Ve
nt
in
g
of the enclosure, shall be permitted where the equipment
has clearances of at least 1 inch from the sides and back
and 6 inches from the front of the appliance. The opening
shall directly communicate with the outdoors or communi-
cate through a vertical or horizontal duct to the outdoors or
spaces (crawl or attic) that freely communicate with the out-
doors, and shall have a minimum of:
A. 1 Square inch for each 3,000 BTUH of the total input rat-
ing of all equipment located in the enclosure
and
NON-DIRECT VENT (cont.)
GENERAL VENTING REQUIREMENTS AND
GUIDELINES
FIGURE 14
NON-DIRECT VENT
AIR FROM ATTIC OR CRAWL
SPACE
O
P
T
IO
N
A
L
IN
LE
T
A
IR
1
S
Q
. I
N
.
(6
.5
S
Q
. C
M
.)
P
ER
4
0
0
0
B
T
U
H
ST-A1194-19
FIG D
FIGURE 16
COMBUSTION AIR
FITTING
OPTION 1
OPTION 2
THIS CONFIGURATION TO BE USED
ONLY WITH THE DOWN FLOW ZERO
CLEARANCE KIT (RXGY-ZK)
T
OPTION 1
OPTION 2
OPTION 1
OPTION 2
THIS CONFIGURATION TO BE USED
ONLY WITH THE DOWN FLOW ZERO
CLEARANCE KIT (RXGY-ZK)
ST-A1194-03-XO
FIGURE 15
NON-DIRECT VENT
OUTSIDE AIR USING A
HORIZONTAL DUCT
OUTLET AIR 1 SQ. IN.
(6.5 SQ. CM.) PER 2000 BTUH
INLET AIR 1 SQ. IN.
(6.5 SQ. CM.) PER 2000 BTUH
ST-A1194-19
FIG E
54
Содержание *96V series
Страница 34: ...Field Conversions 34...
Страница 35: ...Field Conversions 35...
Страница 36: ...36 Field Conversions...
Страница 37: ...37 Field Conversions...
Страница 38: ...Field Conversions 38...
Страница 81: ...81 TABLE 14 SUPPLEMENTAL ORIFICE SIZE CHART HIGH ALTITUDE NATURAL GAS AT HIGH ALTITUDES cont High Altitude...
Страница 112: ...112 Diagnostics TABLE 20 continued R96V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS...
Страница 117: ...117 TABLE 20 continued R96V FAULT CODES WITH DESCRIPTIONS AND SOLUTIONS Diagnostics...
Страница 123: ...123 FIGURE 62 2 STAGE ECM FURNACE WIRING DIAGRAM Troubleshooting...
Страница 124: ...124 CM 1014...