Power and ground connections are made to the compression block on the rear of the RFL3200
UK-10 as shown below.
Compression block on rear of
the RFL3200 UK-10
+
-
Power Supply Label
1.
Before proceeding with the connection of power to the RFL3200 UK-10 ensure that the
power wires to be installed are disconnected at their source.
2.
If the unit is installed in a traditional cabinet type location with a station battery supply,
connect a ground wire to the rack ground; connection type and location will vary by
installation. The grounding wire should be kept as short and straight as possible, to keep its
resistance and inductance to a minimum.
3.
Carefully remove the 3-pin compression block plug from its socket, being careful not to
damage the pins.
4.
The RFL3200 UK-10 is designed for permanently wired installation in restricted access
locations only.
The RFL3200UK-10 contains fuses on both supply poles that are intended for replacement
by qualified personnel only. The following fuses are recommended
19-32V 115V, 5x20 mm, 2 amp
38-150V 250V, 5x20 mm, 1 amp
200-300V 250V, 5x20 mm, 0.25 amp
5.
Strip back and connect the positive and negative leads from the station battery to the
positive and negative connections on the compression block. If an AC supply is used the
negative and positive markings can be ignored. When installing power and protective earth
connections, expose no more than 0.2” (5mm) of bare wire. Twist the wires to prevent
strands from escaping and use care when inserting the wires into the connector. Inspect the
wires prior to energizing to ensure no strands have escaped.
6.
Reinstall the compression block into its socket.
Before connecting the power at its source, check the following: