7. LOGIC OF OPERATION
NOTE:
• Following a ELECTA shutdown due to the opening of the "Remote On/
Off" outer contact or a power outage, the operating status previously
stored in
USER INTERFACE
will be reset at the next start-up
• The OFF command to the heat pump involves the complete deactivation
of all aspects of production of cold water, hot water and hot water.
• Compressor start-up consent is obtained only if the water circulator
(Pump 1) is active therefore, in the event of water production request for
heating or cooling of rooms not controlled by KCTR (accessory provided
separately), the relative room thermostat must be connected to "Pump
1" contact (clamps L - K of SC) to activate Pump 1
Heat pump (HP) ON/OFF TIMER:
Once the heat pump has been switched on, its start-up and switch-off
can be automatically set, through the On/Off timer available in the
USER
INTERFACE
.
This function is enabled by setting the
100=On
parameter inside the
HP
label menu
,W LV SRVVLEOH WR DVVRFLDWH IRXU GLIIHUHQW SUR¿OHV RI 2Q2II WLPHU WR HDFK
weekday, in particular:
3UR¿OH)RXUWLPHEDQGVWZR2QDQGWZR2II
3UR¿OH7ZRWLPHEDQGVRQH2QDQGRQH2II
3UR¿OH6LQJOHWLPHEDQGDOZD\V2Q
3UR¿OH6LQJOHWLPHEDQGDOZD\V2II
6HWWLQJRIWKHWLPHEDQGVRISUR¿OHV
1
and
2
happens inside the
P1
and
P2
label menus.
7KHDVVRFLDWLRQRIWKHYDULRXVSUR¿OHVWRHDFKZHHNGD\KDSSHQVLQVLGH
the
dAYS
label menu.
NOTE:
If the On/Off timer is active and the
set
key is pressed for a long time, the
heat pump on
USER INTERFACE
or KCTR switches off, in both On and Off
time bands. By then pressing the
set
key for a long time again, the On/Off
timer is reactivated. Therefore, in the On time band the HP switches on
and in the Off band it remains off until change over to On band.
7.1 HEAT PUMP ON/OFF STATE:
Contatto esterno “Remote On/Off”
OPEN CIRCUIT (morsetti 7-8 della TERMINAL BLOCK)
Instead of "OFF", displayed is the time or temperature of the
delivery water. It is possible to switch the HP on/off by keeping the
set key pressed
set
With KCTR installed (par. 103 = ON), it is also possible to
switch the HP on/off by keeping the down key pressed
giù
Activation of the ON/OFF control of the HP present on the
USER INTERFACE
and on the KCTR, is subject to closing of the “Remote On/Off” external contact
(clamps 7-8 of the TERMINAL BLOCK).
Feeding electronically heat pump, the display of the
USER IN-
TERFACE
, appears the word "OFF", and the heat pump can not
yet be on.
In this state, only the "Anti-freeze" function is active
External contact “Remote On/Off”
OPEN CIRCUIT (clamps 7-8 of TERMINAL BLOCK)
76
Section I :: User
EN
Содержание ELECTA Series
Страница 40: ...Connessioni sulla TERMINAL BLOCK KEAP 40 Sezione II Installazione e manutenzione IT ...
Страница 95: ...Connections on the TERMINAL BLOCK KEAP 95 Section II Installation and maintenance EN ...
Страница 151: ...Connexions sur la TERMINAL BLOCK KEAP 151 Section II Installation et entretien FR ...
Страница 207: ...Anschlüsse an den TERMINAL BLOCK KEAP 207 Leitungsquersch II Installation und Wartung DE ...
Страница 263: ...Conexiones en la TERMINAL BLOCK KEAP 263 Sección II Instalación y mantenimiento ES ...
Страница 342: ...342 ...
Страница 343: ...343 ...