background image

9

CIRCULATING AIR SUPPLY

Plenum chambers and air ducts must
be installed in accordance with the
Standard for the Installation of Air
Conditioning and Ventilating Systems,
NFPA No. 90A, or the Standard for the
Installation of Warm Air Heating and
Air Conditioning Systems, NFPA No.
90B. 

The circulating air supply may be
taken: (1) exclusively from return air
ducts from several rooms, or (2)
combined with outside air. When
outside air is utilized, the system
should be designed and adjusted such
that the temperature of the combined
return air to the furnace will not be
below 50°F during the heating season.
When using a combination of outside
air and return air, be sure the ducts are
so designed and a diverting damper so
installed that the volume of circulating
air entering the furnace cannot be
reduced or restricted below that which
would normally enter through the
circulating air intake of the furnace. 

When the furnace is installed so that
the supply ducts carry air circulated by
the furnace to areas outside the space
containing the furnace, the return air
shall be handled by a duct or ducts
sealed to the furnace casing and
terminated outside the space
containing the furnace.

IF THERE IS NO COMPLETE
RETURN AIR DUCT SYSTEM, THE
RETURN AIR CONNECTION MUST
RUN FULL SIZE TO A LOCATION
OUTSIDE THE UTILITY ROOM OR
SPACE HOUSING THE FURNACE
TO PREVENT A NEGATIVE
PRESSURE ON THE VENTING
SYSTEMS. A NEGATIVE PRESSURE
CAN DRAW PRODUCTS OF
COMBUSTION INTO CIRCULATING
AIR. 

NEVER ALLOW THE PRODUCTS OF
COMBUSTION OR THE FLUE
PRODUCTS TO ENTER THE RETURN
AIR DUCTWORK OR THE
CIRCULATING AIR SUPPLY. ALL
RETURN DUCTWORK MUST BE
ADEQUATELY SEALED AND
SECURED TO THE FURNACE WITH
SHEET METAL SCREWS, AND
JOINTS TAPED. ALL OTHER DUCT
JOINTS MUST BE SECURED WITH
APPROVED CONNECTIONS AND
SEALED AIRTIGHT. 

FAILURE TO PREVENT PRODUCTS
OF COMBUSTION FROM BEING
CIRCULATED INTO THE LIVING
SPACE CAN CREATE SOOT
DAMAGE, SMOKE, ODORS OR
CARBON MONOXIDE POISONING. 

IMPORTANT:

One of the most

common causes of trouble in forced air
heating systems is insufficient return
air to the furnace. The return air
system should be approximately equal
to or greater than the area of the warm
air discharge. CONSULT LOCAL
CODES FOR SPECIAL
REQUIREMENTS.

DO NOT, UNDER ANY
CIRCUMSTANCES, CONNECT
RETURN OR SUPPLY DUCTWORK
TO OR FROM ANY OTHER HEAT
PRODUCING DEVICE SUCH AS A
FIREPLACE INSERT, STOVE, ETC.
DOING SO MAY RESULT IN FIRE,
CARBON MONOXIDE POISONING,
EXPLOSION, PERSONAL INJURY,
PROPERTY DAMAGE OR DEATH.

Install the cold air return to terminate
through the floor under the furnace. A
direct connection should be made to
the bottom of the furnace. For
installations where return air ducts
cannot be run under the floor, return air
may be taken from the sides by cutting
the furnace casing and installing the
appropriate accessory. 

NOTE: 

Where the maximum air flow is

1800 CFM or more, both sides or the
bottom must be used for return air.

When a cooling coil is used in
conjunction with the furnace, it must be
installed downstream of the outlet end
of the furnace (supply-air side) or in
parallel with the furnace to avoid
condensation in the heat exchanger. 

If the furnace is installed in parallel with
a cooling unit, the damper or other
means used to control the flow of air
must be adequate to prevent chilled air
from entering the furnace, and if
manually operated must be equipped
with means to prevent operation of the
other unit unless the damper is in the
full heat or cool position. 

IMPORTANT:

Air openings in the

casing front, return air grilles and warm
air registers must not be obstructed. 

BLOWER AND BURNERS MUST
NEVER BE OPERATED WITHOUT
BLOWER DOOR IN PLACE. THIS IS
TO PREVENT DRAWING FUMES
(WHICH COULD CONTAIN
ANNOYING AND HAZARDOUS
GASES) INTO THE HOME THAT
COULD RESULT IN PERSONAL
INJURY OR DEATH.

FLUE AND CHIMNEY
EXHAUST

The vent connector should be as short
as possible and installed so that it has
a continuous rise from the furnace to
the chimney or flue.

The number of elbows should be
minimized and the flue pipe should be
joined with sheet metal screw and
properly supported with suitable pipe
hangers.

A barometric draft regulator is required
in each furnace vent connector and
must be installed before the vent
connector enters the chimney or flue.

NOTE: 

The size of the draft regulator

diameter must be no smaller than the
vent connector diameter.

The vent connector should be the
same size as the furnace flue pipe
connection. The sizes are:

CHIMNEY SIZE
RECOMMENDATIONS

The following table shows
recommended size and height for
chimneys based on total BTU input of
all the oil appliances being vented:

VENTING

Unit must be vented through a chimney
or flue. Check chimney for soot, leaks,
obstruction and proper height to
prevent down draft. Clean chimney and
base if necessary. 

The height of the chimney or flue shall
be at least 3 feet above the highest
point where it passes through the roof
of a building and at least 2 feet higher
than any portion of a building within 10
feet of such chimney. 

WARNING

!

WARNING

!

WARNING

!

TABLE 5

GROSS BTU RECTANGULAR

ROUND MINIMUM

INPUT

TILE

TILE

HEIGHT

(INCHES)

(INCHES)

(FEET)

144,000

8

1

/

2

x 8

1

/

2

8

20

235,000

8

1

/

2

x 13

10

30

372,000

13 x 13

12

35

516,000

13 x 18

14

40

612,000

15

45

768,000

18 x 18

50

960,000

20 x 20

18

55

BTU OUTPUT

FLUE SIZE

056
067
084
095
112
130
150

5”
5”
5”
5”
5”
7”
7”

TABLE 4

Содержание OBF Series

Страница 1: ...UE TO VARIOUS FACTORS YOU MAY NOT BE ABLE TO SMELL FUEL GASES U L recognized fuel gas and CO detectors are recommended in all applications and their installation should be in accordance with the manuf...

Страница 2: ...Air Supply 9 Flue and Chimney Exhaust 9 Chimney Size Recommendations 9 Venting 9 Barometric Draft Control 10 Oil Burner Primary Control 10 Tank and Oil LInes 11 Electric Wiring 11 Thermostat 11 Typica...

Страница 3: ...tatic pressure within the allowable range as specified in general information section of these instructions See furnace rating plate 12 When a furnace is installed so that supply ducts carry air circu...

Страница 4: ...Air Heating and Air Conditioning Systems NFPA No 90B Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances NFPA No 211 LOCATION REQUIREMENTS AND CONSIDERATIONS GENERAL INFORMATION...

Страница 5: ...3 4 MED HIGH 1715 1745 1760 1770 1 20 MED HIGH HIGH 151200 MED LOW 1375 1400 1435 1450 44 30KW LOW 1045 1055 1070 1090 1 35 HIGH HIGH MODEL NUMBER 067 112 150 56000 16 41KW 84000 24 62KW 134400 39 38...

Страница 6: ...NOZZLE HAVING A FIRING RATE OF 85 GALLONS PER HOUR AND AN INPUT RATING OF 119 000 BTUH 92 100538 01D 00 THIS FURNACE WAS INSTALLED WITH A NOZZLE HAVING A FIRING RATE OF 1 00 GALLONS PER HOUR AND AN I...

Страница 7: ...SOME HOMES MAY REQUIRE THAT OUTSIDE AIR BE SUPPLIED TO THE FURNACE AREA FAILURE TO PROVIDE ENOUGH FRESH AIR CAN CAUSE DEATH FROM CARBON MONOXIDE POISONING Adequate facilities for combustion and venti...

Страница 8: ...Installation of Oil Burning Equipment defines confined space and unconfined space as follows Confined Space Any space whose volume is less than 50 cu ft per 1 000 BTUH of the aggregate input rating o...

Страница 9: ...t connection should be made to the bottom of the furnace For installations where return air ducts cannot be run under the floor return air may be taken from the sides by cutting the furnace casing and...

Страница 10: ...should be used INJURY OR DAMAGE CAUSED BY THE USE OF SUCH UNTESTED AND OR UNCERTIFIED DEVICES ACCESSORIES OR COMPONENTS BAROMETRIC DRAFT CONTROL The barometric damper see figure 9 is a control instal...

