Operating the water heater

29

Safety Precautions

   Do turn off manual gas shut-off valve if water heater 

has been subjected to over heating, fire, flood, physi-

cal damage or if the gas supply fails  

to shut off.

   Do Not turn on water heater unless it is completely 

filled with water.

   Do Not turn on water heater if cold water supply 

shut-off valve is closed.

   Do Not allow combustible materials such as newspa-

per, rags or mops to accumulate near  

water heater.

   Do Not store or use gasoline or other flammable 

vapors and liquids, such as adhesives or paint thinner, 

in vicinity of this or any other appliance.  

If such flammables must be used, open doors  

and windows for ventilation, and all gas burning 

appliances in the vicinity should be shut off including 

their pilot burners, to avoid vapors lighting.

NOTICE: Flammable vapors can be drawn by air 

currents from surrounding areas to the water heater.

   If there is any difficulty in understanding or following 

the Operating Instructions or the Care and Cleaning 

section, it is recommended that a qualified person or 

serviceman perform the work.

CAUTION: Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a 

long period of time (generally two weeks or more). HYDROGEN GAS IS EXTREMELY FLAMMABLE!! To dissipate such 

gas and to reduce risk of injury, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink 

before using any electrical appliance connected to the hot water system. If hydrogen is present, there will be an unusual sound 

such as air escaping through the pipe as the water begins to flow. Do not smoke or use an open flame near the faucet at the 

time it is open.

!

DANGER: 

Hotter water 

increases the Potential  

for Hot Water SCALDS

Households with small 

children, disabled, or elderly 

persons may require a 120°F  

(49°C ) or lower gas control 

(thermostat) setting to 

prevent contact with unsafe 

water temperatures.

Water Temperature Setting

The temperature of the water in the water 

heater can be regulated by pressing the 

buttons on the front of the gas control 

(thermostat).
Safety and energy conservation are factors 

to be considered when selecting the water 

temperature setting of the water heater’s 

gas control (thermostat(s)). The lower the 

temperature setting, the greater the savings 

in energy and operating costs.
To comply with safety regulations, the gas 

control (thermostat) was set at its lowest 

setting before the water heater was shipped 

from the factory.  The recommended 

starting point temperature is 120°F (49

°C)

.

Water temperatures above 125°F (52

°C)

can cause severe burns or death from 

scalding. Be sure to read and follow the 

warnings outlined in this manual and on 

the label located on the water heater near 

the gas control thermostat.
Mixing valves are available for reducing 

point of use water temperature by mixing 

hot and cold water in branch water lines. 

Contact a licensed plumber or the local 

plumbing authority for further informa-

tion.
The chart on the next page may be used 

as a guide in determining the appropriate 

water temperature for your home.

Operating Procedure

This water heater is equipped with a hot 

surface ignitor to light the main burner. 

There is no pilot light to be lit, but on initial 

start-up, it is recommended that the outer 

door be removed (leave inner door in place 

for safety) to view through the sight glass if 

the hot surface ignitor and main burner are 

operating properly.
Once filled with water, it is only necessary 

to plug the power cord in and make sure the 

“ON/OFF” switch located on the blower 

assembly is in the “ON” position to put the 

water heater into operation. Within seconds 

the hot surface ignitor should heat up, then 

the gas valve should open and the main 

burner ignite. After the main burner ignites, 

replace the outer door. If no main burner 

flame is established, the gas control will go 

through three trials for ignition before going 

into a lock-out. A warning light will alert the 

user of this lock-out condition. If this hap-

pens, refer to “Troubleshooting Guide.”
TO SHUT OFF WATER HEATER – Turn 

switch on the blower assembly to the “OFF” 

position.

Содержание Power Direct Vent Series

Страница 1: ...s for the proper installation and adjustment of the water heater and two for the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater...

Страница 2: ...can save you time and money over the life of your water heater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips first you may n...

Страница 3: ...int thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water heater...

Страница 4: ...water temperature for each LED indicator of the Combination Gas Control s display D A N G E R HOT Water temperature over 125 can cause severe burns instantly or death from scalds Children disabled an...

Страница 5: ...LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look...

Страница 6: ...has been subjected to overheating fire flood physical damage or if the gas supply fails to shut off Read this manual entirely before installing or operating the water heater Use this appliance only f...

Страница 7: ...ids which give off flammable vapors are to be used or stored Such liquids include gasoline LP gas butane or propane paint or adhesives thinners solvents and or combustible removers DO NOT obstruct or...

Страница 8: ...ushion built in that compresses as the system pressure increases thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve Other methods of controlling t...

Страница 9: ...relief valve above a suitable open drain to eliminate potential water damage Piping used should be of a type approved for hot water distribution The discharge line must be no smaller than the outlet...

Страница 10: ...e compound is used as the valve body may be damaged The inlet gas pressure to the water heater must not exceed 14 0 in w c 3 5 kPa w c for natural gas or 14 0 in w c 3 5 kPa w c for LP gas For purpose...

Страница 11: ...ABS Schedule 40 DWV Cellular Core ASTM F628 This water heater is approved to use the following materials for the fittings of the vent and combustion air intake systems PVC Schedule 40 DWV ASTM D2665...

Страница 12: ...the instructions in this manual before completing the installation and putting the water heater into service Connect the vent system piping to the blower assembly using the already installed 2 in 5 1...

