16
2-3-2 Multi-pump Control
Wiring Method (Standard wiring)
Driver #1
I
V
JP1
AI V+
ON
DSW1
1
24V
12V
JP4
CN1
Driver #0
I
V
Pressure
Transmitter
(4~20mA)
JP1
AI V+
ON
DSW1
1
24V
12V
JP4
CN1
+ -
+ -
Pressure
Transmitter
(4~20mA)
Parameter setting
Drive (#0)
Setting
Description
Content
Func.
F015
(Selection of Parallel Control
Mode)
=2 (E-mode) or
=3 (F-mode) or
=4 (M-mode)
F016
(
Set Drive’s No. for Parallel
Control)
=0(Drive#0)
F126 Select the range of AI
=0(4~20mA)
JP1/JP4
Selection
JP1
Input signal type selection of
AI (Voltage/Current)
I position
JP4
Seclect output Voltage(V+)
(24V
:
output DC+24V
;
12V
:
output DC+12V)
24V
Terminal
Resistor Switch
DSW1
ON position
Auxiliary Drive (#1)
Setting
Description
Content
Func.
F015
(Selection of Parallel Control
Mode)
=2 (E-mode) or
=3 (F-mode) or
=4 (M-mode)
F016
(
Set Drive’s No. for Parallel
Control)
=1
F126 Select the range of AI
=0(4~20mA)
JP1/JP4
Selection
JP1
Input signal type selection of
AI (Voltage/Current)
I position
JP4
Seclect output Voltage(V+)
(24V
:
output DC+24V
;
12V
:
output DC+12V)
24V
Terminal
Resistor Switch
DSW1
ON position