42
WARNING
!
FIGURE 19
COOLING TROUBLE SHOOTING CHART
DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAIL-
URE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
SYMPTOM
POSSIBLE CAUSE
REMEDY
Unit will not run
• Power off or loose electrical connection
•
Check for correct voltage at compressor contactor in control
box
• Thermostat out of calibration-set too high
•
Reset
• Failed contactor
•
Check for 24 volts at contactor coil - replace if contacts are
open
• Blown fuses
•
Replace fuses
• Transformer defective
•
Check wiring-replace transformer
• High pressure control open (if provided)
•
Reset-also see high head pressure remedy-The high pressure
control opens at 450 PSIG
• Interconnecting low voltage wiring damaged
•
Replace thermostat wiring
Condenser fan runs, compressor
• Loose connection
•
Check for correct voltage at compressor -
doesn’t
check & tighten all connections
• Compressor stuck, grounded or open motor winding
•
Wait at least 2 hours for overload to reset.
open internal overload.
If still open, replace the compressor.
• Low voltage condition
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
• Low voltage condition
•
Add start kit components
Insufficient cooling
• Improperly sized unit
•
Recalculate load
• Improper airflow
•
Check - should be approximately 400 CFM per ton.
• Incorrect refrigerant charge
•
Charge per procedure attached to unit service panel.
• Air, non-condensibles or moisture in system
•
Recover refrigerant, evacuate & recharge, add filter drier
• Incorrect voltage
•
At compressor terminals, voltage must be within 10% of rating
plate volts when unit is operating.
Compressor short cycles
• Incorrect voltage
•
At compressor terminals, voltage must be ± 10% of
nameplate marking when unit is operating.
• Defective overload protector
•
Replace - check for correct voltage
• Refrigerant undercharge
•
Add refrigerant
Registers sweat
• Low evaporator airflow
•
Increase speed of blower or reduce restriction - replace air
• Room thermostat set too low
filter
High head-low vapor pressures
• Restriction in liquid line, expansion device or filter drier
•
Remove or replace defective component
• Flow check piston size too small
•
Change to correct size piston
• Incorrect capillary tubes
•
Change coil assembly
•
Increase set point on thermostat
High head-high or normal vapor
• Dirty condenser coil
•
Clean coil
pressure - Cooling mode
• Refrigerant overcharge
•
Correct system charge
• Condenser fan not running
•
Repair or replace
• Air or non-condensibles in system
•
Recover refrigerant, evacuate & recharge
Low head-high vapor pressures
• Defective Compressor valves
•
Replace compressor
• Incorrect capillary tubes
•
Replace coil assembly
Low vapor - cool compressor -
• Low evaporator airflow
•
Increase speed of blower or reduce restriction - replace air
iced evaporator coil
filter
• Operating below 65°F outdoors
•
Add Low Ambient Kit
• Moisture in system
•
Recover refrigerant - evacuate & recharge - add filter drier
High vapor pressure
• Excessive load
•
Recheck load calculation
• Defective compressor
•
Replace
Fluctuating head & vapor
• Overcharged
•
Check air distribution on coil – adjust charge.
• Air or non-condensibles in system
•
Recover refrigerant, evacuate & recharge
Gurgle or pulsing noise at
• Air or non-condensibles in system
•
Recover refrigerant, evacuate & recharge
expansion device or liquid line
Содержание RKKL Series
Страница 9: ...9 Illustration ST A0801 17 I FIGURE 6 ROOFCURB INSTALLATION FIGURE 5 ST A1154 02 00...
Страница 41: ...41 TABLE 9 AIR FLOW PERFORMANCE 12 5 TON 43 9 kW RKKL B120 MODELS...
Страница 45: ...45 FIGURE 21...
Страница 46: ...46 FIGURE 22...
Страница 47: ...47 FIGURE 23...
Страница 48: ...48 FIGURE 24...
Страница 49: ...49 FIGURE 25...
Страница 50: ...50 FIGURE 26...
Страница 51: ...51 FIGURE 27 RKKL SYSTEM CHARGE CHART...
Страница 54: ...54...
Страница 55: ...55...
Страница 56: ...56 CM 1110...