11. COMMUNICATING ECM MOTOR COMMUNICA-
TIONS (CONTROL) CONNECTION (P4)
This connector sends and receives messages to and
from the blower motor through a single peer-to-peer
network. The blower motor does not communicate on
the same communications buss as the furnace, con-
denser (or heat-pump) and thermostat. Further, a dif-
ferent communications protocol is used.
12. DIPSWITCHES; S1, S2 AND S3
NOTES:
1. There is a protective cover over the dipswitches
that must be penetrated to change the dipswitch
position. Use a pen or similar tool to penetrate the
cover and change the position. This is normal and
penetration of the protective cover will not damage
the dipswitch.
INTEGRATED FURNACE CONTROL
HUMIDIFICATION/DEHUMIDIFICATION
Co
m
m
un
ica
tin
g
Fu
rn
ac
e
FIGURE 48
WIRING FOR OPTIONAL DE-HUMIDIFICATION AND HUMIDIFICATION WITH OPTIONAL HUMIDIFIER (HUMIDIFIER WITH INTERNAL
POWER SUPPLY). NOTE: FOR USE WITH NON-COMMUNICATING SYSTEMS.
ST-A1194-57-00
FIGURE 49
HUMIDISTAT USED TO CONTROL DEHUMIDIFICATION IN COOLING ONLY (NO HUMIDIFIER)
NOTE: FOR USE WITH NON-COMMUNICATING THERMOSTATS.
ST-A1194-58-00
Содержание *96V series
Страница 34: ...Field Conversions 34...
Страница 35: ...Field Conversions 35...
Страница 36: ...36 Field Conversions...
Страница 37: ...37 Field Conversions...
Страница 38: ...Field Conversions 38...
Страница 81: ...81 TABLE 14 SUPPLEMENTAL ORIFICE SIZE CHART HIGH ALTITUDE NATURAL GAS AT HIGH ALTITUDES cont High Altitude...
Страница 112: ...112 Diagnostics TABLE 20 continued R96V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS...
Страница 117: ...117 TABLE 20 continued R96V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics...
Страница 123: ...123 FIGURE 62 2 STAGE ECM FURNACE WIRING DIAGRAM Troubleshooting...
Страница 124: ...124 CM 1014...