background image

10

Install a single wall, vent connector
from flue outlet to chimney, sloping flue
pipe continuously upward (at least 1/4
inch per foot) toward chimney. The
vent connector should be the same
diameter as the flue collar of the
furnace for the entire length of run and
should not exceed 10 feet in length.
Avoid sharp turns that would create
resistance to the flow of flue gasses.
Vent connector should not extend
beyond the inside wall of the chimney
and must be firmly cemented to
masonry.

IMPORTANT: 

For horizontally vented

applications, use the Tjernlund SS1-R
power vent (date code of ??? or later)
installed to the manufacturer’s
installation instructions.

No other appliances or heating
equipment should be connected to the
vent connector servicing the furnace. 

Bolt, screw and/or support joints to
avoid sag. Fasten the single-wall vent
connector to the outlet collar of the
furnace with at least two sheet metal
screws. Refer to Figure 1 for distances
to combustible materials.

DEVICES ATTACHED TO THE FLUE
OR VENT FOR THE PURPOSE OF
REDUCING HEAT LOSS UP THE
CHIMNEY HAVE NOT BEEN TESTED
AND HAVE NOT BEEN INCLUDED IN
THE DESIGN CERTIFICATION OF
THIS FURNACE. WE, THE
MANUFACTURER, CANNOT AND
WILL NOT BE RESPONSIBLE FOR

OIL BURNER /  PRIMARY
CONTROL

Oil burner and primary control are
mounted to the furnace as a single
assembly. Standard equipment
consists of the oil burner, ignition
transformer, and flame sensor
(cadmium sulfide cell) with primary
control and low voltage transformer all
included on the burner assembly.

The standard oil burner is equipped
with a single stage fuel pump. This
single stage fuel pump may be used in
either a one or two pipe system. If a
two pipe system is required (burner is
above tank) the lift and length of run
must be considered so as not to
overload the fuel unit. 

NOTE: 

If the

length of run and the lift is beyond the
recommended limits of the charts
below, a booster prep unit should be
used. 

INJURY OR DAMAGE CAUSED BY
THE USE OF SUCH UNTESTED
AND/OR UNCERTIFIED DEVICES,
ACCESSORIES OR COMPONENTS.

BAROMETRIC DRAFT
CONTROL

The barometric damper (see figure 9) is
a control installed in the flue pipe to
regulate the draft in the furnace. If the
draft increases in the chimney, the
damper opens to maintain the preset
draft in the furnace. Should the draft
decrease in the chimney, the damper
will close to maintain the preset draft of
the oil furnace. A barometric damper is
supplied with each furnace and must be
installed by the following the
instructions supplied by the
manufacturer. The barometric damper
control should be installed between the
flue outlet of the furnace and the
chimney (see figure 10). The
barometric damper control should be
set for proper draft on start up after the
furnace has been operating for 10 to 15
minutes. See Oil Burner Adjustment
Procedure Section for proper draft
settings.

On start up, the furnace must be set
for field conditions with a
combustion kit for proper operation.
NOTE:

Always use a separate

barometric damper for each oil-fired
appliance. Install the barometric
damper with its hinge level and the face
plumb. Tilting causes erratic damper
operation. Installation of a barometric
damper must be in accordance with the
Installation and Operation Instructions
provided with the damper.

The following standards and codes will
help to make the installation. Current
editions of these standards can be
obtained from:

American National Standards Institute,
1430 Broadway, New York, NY 10018

Metal Thickness for 

Galvanized Steel Pipe Connectors

Diameter of

Galvanized

Minimum

Connector

Sheet

Thickness

(in.)

(mm)

Gauge No. (in.)

(mm)

< 6

< 152

26

0.019

0.48

6 to 

10

152 to 

254

24

0.024

0.61

> 10 to 

16 > 254 to 

406

22

0.029

0.74

>16

> 406

16

0.056

1.42

FIGURE 10

RECOMMENDED BAROMETRIC DAMPER LOCATIONS

FIGURE 9

BAROMETRIC DAMPER

WARNING

!

Lift (in feet)

0

1

2

3

4

5

6

7 8 9 10

3/8" O.D.

53 40 45 41 38 33 20 25 21 18 13

Tubing

1/2" O.D.

100 100 100 100 100 100 100 99 83 68 52

Tubing

Recommended Maximum Length of Tubing

Used on a Single Stage (3450 RPM) Pump Two

Pipe System

Содержание OBF Series

Страница 1: ...UE TO VARIOUS FACTORS YOU MAY NOT BE ABLE TO SMELL FUEL GASES U L recognized fuel gas and CO detectors are recommended in all applications and their installation should be in accordance with the manuf...

Страница 2: ...Air Supply 9 Flue and Chimney Exhaust 9 Chimney Size Recommendations 9 Venting 9 Barometric Draft Control 10 Oil Burner Primary Control 10 Tank and Oil LInes 11 Electric Wiring 11 Thermostat 11 Typica...

Страница 3: ...tatic pressure within the allowable range as specified in general information section of these instructions See furnace rating plate 12 When a furnace is installed so that supply ducts carry air circu...

Страница 4: ...Air Heating and Air Conditioning Systems NFPA No 90B Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances NFPA No 211 LOCATION REQUIREMENTS AND CONSIDERATIONS GENERAL INFORMATION...

Страница 5: ...3 4 MED HIGH 1715 1745 1760 1770 1 20 MED HIGH HIGH 151200 MED LOW 1375 1400 1435 1450 44 30KW LOW 1045 1055 1070 1090 1 35 HIGH HIGH MODEL NUMBER 067 112 150 56000 16 41KW 84000 24 62KW 134400 39 38...