Страница 11: ...IN PROPERTY DAMAGE INJURY OR DEATH SINGLE AND DUAL OIL FILTRATION We recommend the use of a replaceable core or spin on type supply line suction oil filter or dual filtration primary and secondary fi...

Страница 12: ...12 TYPICAL INSTALLATION DIAGRAMS FIGURE 11 TWO PIPE INSTALLATION FIGURE 12 ONE PIPE INSTALLATION...

Страница 13: ...NOTE Do not expose cad cell to direct electric bulb light or sunlight Light may enter through the air control band slot and upset the electric circuit of this device OPERATING INSTRUCTIONS FIGURE 14 C...

Страница 14: ...r from the barometric damper Another 1 4 inch hole is provided by the manufacturer for testing over the fire Drill another 1 4 hole between the barometric damper and the chimney as shown in Figure 14...

Страница 15: ...ell matched and well tuned burner should be capable of operation at a CO2 level between 10 and 12 checking cut off pressure Slow pump cutoff at the end of a firing cycle can cause smoke and other poll...

Страница 16: ...a toolbox used in the field Construct the assembly as shown in Figure 17 and install it as shown in Figure 18 Once the pressure testing assembly has been made and installed as shown in Figure 18 turn...

Страница 17: ...inst the face of the nozzle and between the electrode tips see figure 20 2 Position the gauge so the center scribe mark is in line with the nozzle orifice Do not scratch the nozzle face The nozzle sho...

Страница 18: ...grees Return air temperature 75 degrees Temperature rise 80 degrees E Compare the calculated tempera ture rise with the specified temperature rise on the rating plate TEMPERATURE RISE TOO HIGH Check f...

Страница 19: ...or rust tighten the clamp screw without any filter paper in the slot and purge with several rapid pump strokes of room air 2 Warm the True Spot to room temperature before using 3 In sampling be sure...

Страница 20: ...airflow is not reduced to maximize system performance and life Always verify that the systems airflow is not impaired by the filtering system that has been installed by performing a temperature rise a...

Страница 21: ...ove Enlarge to match chimney interior Replace loose bricks and mortar If all other causes have been eliminated a new chimney may have to be built Replace loose bricks or mortar Remove Have chimney cle...

Страница 22: ...ISC RATING 067 112 150 NOTE This appliance should only be used with specified Delavan or Del O Flo nozzles Use of other nozzles may result in unsatisfactory performance DEL O FLO 50 65 70 B DELAVAN 1...

Страница 23: ...inlet restricted or burner blower wheel dirty 17 Restricted flue 1 Cracked dirty or loose electrodes 2 Electrodes not properly adjusted 3 Incorrect nozzle 4 Improper primary air adjustment 5 Faulty i...

Страница 24: ...urnace 5 Dirty heat exchanger 6 High draft barometric damper not properly set 7 Excessive temperature rise 8 Air shutter adjustment open too much 1 Lack of combustion air 2 Inadequate overfire draft 3...

Страница 25: ...in operating position 7 Dirty strainers 8 Dirty line filter 9 Motor does not come up to speed 10 Bad air leak at seal 11 Improper pump setting 1 Pump gears worn 2 Vertical oil lift too great over 10...

Страница 26: ...CHECK ELECTRODES IGNITION TRANSFORMER CHECK FUEL SUPPLY NOZZLE CHECK CAD CELL PRIMARY CONTROL CHECK FAN CENTER CHECK BLOWER MOTOR WIRING CHECK BLOWER MOTOR CAPACITOR CHECK THERMOSTAT AND CONTROL WIRI...

Страница 27: ...fire Draft inches negative H2O Breech Draft inches negative H2O Chimney Draft inches negative H2O Smoke Reading CO2 CO2 Stack Temperature degrees F Room Temperature degrees F Net Stack Temperature deg...

Страница 28: ...TING AND COOLING SCHEMATIC 38 FOR MODELS WITH UTEC 1012 925 INTEGRATED FURNACE CONTROL IMPORTANT Do not use a power robbing thermostat with this furnace Use only mechanical thermostats or battery powe...

Страница 29: ...29 FIGURE 34 HEATING AND COOLING CONTINUOUS LOW SPEED BLOWER SCHEMATIC IMPORTANT Do not use a power robbing thermostat with this furnace Use only mechanical thermostats or battery powered thermostats...

Страница 30: ...30 NOTES...

Страница 31: ...31 NOTES...

Страница 32: ...32 CM 1005 NOTES...

Отзывы: