Leak Testing

The water heater and its gas connections 

must be leak tested at normal operating 

pressures before it is placed in operation.

   Turn on the manual gas shut-off 

valve near the water heater.

   Use a soapy water solution to test for 

leaks at all connections and fittings. 

Bubbles indicate a gas leak that must 

be corrected. 

The factory connections to the combina-

tion gas control should also be leak tested 

after the water heater is placed in opera-

tion.

High Altitude

Pressure Testing the Gas Supply System

The water heater and its individual shut-

off valve must be disconnected from the 

gas supply piping system during any 

pressure testing of that system at test 

pressures in excess 1/2 psi (3.5 kPA).

The water heater must be isolated from 

the gas supply piping system by closing 

its individual manual gas shutoff valve 

during any pressure testing of the gas 

supply at test pressures equal to or less 

than 1/2 psi (3.5 kPa).

WARNING: Never use 

an open flame to test for 

gas leaks, as property 

damage, personal injury, or 

death  could result.

11

Vent and Combustion Air-Inlet

This water heater is a direct vent appli-

ance and must be installed so that all air 

for combustion is derived directly from 

the outside atmosphere and all flue gases 

are discharged to the outside atmosphere.  

For proper installation of the vent and 

combustion air-inlet systems, follow the 

instructions as detailed in this manual. 

DO NOT

 connect this water heater to 

an existing vent or chimney - it must be 

vented separately from all other appli-

ances.
NOTICE: This water heater is approved 

to use the following materials for pipe of 

the vent and Combustion Air-Inlet sys-

tems:
PVC (Schedule 40, Cellular Core, 

ASTM-F891)
PVC (DWV, ASTM-D2665 or CSA 

B181.2)
PVC (Schedule 40, ASTM-D1785 or CSA  

B137.3)
PVC (SDR Series, ASTM-D2241 or CSA 

B137.3)

CPVC (CPVC 4120, ASTM-D2846 or 

CSA B137.6)
CPVC (Schedule 40, ASTM-F441 or CSA 

B137.3)
CPVC (SDR Series, ASTM-F442)
ABS (Schedule 40, DWV, ASTM-D2661 

or CSA B181.1)
ABS (Schedule 40, DWV, Cellular Core, 

ASTM-F628)
This water heater is approved to use the 

following materials for the fittings of the 

vent and combustion air-intake systems:
PVC (Schedule 40 DWV, ASTM D2665)
CPVC (Schedule 40, ASTM F438)
ABS (Schedule 40 DWV, ASTM D2661)

DO NOT mix ABS pipe and fittings 

with PVC or CPVC pipe fittings. Note: 

It is acceptable to interchange PVC and 

CPVC pipe and fittings.

Vent and combustion air-inlet systems 

must be adequately supported along both 

vertical and horizontal lengths.

DANGER: Failure to 

properly install the vent and 

combustion air-inlet systems as 

outlined in the Vent and 

Combustion Air-Inlet section of 

this manual will result in 

unsafe operation of the water 

heater causing bodily injury, 

explosion, fire or death. 
To avoid the risk of fire, 

explosion, or asphyxiation from 

carbon monoxide, NEVER 

operate the water heater unless 

it is properly vented and the 

vent and combustion air-inlet 

systems are properly installed 

as detailed in the "Vent and 

Combustion Air-Inlet" section 

of this manual.
The vent and combustion air 

inlet pipes must overlap a 

minimum of 1/2 in. (1.3 cm) 

at each joint.  It is important 

that the vent and combustion 

air-inlet pipes engage fully into 

any pipe fitting and be kept in 

that position until the adhesive 

has fully cured.  DO NOT drill 

or punch holes in the plastic 

pipe or fittings.

Input rating of this water heater is based 

on sea level operation.  At higher eleva-

tions the actual input rate may be lower 

than the value listed on the rating label 

due to the derating of Natural Gas and LP 

Gas.  For Power Direct Vent models listed 

in the venting tables that do not show 

venting configurations above 7,700 ft. 

(2,347 m), contact the water heater manu-

facturer for a required High Altitude Kit 

that will allow the specific water heater 

model to operate at altitudes between 

7,700 ft. (2,347 m) and 10,200 ft. (3,109 

m),(see page 40).

!

WARNING: Failure to 

install a water heater suitable 

for the altitude at the location 

it is intended to serve, can 

result in improper operation 

of the appliance resulting 

in property damage and/or 

producing carbon monoxide 

gas, which could result in 

personal injury, or death.

Содержание Power Direct Vent Series

Страница 1: ...s for the proper installation and adjustment of the water heater and two for the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater...

Страница 2: ...can save you time and money over the life of your water heater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips first you may n...

Страница 3: ...int thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water heater...

Страница 4: ...water temperature for each LED indicator of the Combination Gas Control s display D A N G E R HOT Water temperature over 125 can cause severe burns instantly or death from scalds Children disabled an...

Страница 5: ...LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look...

Страница 6: ...has been subjected to overheating fire flood physical damage or if the gas supply fails to shut off Read this manual entirely before installing or operating the water heater Use this appliance only f...

Страница 7: ...ids which give off flammable vapors are to be used or stored Such liquids include gasoline LP gas butane or propane paint or adhesives thinners solvents and or combustible removers DO NOT obstruct or...

Страница 8: ...ushion built in that compresses as the system pressure increases thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve Other methods of controlling t...

Страница 9: ...relief valve above a suitable open drain to eliminate potential water damage Piping used should be of a type approved for hot water distribution The discharge line must be no smaller than the outlet...

Страница 10: ...e compound is used as the valve body may be damaged The inlet gas pressure to the water heater must not exceed 14 0 in w c 3 5 kPa w c for natural gas or 14 0 in w c 3 5 kPa w c for LP gas For purpose...

Страница 11: ...ABS Schedule 40 DWV Cellular Core ASTM F628 This water heater is approved to use the following materials for the fittings of the vent and combustion air intake systems PVC Schedule 40 DWV ASTM D2665...

Страница 12: ...the instructions in this manual before completing the installation and putting the water heater into service Connect the vent system piping to the blower assembly using the already installed 2 in 5 1...

Страница 13: ...e same atmospheric pressure zone The minimum and maximum equivalent lengths for the vent and combustion air inlet systems are shown in Table 1 Maintain a minimum vertical height of 1 foot 3 5 cm of pi...

Страница 14: ...alent Vent Combustion Air Inlet Lengths Each Pipe Run Max Allowed Equivalent Vent Combustion Air Inlet Lengths Each Pipe Run Vent and Combustion Air Inlet System Termination s Inches Feet Meters Feet...

Страница 15: ...re firmly tight then leak test the vent sys tem joints using a soap and water solution Repair any leak before allowing the water heater to oper ate When using CPVC or ABS pipe and fittings use 90 elbo...

Страница 16: ...ows 75 Gallon 75 100 70 000 Btu hr Models 3 8 2 5 50 15 90 Elbows 3 8 2 5 40 12 Concentric 4 8 2 5 100 30 90 Elbows From 2 000 Ft 609 m Above Sea Level through 5 999 Ft 1 828 m Above Sea Level Model V...

Страница 17: ...bows 3 7 2 45 13 5 Concentric 4 7 2 100 30 90 Elbows 65 Gallon 65 000 56 000 Btu hr Models 4 8 3 50 15 90 Elbows 75 Gallon 75 100 70 000 Btu hr Models 4 8 3 50 15 90 Elbows From 7 701 Ft 2347 m Above...

Страница 18: ...to inside corner H Clearance to each side of centerline extend ed above meter regulator assembly I Clearance to service regulator vent outlet J Clearance to nonmechanical air supply inlet to building...

Страница 19: ...ctors in equivalent vent and or combus tion air inlet lengths longer than 8 feet 2 44 meters or on any other Power Direct Vent model Additional Considerations Do Not install the vent terminal under an...

Страница 20: ...it to the vent connector fitting on the water heater s blower assembly Horizontal lengths of the vent system must slope downward away from the water heater a minimum of 1 8 in per foot 10 mm per meter...

Страница 21: ...ed downward Support vertical and horizontal lengths of the vent and combustion air inlet systems as previously mentioned Vent Connections Figure 5 Combustion Air Inlet Connection Vent Connections Comb...

Страница 22: ...warnings on material containers CAUTION For proper installation DO NOT use solvent cement that has become curdled lumpy or thickened DO NOT thin solvent cement Observe shelf precautions printed on th...

Страница 23: ...ALLUMAGE DE REMPLACEMENT DOIT TRE TALONN 250 C IGNITER AND FLAME SENSOR ALLUMEUR ET CAPTEUR DE FLAMME FLAMMABLE VAPOR SENSOR D TECTEUR DE VAPEUR INFLAMMABLE H G N 120 VAC PLUG FOR POWERVENT BLOWER ASS...

Страница 24: ...any responsibility for such loss or injury resulting from the use of such unau thorized devices CAUTION If local codes require the application of an external insulation blanket to this water heater p...

Страница 25: ...techni cian A new burner access door gasket must be installed on any burner access door that has been removed DON T install this water heater where standing water may occur The base of the water heat...

Страница 26: ...ed Soap and water solution used to check all con nections and fittings for possible gas leak GasCompanyinspectedinstallation ifrequired D Relief Valve Temperature and Pressure Relief Valve properly in...

Страница 27: ...Installation Spring loaded check valve in heating unit hot water supply line and cold water return line not supplied with water heater NOTE This check valve is incorporated in some heating units Refer...

Страница 28: ...all your gas supplier from a neighbor s phone Follow the Do not try to light any appliance Do not touch any electric switch do not use any phone in your building WHAT TO DO IF YOU SMELL GAS Turn off a...

Страница 29: ...ting The temperature of the water in the water heater can be regulated by pressing the buttons on the front of the gas control thermostat Safety and energy conservation are factors to be considered wh...

Страница 30: ...trol thermostat Therefore always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury Also always supervise young children...

Страница 31: ...in gas valve which will extinguish the main burner flames The blower motor will stay energized for an additional 30 seconds after the control verifies that the burner flame is extinguished in order to...

Страница 32: ...es periodically this may be due to ther mal expansion in a closed water system Contact the water supplier or your plumb ing contractor on how to correct this DO NOT plug the relief valve outlet A wate...

Страница 33: ...ssembly Inspect the combustion air inlet and vent systems Make certain that all joints are secure and that combustion air inlet and vent system supports are all in place Check the outdoor combustion a...

Страница 34: ...combustion air inlet systems Unable to light the main burner Air in gas line Contact a qualified service techni cian to purge the air from the gas line Blocked vent system Contact a qualified service...

Страница 35: ...ow to correct this Do not plug the relief valve outlet Not enough or no hot water Water usage may have exceeded the capacity of the water heater Wait for the water heater to recover after an abnormal...

Страница 36: ...t surface ignitor A B C System in lockout 1 Gas supply is off or too low to operate Turn on the gas supply and or increase the inlet gas supply pres sure 2 Hot surface ignitor not positioned correctly...

Страница 37: ...ing gas control thermostat burners vent connectors or other safety devices Refer repairs to qualified service personnel Use only original equipment replacement parts Blower Assembly Flue Baffle Anode...

Страница 38: ...38 Notes...

Страница 39: ...39 Notes...

Страница 40: ...tic the hard wired carbon monoxide detec tor with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at...

Отзывы: