11
Installation
Installation into vertical concrete shaft with built-in mounting frame
The product was tested and approved in:
Product
Range
Wall type
Classification
Kamouflage 60 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Concrete ≥ 90 mm
EI 60 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 60 MP
350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Masonry, concrete blocks, concrete
≥ 100 mm
EI 60 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP 350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Concrete ≥ 90 mm
EI 90 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP 350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Masonry, concrete blocks, concrete
≥ 100 mm
EI 90 (v
ed
i
n
o) S 1500 C10000 AA multi
Kamouflage 120 MP 350x385 mm ≤ Kamouflage 1V MP ≤ 700x1075 mm Shaft
Masonry, concrete blocks, concrete
≥ 100 mm
EI 120 (v
ed
i
n
o) S 1500 C10000 AA multi
A=20-100 mm
A=20 mm
KAMOUFLAGE MP
EASY-KAP ME/MP
(W+
A
) x (H+
A
) mm
Mortar
1. In case the mounting frame is screwed:
Make an opening with dimensions (W+20) x (H+20) mm.
In case the mounting frame is fixed with mortar:
Make an opening with dimensions (W+20) x (H+20) mm till
(W+100) x (H+100) mm.
2. The mounting frame should always be fastened to the
concrete shaft with screws and dowels (Ø6 x minimum 60 mm,
steel or stainless steel).
For an opening with dimensions up to (W+20) x (H+20) mm:
Two fixing lugs are provided at the bottom and at the top of
the mounting frame: fold these against the shaft and fasten the
mounting frame with 4 screws Ø6 x 60 mm, taking care not to
misshape it. These screws can be inserted through any of the
punched holes in the lugs, depending on the thickness of the
shaft wall.
The finished opening must have the same size as the mounting
frame (W+10) x (H+10) mm.
For an opening with dimensions up to (W+100) x (H+100) mm:
Apply mortar around the opening to reduce the opening to
the outer dimensions of the frame, then proceed as mentioned
above to fasten the frame into the opening. Make sure that the
gap between the frame and the opening in sealed completely
with mortar.
The mortar must harden completely before the damper is
fastened to the mounting frame.
1
2