![RFnivo rf3000 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/rfnivo/rf3000/rf3000_technical-information-and-instructions_1450404009.webp)
Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
Technical data - Electrical data
Electrical data
Connection terminals
0.14 - 2.5mm
2
(AWG 26-14)
Cable entry
M20 x 1.5 screwed cable gland
NPT 1/2“ conduit connection
NPT 3/4” conduit connection
Clamping range (diameter) of the factory provided cable glands:
M20 x 1.5: 6 .. 12mm (0.24 .. 0.47"")
Signal delay
Sensor uncovered -> covered or covered -> uncovered or covered <-> uncovered:
adjustable ca. 0.5 to 60 sec
Safety operation
(FSL,FSH)
Switchable for minimum or maximum safety
Operation frequency
ca. 100kHz
Overvoltage category
II
Pollution degree
2 (inside housing)
Electronics
Universal voltage
Relay DPDT
Power supply
21 .. 230V 50-60Hz or DC ±10%*
*incl. ±10% of EN 61010
Max. ripple of power
supply
7 V
ss
at DC sypply
Installed load
max. 1.5VA or 1.5W
Signal output
Floating relay DPDT
AC max. 250V, 8A non inductive
DC max. 30V, 5A non inductive
Display
4 digit LCD
Display of actual measured capacitance, signal
output state and self diagnostics
Min. operating temperature: -30°C (-22°F)
Indicating light
Status by 3 colour built-in LED (according to NE44):
Power on, signal output, failure /maintenance
Data storage
Nonvolatile EPROM for Menu settings and calibration data
Isolation
Power supply to signal output: 2225Vrms
Signal output to signal output: 2225Vrms
Protection class
I
RFnivo
®
1
2
3
4
5
6
7
8
9
10
11
12
RF 3000 d
gi241014
9