORM SETTING
OF THE CURRENT SENSORS
otherwise carry on the next step. For a correct setting
select first the type of motor under use through connectors JP1 and JP2. Rotate the
trimmer fully clockwise (+), maintain depressed the pushbutton PROG and as the gate
leaves get to the mechanical stop operate the trimmers M1 and M2 to locate the
switching treshold of the current sensors. Operation of the current sensor is shown by
the led DL3 lit for motor 2 and DL4 for motor 1. The test can be repeated as desired
both with gate fully open and closed.
6 - Drive the two leaves to full closure, preparing for time setting.
7 - At the end of the procedure, switch DIP1 to OFF. LED DL7 goes off to confirm exit
from the check procedure.
N.B. During this check, the encoder and photocells are not active.
TIME PROGRAMMING FOR TWO MOTORS (#)
THIS CAN BE DONE IN EITHER OF TWO WAYS:
MODE 1
- WITH ENCODER (DIP 7 ON ) (FOR PRINCE - KING)
MODE 2
- WITH CURRENT SENSOR (DIP 7 OFF) (FOR OTHER ACTUATORS)
MODE 1
1 - Start with the gate completely closed.
2 - Switch DIP 2 to ON => LED DL7 will blink rapidly.
3 - Press PROG. => M1 opens.
4 - When the gate comes into contact with the opening stop, the ENCODER stops M1
(with storage of the encoder readings and the time) and M2 starts to open
simultaneously.
5 - When the gate comes into contact with the opening stop, the ENCODER stops M1
(with storage of the encoder readings and the time) => the delay countdown prior to
automatic closing starts simultaneously (max 5 minutes).
6 - Press PROG. => delay countdown prior to automatic closing stops and M2 closes.
7 - Press PROG. => M1 closes and creates a phase difference between M2 and M1. At
the same time LED DL7 stops blinking to signal exit from the programming mode.
At this point, the safety devices and other gate controls will resume normal operation
(inversions, stops, alarms, etc.).
8 - Leaves closure is carried in quick mode, reverting to slow mode in proximity of the
travel end.
9 - On completion of ENCODER measurement the gate stops.
AFTER PROGRAMMING, SWITCH DIP 2 TO OFF.
MODE 2
1 - Start with the gate completely closed.
2 - Switch DIP 2 to ON => LED DL7 will blink rapidly.
3 - Press PROG. => M1 opens.
4 - When the gate comes into contact with the opening stop, the CURRENT SENSOR
stops M1 (with storage of the time) and M2 starts to open simultaneously.
5 - When the gate comes into contact with the opening stop, the CURRENT SENSOR
stops M2 (with storage of the time) and the delay countdown prior to automatic closing
starts simultaneously (max 5 minutes).
6 - Press PROG. => delay countdown prior to automatic closing stops and M2 closes.
7 - Press PROG. => M1 closes and creates a phase difference between M2 and M1. At
the same time LED DL7 stops blinking to signal exit from the programming mode.
At this point, the safety devices and other gate controls will resume normal operation
(inversions, stops, alarms, etc.).
8 - Leaves closure is carried in quick mode, reverting to slow mode in proximity of the
travel end.
9 - Upon closure through the current sensors the gate stops.
AFTER PROGRAMMING, SWITCH DIP 2 TO OFF.
TIME PROGRAMMING FOR ONE MOTOR (#)
IMPORTANT: CUT OUT JP3 TO OPERATE ONE MOTOR.
THIS CAN BE DONE IN EITHER OF TWO WAYS
MODE 3
- WITH ENCODER (DIP 7 ON)
MODE 4
- WITH CURRENT SENSOR (DIP 7 OFF)
MODE 3
1 - Start with the gate completely closed.
2 – Switch DIP 2 to ON => LED DL7 will blink rapidly.
3 - Press PROG. => M1 opens.
4 - When the gate comes into contact with the opening stop, the ENCODER stops M1
(with storage of the encoder readings and the time) and the delay countdown priot to
automatic closing starts (max 5 minutes).
5 - Press PROG. => delay countdown prior to automatic closing stops and M2 closes.
At the same time LED DL7 stops blinking to signal exit from the programming mode.
At this point, the safety devices and other gate controls will resume normal operation
(inversions, stops, alarms, etc.).
6 - The gate will stop at the end of the ENCODER countdown.
7 - AFTER PROGRAMMING, SWITCH DIP 2 TO OFF.
MODE 4
1 - Start with the gate completely closed.
2 - Switch DIP 2 to ON => LED DL7 will blink rapidly.
3 - Press PROG. => M1 opens.
4 - When the gate comes into contact with the opening stop, wait one second then press
PROG. => M1 stops and the delay countdown prior to automatic closing starts (max 5
minutes).
5 - Press PROG. => delay countdown prior to automatic closing stops and M1 closes.
At the same time LED DL7 stops blinking to signal exit from the programming mode.
At this point, the safety devices and other gate controls will resume normal operation
(inversions, stops, alarms, etc.).
6 -
7 - The gate will stop at the end of the ENCODER countdown.
AFTER PROGRAMMING, SWITCH DIP 2 TO OFF.
(#) SAFETY DEVICES ARE ACTIVE DURING THE PROGRAMMING AND THEIR
INTERVENTION STOPS IT (THE LED 7 BLINKS NO MORE BUT REMAINS
CONSTANTLY TURNED ON). TO REPEAT THE PROGRAMMING SET DIP 2 OFF
(IF IN NORMAL MODE) OR DIP 1 AND DIP 2 OFF (IF IN PEDESTRIAN MODE),
CLOSE THE GATE ACCORDING TO THE PROCEDURE “VERIFICATION OF
MOTORS DIRECTION OF ROTATION” AND REPEAT THE PROGRAMMING AS
DESCRIBED ABOVE.
OPERATION OF THE OPERATING ACCESSORIES
OPENING BUTTON (with timer function)
When the gate is standstill, the button operates the opening mode. If you push this button
when the gate is on closure, It opens again.
TIMER FUNCTION
This function is useful In the rush hours, when vehicle traffic is slow (e.g. entry/exit of
workers, emergencies In residential or parking areas and, temporary, for removals).
APPLICATIONS
By connecting a switch and/or a daily/weekly timer (in place or in parallel with the opening
button N.O. “COM-OPEN”), it is possible to open the automation or to keep It open, as
long as the switch is on or the timer is activated.
When the automation is open, all operating functions are inhibited.
If the automatic closing Is started, by releasing the switch or at the time set before, the
automation immediately closes; if not, you need to operate a command.
CLOSING BUTTON (COM-CLOSE)
When the gate Is standstill, It operates the closing.
JOGGING OPERATION BUTTON (COM-K BUTTON)
DIP5 - OFF => It cyclically commands open-stop-close-stop-open-etc.
DIP5 - ON => It opens the gate when this Is closed. If It Is operated while the gate Is
opening, It has no effect. If It Is operated when the gate is open, it closes
the gate and, If It Is operated while the gate Is closing, It opens the gate
again.
RADIO TRANSMITTER
DIP4 - OFF => It cyclically commands open-stop-close-stop-open-etc.
DIP4 - ON => It opens the gate when this is closed. If It Is operated while the gate Is
opening, It has no effect. If It Is operated when the gate Is open, It closes. If
It Is operated while the gate Is closing, It opens the gate again.
AUTOMATIC CLOSING
Pause times before the automatic closing of the gate are set with the timing procedure.
The maximum pause time Is 5 minutes.
Pause time can be started or stopped by DIP3 (ON started).
E
N
G
L
I
S
H
Dip position for PRINCE / KING - Standard setting
DIP 7 OFF - Current sensors Off / Encoder On
Dip position for PRINCE when Encoders are not active
DIP 7 OFF - Current sensors On / Encoder Off
Dip position for KING when the Encoders are not active
DIP 7 OFF - Current sensors On / Encoder Off