Installation
3. Put aside the screws that are affixed to one of the cross slats,
then unscrew the 4 cross slats of the mounting frame and fold
the 8 fastening plates in the frame.
When the EASY-KGC ME/MP mounting frame is used, unfold
the drop-guard grid (90°) in the shaft.
4. Rotate the four fastening plates on the damper 90° (to the
upright position).
5. Open the shutter and position it in the mounting frame.
Fasten the shutter onto the mounting frame with the 4 screws
supplied, as shown in the drawing. Tightening the screws pulls
the shutter towards the wall until its final position.
You can also slightly correct the angle of the shutter with
respect to the mounting frame.
Connect the mechanism according to the wiring diagram.
Caution: Connecting the frame to a uneven surface can lead
to distortion of this frame. Check whether the slack between
the frame and the surface of the door is still acceptable.
Check the mobility of the shutter.