Страница 6: ...NOZZLE HAVING A FIRING RATE OF 85 GALLONS PER HOUR AND AN INPUT RATING OF 119 000 BTUH 92 100538 01D 00 THIS FURNACE WAS INSTALLED WITH A NOZZLE HAVING A FIRING RATE OF 1 00 GALLONS PER HOUR AND AN I...

Страница 7: ...SOME HOMES MAY REQUIRE THAT OUTSIDE AIR BE SUPPLIED TO THE FURNACE AREA FAILURE TO PROVIDE ENOUGH FRESH AIR CAN CAUSE DEATH FROM CARBON MONOXIDE POISONING Adequate facilities for combustion and venti...

Страница 8: ...Installation of Oil Burning Equipment defines confined space and unconfined space as follows Confined Space Any space whose volume is less than 50 cu ft per 1 000 BTUH of the aggregate input rating o...

Страница 9: ...t connection should be made to the bottom of the furnace For installations where return air ducts cannot be run under the floor return air may be taken from the sides by cutting the furnace casing and...

Страница 10: ...should be used INJURY OR DAMAGE CAUSED BY THE USE OF SUCH UNTESTED AND OR UNCERTIFIED DEVICES ACCESSORIES OR COMPONENTS BAROMETRIC DRAFT CONTROL The barometric damper see figure 9 is a control instal...

Страница 11: ...IN PROPERTY DAMAGE INJURY OR DEATH SINGLE AND DUAL OIL FILTRATION We recommend the use of a replaceable core or spin on type supply line suction oil filter or dual filtration primary and secondary fi...

Страница 12: ...12 TYPICAL INSTALLATION DIAGRAMS FIGURE 11 TWO PIPE INSTALLATION FIGURE 12 ONE PIPE INSTALLATION...

Страница 13: ...NOTE Do not expose cad cell to direct electric bulb light or sunlight Light may enter through the air control band slot and upset the electric circuit of this device OPERATING INSTRUCTIONS FIGURE 14 C...

Страница 14: ...r from the barometric damper Another 1 4 inch hole is provided by the manufacturer for testing over the fire Drill another 1 4 hole between the barometric damper and the chimney as shown in Figure 14...

Страница 15: ...ell matched and well tuned burner should be capable of operation at a CO2 level between 10 and 12 checking cut off pressure Slow pump cutoff at the end of a firing cycle can cause smoke and other poll...

Страница 16: ...a toolbox used in the field Construct the assembly as shown in Figure 17 and install it as shown in Figure 18 Once the pressure testing assembly has been made and installed as shown in Figure 18 turn...

Страница 17: ...inst the face of the nozzle and between the electrode tips see figure 20 2 Position the gauge so the center scribe mark is in line with the nozzle orifice Do not scratch the nozzle face The nozzle sho...

Страница 18: ...grees Return air temperature 75 degrees Temperature rise 80 degrees E Compare the calculated tempera ture rise with the specified temperature rise on the rating plate TEMPERATURE RISE TOO HIGH Check f...

Страница 19: ...or rust tighten the clamp screw without any filter paper in the slot and purge with several rapid pump strokes of room air 2 Warm the True Spot to room temperature before using 3 In sampling be sure...

Страница 20: ...airflow is not reduced to maximize system performance and life Always verify that the systems airflow is not impaired by the filtering system that has been installed by performing a temperature rise a...

Страница 21: ...ove Enlarge to match chimney interior Replace loose bricks and mortar If all other causes have been eliminated a new chimney may have to be built Replace loose bricks or mortar Remove Have chimney cle...

Страница 22: ...ISC RATING 067 112 150 NOTE This appliance should only be used with specified Delavan or Del O Flo nozzles Use of other nozzles may result in unsatisfactory performance DEL O FLO 50 65 70 B DELAVAN 1...

Страница 23: ...inlet restricted or burner blower wheel dirty 17 Restricted flue 1 Cracked dirty or loose electrodes 2 Electrodes not properly adjusted 3 Incorrect nozzle 4 Improper primary air adjustment 5 Faulty i...

Страница 24: ...urnace 5 Dirty heat exchanger 6 High draft barometric damper not properly set 7 Excessive temperature rise 8 Air shutter adjustment open too much 1 Lack of combustion air 2 Inadequate overfire draft 3...

Страница 25: ...in operating position 7 Dirty strainers 8 Dirty line filter 9 Motor does not come up to speed 10 Bad air leak at seal 11 Improper pump setting 1 Pump gears worn 2 Vertical oil lift too great over 10...

Страница 26: ...CHECK ELECTRODES IGNITION TRANSFORMER CHECK FUEL SUPPLY NOZZLE CHECK CAD CELL PRIMARY CONTROL CHECK FAN CENTER CHECK BLOWER MOTOR WIRING CHECK BLOWER MOTOR CAPACITOR CHECK THERMOSTAT AND CONTROL WIRI...

Страница 27: ...fire Draft inches negative H2O Breech Draft inches negative H2O Chimney Draft inches negative H2O Smoke Reading CO2 CO2 Stack Temperature degrees F Room Temperature degrees F Net Stack Temperature deg...

Страница 28: ...TING AND COOLING SCHEMATIC 38 FOR MODELS WITH UTEC 1012 925 INTEGRATED FURNACE CONTROL IMPORTANT Do not use a power robbing thermostat with this furnace Use only mechanical thermostats or battery powe...

Страница 29: ...29 FIGURE 34 HEATING AND COOLING CONTINUOUS LOW SPEED BLOWER SCHEMATIC IMPORTANT Do not use a power robbing thermostat with this furnace Use only mechanical thermostats or battery powered thermostats...

Страница 30: ...30 NOTES...

Страница 31: ...31 NOTES...

Страница 32: ...32 CM 1005 NOTES...

Отзывы: