1. INSPECT SHIPMENT — 

Inspect the water heater for possible damage.

Check the markings on the rating plate of the water heater to be certain
the power supply corresponds to that for which the water heater is
equipped.

2. THERMAL EXPANSION — Determine if a check valve exists in the

inlet water line.

It may have been installed in the cold water line as a

separate back flow preventer, or it may be part of a pressure reducing
valve, water meter or water softener. A check valve located in the cold
water inlet line can cause what is referred to as a 

”closed water

system”

. A cold water inlet line with no check valve or back flow

prevention device is referred to as an ”open” water system.

As water is heated, it expands in volume and creates an increase
in the pressure within the water system. This action is referred
to as 

”thermal expansion”

. In an ”open” water system, expanding

water which exceeds the capacity of the water heater flows back
into the city main where the pressure is easily dissipated.

A

”closed water system”

, however,  prevents the expanding

water from flowing back into the main supply line, and the result
of

”thermal expansion”

can create a rapid, and dangerous pres-

sure increase in the  water heater and system piping. This rapid
pressure increase can quickly reach the safety setting of the re-
lief valve, causing it to operate during each heating cycle. Ther-
mal expansion, and the resulting rapid, and repeated expansion
and contraction of components in the water heater and piping
system can cause premature failure of the relief valve, and pos-
sibly the heater itself.Replacing the relief valve 

will not

correct

the problem! 

The suggested method of controlling thermal expansion is to install
an expansion tank in the cold water line between the water heater and
the check valve. (refer to Figure 2.) The expansion tank is designed
with an air cushion built in that compresses as the system pressure
increases, thereby relieving the over pressure condition and elimi-
nating the repeated operation of the relief valve. Other methods of
controlling thermal expansion are also available. Contact your in-
stalling contractor, water supplier, or plumbing inspector for additional
information regarding this subject.

NOTICE!! Do not apply heat to the hot or cold heat trap fittings. If
sweat connections are used, sweat tubing to adapter before fitting
adapter to water connections on heater. Any heat applied to the water
connections will permanently damage the heat trap fittings.

WATER SUPPLY CONNECTIONS —

Refer to Fig. 2 for suggested

typical installation. The installation of unions or flexible copper connectors
is recommended on the hot and cold water connections so that the water
heater may be easily disconnected for servicing if necessary. The HOT
and COLD water connections are clearly marked and are 3/4” NPT on all
models. Install a shut-off valve in the cold water line near the water
heater.

3. RELIEF VALVE —

A new combination pressure and temperature

relief valve, complying with the Standard for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water Supply Systems,
ANSI Z21.22, must be installed in the opening provided and
marked for the purpose on the water heater. (Refer to Fig. 2.) No
valve of any type should be installed between the relief valve and
the tank. Local codes shall govern the installation of relief valves.

4

The location chosen for the water heater must take into consideration the
following:

LOCAL INSTALLATION REGULATIONS

This water heater must be installed in accordance with these instructions,
local codes, utility company requirements or, in the absence of local codes,
the latest edition of the National Electrical Code. It is available from some
local libraries or can be purchased from the National Fire Prevention
Association, 1 Batterymarch Park, Quincy, MA 02269 as booklet ANSI/NFPA
70. In Canada, use the latest edition of the Canadian Electric Code.

LOCATION

Locate the water heater in a clean dry area as near as practical to the area of
greatest heated water demand. Long uninsulated hot water lines can waste
energy and water. Place the water heater in such a manner that the
thermostat and element access panels can be removed to permit inspection
and servicing such as removal of elements or checking controls. The water
heater and water lines should be protected from freezing temperatures. Do
not install the water heater in outdoor, unprotected areas.

Make certain the floor underneath the water heater is strong enough
to sufficiently support the weight of the water heater once it is filled
with water.

The water heater should not be located in an area where leakage of
the tank or connections will result in damage to the area adjacent
to it or to lower floors of the structure. Where such areas cannot be
avoided, it is recommended that a suitable catch pan, adequately
drained, be installed under the water heater.

NOTICE: Auxiliary catch pan installation MUST conform to local
codes.

Catch Pan Kits are available from the distributor or store where
the water heater was purchased.

Introduction 

A — Diameter of water

heater plus 2" (5 cm)
min.

B — Maximum 2" (5 cm)

To open drain, line should
be at least 

3

/

4

" (1.9cm) ID

and pitched for proper
drainage.

A

B

Figure 1. — Auxiliary Catch Pan

CAUTION

!

Installation

Содержание Light Duty Commercial Electric Water Heater

Страница 1: ...ructions or any terms within it seek professional advice Any questions regarding the operation maintenance service or warranty of this water heater should be directed to the seller from whom it was pu...

Страница 2: ...can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date is needed to obtain service under the warranty Your safety and the safety of ot...

Страница 3: ...CE When this water heater is supplying general purpose hot water requirements for use by individuals a thermostatically controlled mixing valve for reducing point of use water temperature is recommend...

Страница 4: ...suggested typical installation The installation of unions or flexible copper connectors is recommended on the hot and cold water connections so that the water heater may be easily disconnected for ser...

Страница 5: ...ion Box Kit be installed per figure 3 above An opening for either 1 2 or 3 4 electrical fitting is provided for field wiring connections Refer to Figure 3 The voltage requirements and wattage load for...

Страница 6: ...cover any damage or defect caused by installation attachment or use of any type of energy saving or other unapproved devices other than those authorized by the manufacturer into onto or in conjunctio...

Страница 7: ...ater heater remove jacket access panel and insulation exposing thermostats The thermostat protective covers should not be removed Set thermostat dial pointers with a small screwdriver to desired tempe...

Страница 8: ...ter pipe system can be used to minimize the problem Also water hammer arresting devices are usually available from your plumber or local plumbing supply store 2 ANODE ROD INSPECTION The anode rod shou...

Страница 9: ...s normal for periods of water usage Heat Traps when in operation and does not indicate a need for service How to Obtain Service Assistance 1 Should you have any questions about your new water heater o...

Страница 10: ...ER BEF ORE SER VICIN G 140 130 120 110 100 90 T H E R M O D I S C Drain valve Jacket access panel s Heating element gasket Heating element Thermostat bracket Lower thermostat Cavity insulation Lower t...

Страница 11: ...access panel s and insulation 3 Rotate the crossbar up and down until it breaks away from the remainder of the cavity insert See illustration to the left Discard the crossbar It cannot and need not b...

Страница 12: ...ELECTRICAL DISTRIBUTION PANEL G G G BRANCH CIRCUIT TO ELECTRICAL DISTRIBUTION PANEL UPPER THERMOSTAT HIGH TEMP LIMIT ECO 2 UPPER HEATING ELEMENT BLUE L1 JUNCTION BOX 4 L2 1 3 RED 10 GA BLACK LOWER HE...

Отзывы: