Level limit switch
Series RF 3000
Technical Information / Instruction manual
page
Advanced programming - Advanced menu
Display
Explanation Menu item
Auto recalibration
F.
OFF *
ON
Auto recalibration to uncovered probe.
If may be required to do comissioning in an already filled silo (covered probe). With covered probe a
proper calibration is not possible. A solution can be to cause the unit to do a auto calibration when
the silo becomes empty (uncovered probe).
To do this, set Auto recalibration to "ON" and do a push button calibration with a covered probe
(press the CAL button for 3 seconds).
The unit will recalibrate to uncovered probe automatically after 2 minutes, if the measured
capacitance becomes 50% of the setted sensitivity (Menu item D) lower than the calibrated
capacitance. During calibration "CAL" is displayed.
Do not set to "ON" if excessive material build up is present, since this build up may decrease the
measured capacitance and causes a wrong calibration.
Note: Menu item F is not valid and will not bee shown on the display, if Manual calibration (Menu item
G) is set to "ON".
Manual calibration
The unit allows Manual calibration similar to conventional potentiometer calibration, but using a comfortable display and menu.
Procedure for Manual calibration see page 32 to 34.
G. OFF *
ON
Manual calibration ON/OFF
If set to ON:
- Menu items H-P appear.
- Menu items D (Sensitivity in Quicksart Menu) and F (Auto recalibration) are no more
valid and will be hidden.
- Push button calibration is no more possible (if CAL button is pressed, the display
states G.ON")
H.
LO *
HI
Low
High
Sensitivity
range
Low sensitivity range allows to detect a capacitance change of >=2pF
High sensitivity range allows to detect a capacitance change of >=0.5pF
See also calibration guide on page 32
Advanced menu
• When the unit is in Measurement mode, press MENU button for 10 sec to enter in Advanced menu
(keep pressed, ignore when unit goes after 3 sec to Quickstart Menue and A.FSx is displayed).
Note: If "Code" is displayed, a Lock Code is required. Set the code number with the arrow buttons and confirm with
the Menu button. Then press again the Menu button for 10 sec to enter in Advanced menu.
• Press for 3 sec to return to Measurement mode.
• Press for <1 sec to store setted value and jump to next menu item.
• Arrow buttons increase / decrease the value to be setted
Continuation next page
Note: Red LED is blinking during Menu setting
* Factory setting