Страница 13: ...e same atmospheric pressure zone The minimum and maximum equivalent lengths for the vent and combustion air inlet systems are shown in Table 1 Maintain a minimum vertical height of 1 foot 3 5 cm of pi...

Страница 14: ...alent Vent Combustion Air Inlet Lengths Each Pipe Run Max Allowed Equivalent Vent Combustion Air Inlet Lengths Each Pipe Run Vent and Combustion Air Inlet System Termination s Inches Feet Meters Feet...

Страница 15: ...re firmly tight then leak test the vent sys tem joints using a soap and water solution Repair any leak before allowing the water heater to oper ate When using CPVC or ABS pipe and fittings use 90 elbo...

Страница 16: ...ows 75 Gallon 75 100 70 000 Btu hr Models 3 8 2 5 50 15 90 Elbows 3 8 2 5 40 12 Concentric 4 8 2 5 100 30 90 Elbows From 2 000 Ft 609 m Above Sea Level through 5 999 Ft 1 828 m Above Sea Level Model V...

Страница 17: ...bows 3 7 2 45 13 5 Concentric 4 7 2 100 30 90 Elbows 65 Gallon 65 000 56 000 Btu hr Models 4 8 3 50 15 90 Elbows 75 Gallon 75 100 70 000 Btu hr Models 4 8 3 50 15 90 Elbows From 7 701 Ft 2347 m Above...

Страница 18: ...to inside corner H Clearance to each side of centerline extend ed above meter regulator assembly I Clearance to service regulator vent outlet J Clearance to nonmechanical air supply inlet to building...

Страница 19: ...ctors in equivalent vent and or combus tion air inlet lengths longer than 8 feet 2 44 meters or on any other Power Direct Vent model Additional Considerations Do Not install the vent terminal under an...

Страница 20: ...it to the vent connector fitting on the water heater s blower assembly Horizontal lengths of the vent system must slope downward away from the water heater a minimum of 1 8 in per foot 10 mm per meter...

Страница 21: ...ed downward Support vertical and horizontal lengths of the vent and combustion air inlet systems as previously mentioned Vent Connections Figure 5 Combustion Air Inlet Connection Vent Connections Comb...

Страница 22: ...warnings on material containers CAUTION For proper installation DO NOT use solvent cement that has become curdled lumpy or thickened DO NOT thin solvent cement Observe shelf precautions printed on th...

Страница 23: ...ALLUMAGE DE REMPLACEMENT DOIT TRE TALONN 250 C IGNITER AND FLAME SENSOR ALLUMEUR ET CAPTEUR DE FLAMME FLAMMABLE VAPOR SENSOR D TECTEUR DE VAPEUR INFLAMMABLE H G N 120 VAC PLUG FOR POWERVENT BLOWER ASS...

Страница 24: ...any responsibility for such loss or injury resulting from the use of such unau thorized devices CAUTION If local codes require the application of an external insulation blanket to this water heater p...

Страница 25: ...techni cian A new burner access door gasket must be installed on any burner access door that has been removed DON T install this water heater where standing water may occur The base of the water heat...

Страница 26: ...ed Soap and water solution used to check all con nections and fittings for possible gas leak GasCompanyinspectedinstallation ifrequired D Relief Valve Temperature and Pressure Relief Valve properly in...

Страница 27: ...Installation Spring loaded check valve in heating unit hot water supply line and cold water return line not supplied with water heater NOTE This check valve is incorporated in some heating units Refer...

Страница 28: ...all your gas supplier from a neighbor s phone Follow the Do not try to light any appliance Do not touch any electric switch do not use any phone in your building WHAT TO DO IF YOU SMELL GAS Turn off a...

Страница 29: ...ting The temperature of the water in the water heater can be regulated by pressing the buttons on the front of the gas control thermostat Safety and energy conservation are factors to be considered wh...

Страница 30: ...trol thermostat Therefore always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury Also always supervise young children...

Страница 31: ...in gas valve which will extinguish the main burner flames The blower motor will stay energized for an additional 30 seconds after the control verifies that the burner flame is extinguished in order to...

Страница 32: ...es periodically this may be due to ther mal expansion in a closed water system Contact the water supplier or your plumb ing contractor on how to correct this DO NOT plug the relief valve outlet A wate...

Страница 33: ...ssembly Inspect the combustion air inlet and vent systems Make certain that all joints are secure and that combustion air inlet and vent system supports are all in place Check the outdoor combustion a...

Страница 34: ...combustion air inlet systems Unable to light the main burner Air in gas line Contact a qualified service techni cian to purge the air from the gas line Blocked vent system Contact a qualified service...

Страница 35: ...ow to correct this Do not plug the relief valve outlet Not enough or no hot water Water usage may have exceeded the capacity of the water heater Wait for the water heater to recover after an abnormal...

Страница 36: ...t surface ignitor A B C System in lockout 1 Gas supply is off or too low to operate Turn on the gas supply and or increase the inlet gas supply pres sure 2 Hot surface ignitor not positioned correctly...

Страница 37: ...ing gas control thermostat burners vent connectors or other safety devices Refer repairs to qualified service personnel Use only original equipment replacement parts Blower Assembly Flue Baffle Anode...

Страница 38: ...38 Notes...