background image

34

2. Upon a loss of flame, each inducer will complete a 5 second postpurge and the indoor

blower will complete a 90 second delay off.

3. Control in the stand by mode with solid red LED.

The integrated control is a four-ignition system.
After a total of four cycles without sensing main burner flame, the system goes into a 100%
lockout mode. After one hour, the ignition control repeats the prepurge and ignition cycles
for 4 tries and then go into 100% lockout mode again. It continues this sequence of cycles
and lockout each hour until ignition is successful or power is interrupted. During the lockout
mode, neither the ignitor or gas valve will be energized until the system is reset by turning
the thermostat to the “OFF” position or interrupting the electrical power to the unit for 3
seconds or longer. The induced draft blower and main burner will shut off when the ther-
mostat is satisfied.
The circulating air blower will start and run on the heating speed if the thermostat fan
switch is in the “ON” position.
The integrated furnace control is equipped with diagnostic LED. The LED is lit continuously
when there is power to the control, with or without a call for heat. If the LED is not lit, there
is either no power to the control or there is an internal component failure within the control,
and the control should be replaced.
If the control detects the following failures, the LED will flash on for approximately 1/4 sec-
ond, then off for 3/4 second for designated failure detections.
1 Flash: Failed to detect flame within the four tries for ignition.
2 Flash: Pressure switch or induced draft blower problem detected.
3 Flash: High limit or auxiliary limit open.
4 Flash: Flame sensed and gas valve not energized or flame sensed with no “W” signal.
5 Flash: Overtemperature switch open.

OPERATING INSTRUCTIONS

This appliance is equipped with integrated furnace control. This device lights the main
burners each time the room thermostat (closes) calls for heat. See operating instructions
on the back of the furnace/controls access panel.

TO START THE FURNACE

1. Set the thermostat to its lowest setting.
2. Turn off all electric power to the appliance.
3. This appliance does not have a pilot. It is equipped with an ignition device which auto-

matically lights the burner. Do not try to light the burner by hand.

4. Remove control door.
5. Move control knob to the “OFF” position. Turn the knob by hand only, do not

use any kind of tool.

6. Wait five (5) minutes to clear out any gas. Then smell for gas, including

near the floor. If you smell gas, STOP! Follow B in the safety information on
the Operating Instructions located on the back of the controls/access panel.
If you don’t smell gas, go to the next step.

7. Move the gas control knob from “OFF” position to “ON” position. Operate

this appliance with the gas control knob in the “ON” position only. Do not
use the gas control knob as a means for throttling the burner input rate.

8. Replace the control door.
9. Turn on all electric power to the appliance.

10. Set the thermostat to the desired setting.
11. If the appliance will not operate, follow the instructions below on how to shut

down the furnace.

The initial start-up on a new installation may require the control system to be
energized for some time until air has bled through the system and fuel gas is
available at the burners.

!

WARNING

DO NOT ATTEMPT TO MANUALLY LIGHT THIS FURNACE WITH A MATCH OR
ANY OPEN FLAME. ATTEMPTING TO DO SO CAN CAUSE AN EXPLOSION OR
FIRE RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

!

WARNING

THE SPARK IGNITOR AND IGNITION LEAD FROM THE IGNITION CON-
TROL ARE HIGH VOLTAGE. KEEP HANDS OR TOOLS AWAY TO PRE-
VENT ELECTRICAL SHOCK. SHUT OFF ELECTRICAL POWER BEFORE
SERVICING ANY OF THE CONTROLS. FAILURE TO ADHERE TO THIS
WARNING CAN RESULT IN PERSONAL INJURY OR DEATH.

Содержание RKKL Series

Страница 1: ...5 01 SUPERSEDES 92 23577 105 00 INSTALLATION INSTRUCTIONS FOR COMBINATION HEATING AND COOLING ROOFTOP UNITS RKKL SERIES 7 5 10 AND 12 5 TON 26 4 35 2 AND 44 0 kW ISO 9001 2008 Featuring Industry Stand...

Страница 2: ...SUPPLY CONDENSATE DRAIN AND PIPING 26 Gas Connection 26 LP Conversion 28 Adjusting or Checking Furnace Input 28 Condensate Drain 29 IV WIRING 30 Power Supply 30 Hook up 31 Internal Wiring 31 Thermost...

Страница 3: ...ALL UNIT TO OPERATE WITHIN THE UNIT S INTENDED TEM PERATURE RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE AS SPECIFIED IN DUCTING SECTION OF THESE INST...

Страница 4: ...AIR DUCT SEALED TO THE FURNACE AIR FILTERS IN PLACE SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RATING PLATE MARKING RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55 F 13 C AND 80 F 27 C AND INSTALLAT...

Страница 5: ...anger assembly gas burner and control assembly com bustion air motor and fan and all necessary internal electrical wiring The cooling systems of these units are factory evacuated charged and performan...

Страница 6: ...not install a suction line filter drier in the liquid line A liquid line filter drier is standard on every unit Desiccant drying agent must be compatible for POE oils and R 410A 3 Evaporator Coil Exp...

Страница 7: ...IMPORTANT THIS UNIT MUST BE MOUNTED LEVEL IN BOTH DIRECTIONS TO ALLOW WATER TO DRAIN FROM THE CONDENSER SEC TION AND CONDEN SATE PAN LEFT SIDE FRONT SIDE 7 ST A1154 01 00 ELECTRICAL ACCESS BLOWER ACCE...

Страница 8: ...OW APPLICATIONS Illustration ST A0738 02 SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATIONS RECOMMENDED DUCT DIMENSIONS ARE 26 Illustration ST A0736 02 X1 BOTTOM VIEW SIDE VIEW REAR LEFT SIDE FR...

Страница 9: ...9 Illustration ST A0801 17 I FIGURE 6 ROOFCURB INSTALLATION FIGURE 5 ST A1154 02 00...

Страница 10: ...l Depth in mm 1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 13 5 1 25 13 5 1 25 13 5 1 25 13 5 1 25 Rows FPI FPcm 1 23 9 1 23 9 1 23 9 1 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Louvere...

Страница 11: ...el Depth in mm 1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 13 5 1 25 13 5 1 25 13 5 1 25 13 5 1 25 Rows FPI FPcm 1 23 9 1 23 9 1 23 9 1 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Louver...

Страница 12: ...el Depth in mm 1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 13 5 1 25 13 5 1 25 13 5 1 25 13 5 1 25 Rows FPI FPcm 1 23 9 1 23 9 1 23 9 1 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Louver...

Страница 13: ...nel MicroChannel MicroChannel Depth in mm 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 13 5 1 25 13 5 1 25 13 5 1 25 Rows FPI FPcm 1 23 9 1 23 9 1 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Tub...

Страница 14: ...nel MicroChannel MicroChannel Depth in mm 1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 23 9 1 23 9 1 23 9 1 23 9 Indoor Coil Fin Type Louvered Louve...

Страница 15: ...nel MicroChannel MicroChannel Depth in mm 1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 23 9 1 23 9 1 23 9 1 23 9 Indoor Coil Fin Type Louvered Louve...

Страница 16: ...hannel MicroChannel Depth in mm 1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 1 23 9 1 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Louvered Louver...

Страница 17: ...nnel Depth in mm 1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 23 9 2 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tub...

Страница 18: ...l MicroChannel Depth in mm 1 25 4 1 25 4 1 25 4 1 25 4 Face Area sq ft sq m 27 2 51 27 2 51 27 2 51 27 2 51 Rows FPI FPcm 2 23 9 2 23 9 2 23 9 2 23 9 Indoor Coil Fin Type Louvered Louvered Louvered Lo...

Страница 19: ...1 2 1 2 1 2 1 2 1 2 1 2 2 3 2 3 2 3 2 3 2 3 2 3 1 5 1 5 1 5 1 1 1 5 6 5 6 5 6 5 6 5 6 5 6 3 1 3 1 3 1 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 208 230 208 230 208 230 460 460 460 575 575 575 3 3 3 3 3 3 3 3 3 2...

Страница 20: ...0 35 80 80 90 90 40 45 35 35 1 1 1 1 1 1 2 2 2 2 2 2 200 240 200 240 480 480 600 600 208 230 208 230 460 460 575 575 3 3 3 3 3 3 3 3 3 3 3 3 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450...

Страница 21: ...s sulphur or chlorine from lawn watering systems and vari ous chemical contaminants from industries such as paper mills and petroleum refineries are especially corrosive If the unit is to be installed...

Страница 22: ...area snowfall and to allow combustion air to enter the combustion air inlet 7 Select an area which will keep the areas of the vent air intake and A C condenser fins free and clear of obstructions such...

Страница 23: ...niques E COVER PANEL INSTALLATION CONVERSION PROCEDURE DOWNFLOW TO HORIZONTAL 1 Remove the screws and covers from the outside of the supply and return sections See Figure 2 2 Install the covers over t...

Страница 24: ...rvice immediately block off supply and return air openings to prevent excessive condensation I DUCTING The installing contractor should fabricate ductwork in accordance with local codes Use industry m...

Страница 25: ...uction which might change this to a confined space Also caution the user homeowner against any future installation of additional equipment such as power ventilators clothes dryers etc within the exist...

Страница 26: ...ty company In the absence of local codes the installation must conform to the specifi cations of the National Fuel Gas Code ANSI Z223 1 latest edition NOTE The use of flexible gas connectors is not pe...

Страница 27: ...pressure testing of this gas supply system at pressures equal to or less than 1 2 PSIG TO CHECK FOR GAS LEAKS USE A SOAP AND WATER SOLUTION OR OTHER APPROVED METHOD DO NOT USE AN OPEN FLAME IMPORTANT...

Страница 28: ...fold pressure should be set at 10 W C at the gas con trol valve WARNING THIS UNIT IS EQUIPPED AT THE FACTORY FOR USE ON NATURAL GAS ONLY CONVERSION TO LP GAS REQUIRES A SPECIAL KIT SUPPLIED BY THE DIS...

Страница 29: ...uce the input 4 for each 1 000 feet 305 meters above sea level NOTICE DERATING OF THE HEATING INPUT FOR HIGH ALTITUDE IN THE FIELD IS UNLAWFUL IN CANADA REFER TO CAN CGA 2 17 UNITS INSTALLED IN ALTITU...

Страница 30: ...o unit 4 For through the base wiring entry reference Figure 17 All fittings and conduit are field supplied for this application Reference the chart with Figure 17 for proper hole and conduit size NOTE...

Страница 31: ...he field between the unit and devices not attached to the unit or between separate devices which are field installed and located shall conform with the temperature limitation for Type T wire 63 F rise...

Страница 32: ...IRED WIRE SIZE FROM MINIMUM CIRCUIT AMPACITY SHOWN IN INSTALLATION OPERATING INSTRUCTION 2 BOTTOM POWER ENTRY WILL NOT ACCOMMODATE WIRE LARGER THAN 2 AWG SHADED AREA WIRE FROM ZONE THERMOSTAT TO BE RO...

Страница 33: ...Control enters normal operating loop where all inputs are continuously checked C Second Stage Satisfied First Stage Still Called For Starting From B 2 1 Once the call for second stage is satisfied the...

Страница 34: ...ING INSTRUCTIONS This appliance is equipped with integrated furnace control This device lights the main burners each time the room thermostat closes calls for heat See operating instructions on the ba...

Страница 35: ...the furnace from exceeding the maxi mum outlet air temperature IMPORTANT Replace this control only with the identical replacement part VI SYSTEM OPERATING INFORMATION ADVISE THE CUSTOMER 1 Change the...

Страница 36: ...the heat exchanger center panel Remove the induced draft blower and the collector box from the unit 9 Remove the turbulators from inside the heat exchangers by inserting the blade of a screwdriver un...

Страница 37: ...PORTANT Do not use excessive water pressure Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit performance Be careful not to splash water excessively into un...

Страница 38: ...unit and check for proper operation especially the condenser fan motor REPLACEMENT PARTS Contact your local distributor for a complete parts list TROUBLESHOOTING Refer to Figures 19 and 20 for determ...

Страница 39: ...1148 2606 1178 2691 1133 2649 1163 2734 1192 2820 0 1 02 0 2 05 0 3 07 0 4 10 0 7 17 0 8 20 0 9 22 1 0 25 1 1 27 1 2 30 1 3 32 1 4 35 1 5 37 1 6 40 1 7 42 1 8 45 1 9 47 2 0 50 External Static Pressur...

Страница 40: ...2338 1188 932 2452 4600 2171 794 2105 821 2180 840 2254 876 2329 919 2457 940 2571 960 2684 980 2798 1000 2911 1021 3025 1041 3138 1061 3252 1124 3365 1151 3479 1122 3592 952 2585 973 2679 993 2793 10...

Страница 41: ...41 TABLE 9 AIR FLOW PERFORMANCE 12 5 TON 43 9 kW RKKL B120 MODELS...

Страница 42: ...ltage At compressor terminals voltage must be within 10 of rating plate volts when unit is operating Compressor short cycles Incorrect voltage At compressor terminals voltage must be 10 of nameplate m...

Страница 43: ...OLTAGE TRANSFORMER CHECK WIRING CHECK FOR 208 230 VAC TO IDM MOTOR CHECK IGNITOR CABLE CHECK SPARK IGNITOR POSITION AND CONDITION IS EACH NEGATIVE PRESSURE SWITCH CLOSED CHECK FOR OPEN ROLL OUT CONTRO...

Страница 44: ...OPER THERMOSTAT OPERATION REMOVE VALVE LEAD AT GAS VALVE IF VALVE CLOSES RECHECK THE THERMOSTAT AND WIRING IF OK THEN REPLACE VALVE YES NO SYSTEM RUNS UNTIL CALL FOR HEAT ENDS TROUBLESHOOTING ENDS REP...

Страница 45: ...45 FIGURE 21...

Страница 46: ...46 FIGURE 22...

Страница 47: ...47 FIGURE 23...

Страница 48: ...48 FIGURE 24...

Страница 49: ...49 FIGURE 25...

Страница 50: ...50 FIGURE 26...

Страница 51: ...51 FIGURE 27 RKKL SYSTEM CHARGE CHART...

Страница 52: ...52 FIGURE 28 RKKL SYSTEM CHARGE CHART 10 TON CIRCUIT 1 92 102259 20 00 SYSTEM CHARGE CHART REFRIGERANT 410A 115 105 95 85 75 65 55...

Страница 53: ...53 FIGURE 29 RKKL SYSTEM CHARGE CHART BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING REFRIGERANT CHARGE BEFORE FINAL REFRIGERANT CHECK RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS...

Страница 54: ...54...

Страница 55: ...55...

Страница 56: ...56 CM 1110...

Отзывы: