60
Ac
ce
ss
or
ie
s
ELECTRONIC AIR CLEANER
Line voltage power can be supplied from the terminal la-
beled “EAC” and a line voltage neutral terminal on the
control board. This will power the electronic air cleaner
whenever the circulating air blower is in operation.
NOTE:
The electronic air cleaner output will not be ener-
gized when the ECM blower motor target CFM is below
the following thresholds:
(-)97V060 = 500 CFM
(-)97V070 = 500 CFM
(-)97V085 = 600 CFM
(-)97V100 = 600 CFM
(-)97V115 = 600 CFM
Under some circumstances, such as low-speed continu-
ous fan, the target blower CFM may be below the above
threshold. In these cases the electronic air cleaner output
will NOT be energized.
NOTE:
Maximum current is 1.0 amps for the electronic air
cleaner output.
HUMIDIFIER
Humidifier output is a set of dry contacts. The logic control-
ling these contacts and the necessary wire diagrams for in-
stalling a humidifier are detailed in the section of this
manual titled
Humidification/Dehumidification
.
FILTERS
(See Figure 46)
Keep filters clean at all times.
A filter is not provided
with the furnace, but one must be field-supplied and
installed.
It is recommended to replace the furnace filter periodically
to maintain optimum furnace performance.
TWINNING
Twinning of these furnaces is NOT permitted!
AIR TEMPERATURE SENSORS
Outdoor Air Temperature Kit RXGJ-J02
Supply Air Temperature Sensor 47-24225-01
Refer to supply/outdoor air temperature section of inte-
grated furnace control for more detailed information.
ACCESSORIES
FIELD INSTALLED OPTION ACCESSORIES