32
Func.
Name
Description
Range of
Setting
Unit Def50 Note
F060
Multi-function
Output
Terminal
Ta,Tb1
0: Disable
±1: Running detection
±2: Constant speed detection
±3: Zero speed detection
±4: Frequency range detection
±5: System overload detection (OLO)
±6: Stall prevention detection
±7: Low voltage detection (LE)
±8: Braking detection
±9: Restart after instantaneous power failure
detection
±10: Restart after error condition detection
±11: Error detection
±12: Overheating warning detection (Ht)
±13: Over pressure detection (OP)
±14: Standby detection
-14 ~ +14
(Note4)
─
-11
F062
Frequency
Detection
Range
Set the bandwidth of frequency detection
range.
0.0~10.0 0.1Hz 2.0
F063
Frequency
Detection
Level
Set the frequency detection level of
multi-function output terminal.
0.0~400.0 0.1Hz 0.0
F064
Automatic
Torque
Compensa-
tion
According to the load condition, adjust the
output voltage of the V/F Pattern. (0.0: Off)
0.0~25.5
0.1
1.0
F065
System
Overload
Detection
(OLO)
0: Disable
1: Enable(OLO)
0,1
─
0
F066
System
Overload
Detecting
Selection
0: Detection during constant speed only
1: Detection during operation only
0,1
─
0
F067
Output
Setting after
System
Overload
0: Drive keeps operation when the overload is
detected
1: Drive trips to protection when the overload
is detected
0,1
─
0
F068
System
Overload
Detection
Level
Set the level of the current for overload
detection.
30%~200%
of drive
rated
current
1%
160
F069
System
Overload
Detection
Time
When rhe output current is larger than the
level (F068) and exceeds the time interval of
the overload detection,the drive trips to
protect.
0.1~25.0
0.1
sec
2.0
F070
Stall
Prevention
Level at
Acceleration
If stall is occurred during acceleration, the
motor keeps running at the constant speed.
(200%: Off)
30%~200%
of drive
rated
current
1%
170
function can be set during the operation. / Gray words: The setting use default value.