Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
Electrical installation
Relay protection
Provide protection for relay contacts to protect the device against spikes with inductive loads.
Protection against static
charging
The housing of the unit must be grounded in any case to avoid static charging of the unit on
applications with pneumatic conveying and non-metallic containers .
Opening the lid
Before opening the lid take care, that the unit is clean and no water or dirt can enter into the housing.
Additional Safety Instructions for Hazardous Locations
External equipotential
bonding terminal
Connect with
equipotential
bonding of
the plant
Field wiring
A pull relief must be provided for the field wiring cables, when the device is installed with the factory
provided cable glands.
Field wiring terminals for
“de” housing
Fixing torque : 0,5-0,6Nm
Remove wire isolation: 9mm
Cable glands and conduit
system for ATEX /
IEC-Ex/ TR-CU
(Dust and Gas Hazardous
Locations)
Installation according to the regulations of the country, where the product is installed.
Not used entries have to be closed with blanking elements certified for this purpose.
Where available the factory provided parts must be used.
A strain relief must be provided for the field wiring cables, when the device is installed with the factory
provided cable glands.
If other than the factory provided parts are used, following must be ensured:
The parts must have an approval adequate to the approval of the level sensor (certificate and type of
protection).
The approved temperature range must be from the min. ambient temperature of the level sensor to the
max. ambient temperature of the level sensor increased by 10 Kelvin.
The parts must be mounted according to the instructions of the supplier.
Conduit system
for FM
(
Dust and Gas Hazardous
Locations)
General requirements:
In addition the regulations of the country must be observed. The used flameproof seals and blanking
elements must have an adequate type approval and a temperature range of at least –40°C (-40°F)
to +80°C (176°F). In addition they shall be suitable for the conditions and correctly installed. Where
available the provided original parts of the manufacturer must be used.
Installation of a flameproof enclosure “d” with a conduit system:
In a conduit system single electric conductors are installed in a certified pipe system. This pipe system
is in a flameproof construction as well. The flameproof enclosure “d” and the pipe system needs to be
sealed from each other by a certified flameproof seal. Conduit entries of a flameproof enclosure “d”
shall have installed the flameproof seal within 18 inches from the enclosure wall. Not used entries have
to be closed with adequate blanking elements of a certified flameproof type Cl.1 Div.1 A.
Opening the lid
Units with Dust Explosion approval:
Before opening the lid take care, that no dust deposits or whirlings and no hazardous atmosphere is
present.
Units with flameproof GasExplosion approval (d-housing):
To prevent ignition of hazardous atmospheres, do not remove the lid (cover) while circuits are alive.
RFnivo
®
1
2
3
4
5
6
7
8
9
10
11
12
RF 3000 d
gi241014
20