background image

4b

) Drill a drain hole.

 On the bottom side of the pipe, mark a location that 

will be outside between the end of pipe and the building (about 2/3 of the 

distance from the end of the pipe to the edge of the building) when the box 

is installed. Drill a 1/2” diameter drain hole in the pipe at that location. 

4c

) Attach the inlet air guard.

 Position the inlet air ring guard over the end 

of the combustion air pipe. See 

FIGURE 16.

 Attach the guard to the inlet air 

pipe with the four 1/2” long screws provided.

5. Attach the concentric adapter box to the wall.

 

Insert  the  combustion  air  pipe  with  inlet  guard  attached  out  through  the 

wall. Position the box so that the pipe is centered in the opening. Attach the 

brackets to the wall with field-supplied hardware. 

6. Determine length and install the “terminal-end” vent pipe.

 

6a

) Determine length of pipe.

 The length of the continuous piece of termi-

nal-end vent pipe is determined by the installation within the maximum and 

minimum requirements. See 

FIGURE 16

 to determine lengths of each seg-

ment and calculate the total length required. The “terminal-end” vent pipe 

extending through the box and concentric through the inlet air pipe must be 

one piece of vent pipe without joints. 

6b

) Drill a hole to attach the elbow at the end and install the pipe.

 Being 

sure the vent pipe is in the proper flow direction, temporarily fit the elbow 

on the exhaust end of the vent pipe. For easier future service, the elbow is 

being attached using one field-provided 3/4” long sheetmetal screw. Using 

a drill that is a size smaller than the 3/4” long sheetmetal screw, with the 

elbow pointing down, drill a pilot hole through the top center of the elbow 

socket and the vent pipe. 
Remove the elbow. In the elbow only, enlarge the drilled hole to 7/32”. The 

elbow will be attached from the outside in Step 8b). 

With the pipe turned so that the drilled hole is at the top, slide the end of 

the vent pipe out through the box and the combustion air pipe. Position the 

vent pipe so that it will extend between 3” (76mm) and 6” (152mm) past 

the end of the combustion air pipe. Adjust the pipe so that the screw hole is 

in the top center. Verify that the silicone sealing ring on the box is properly 

seated. 

Do not add sealant to the ring

Join the “terminal end” vent pipe to the vent pipe run. Re-check the silicone 

ring to be sure that it is still properly seated. 

7. Attach the indoor portion of the combustion air pipe.

  Use  sheet-

metal screws to attach the single-wall combustion air pipe run to the collar 

on the concentric adapter box. Seal with tape or sealant. 

8. On the outside, install the inlet air guard spacers, attach the elbow, 

install the bird screen, and seal or flash around the combustion air 

pipe.

8a)

 Remove the screws holding the inlet air guard (installed in Step 4c). 

Slide the spacers onto the ends of the four spokes that support the vent 

pipe. Re-attach the guard.

8b)

 Slide the elbow over the end of the vent pipe and attach it with the field-

provided 3/4” long sheetmetal screw. Slide the bird screen into the socket 

on the open end of the elbow. The elbow must be pointing down. 

7.2.2 

HORIZONTAL VENT 

TERMINAL Installation - 

Option CC6 (cont’d)

7.2 Venting and 

Combustion Air 

(cont’d) 

7. Mechanical 

(cont’d)

Form I-UEAS, Page 22

Содержание UEAS

Страница 1: ...R WARRA N T Y C ONVERGEN T Q UALITY SYSTE M CQS CQS FOR YOUR SAFETY What to do if you smell gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your build...

Страница 2: ...rne silicone substances See Hazard Levels above 1 General Table of Contents 1 General 2 4 1 1 Hazard Labels and Notices 2 1 2 General Information 3 1 3 Warranty 3 2 Unit Heater Location 4 6 1 4 Instal...

Страница 3: ...or if the air delivery sys tem is modified Model UEAS high efficiency unit heaters are design certified by ITS for use in industrial and commercial installations in the United States and Canada Instr...

Страница 4: ...es in accordance with ANSI NFPA No 88A latest edition Standard for Park ing Structures and for repair garages in accordance with ANSI NFPA No 88B latest edition Standard for Repair Garages In Canada i...

Страница 5: ...arge air along exposed walls with extra units provided to discharge air in toward the center of the area At those points where infiltration of cold air is excessive such as at entrance doors and shipp...

Страница 6: ...A conversion kit is included with the heater for converting for use with propane see instructions in Paragraph 7 1 4 Read this booklet and become familiar with the installation requirements of your p...

Страница 7: ...rt External Gas Connection S Size A B C E F G H J K M N P R S Dimensions inches 1 8 inch 130 160 20 1 8 39 3 16 16 1 16 11 15 16 2 3 8 25 11 16 50 1 2 42 13 7 16 8 5 16 4 5 16 5 1 16 6 5 16 1 3 4 260...

Страница 8: ...cture to be used to verify that it has sufficient load carrying capacity to support the weight of the unit Model UEAS Weight Size 130 180 260 310 lbs 230 245 360 395 kg 104 111 163 179 If the heater i...

Страница 9: ...ope shall be resistant to the action of lique fied petroleum gas or any other chemical constituents of the gas being supplied 7 Mechanical Sizing Gas Supply Line 7 1 Gas Piping and Pressure 7 1 1 Gas...

Страница 10: ...pply WARNING Valve outlet gas pressure must never exceed 3 5 w c for natural gas and 10 w c for propane gas For Natural Gas When the heater leaves the factory the combination gas valve is set so that...

Страница 11: ...ntact the local gas supplier Before attempting to measure or adjust valve outlet gas pressure the inlet supply pressure must be within the specified range both when the heater is in operation and on s...

Страница 12: ...outside of the heater access panel so that it will be con spicuous to anyone operating or servicing the unit Be sure the surface is clean and dry and adhere the label The input and or the capacity of...

Страница 13: ...Normal Input Thermal Output Capacity Normal Input Thermal Output Capacity Normal Input Thermal Output Capacity Feet Meters Size 130 Size 180 Size 260 Size 310 0 2000 0 610 131 000 121 830 175 000 159...

Страница 14: ...and 9B are field supplied See Paragraph 7 2 1 6 page 16 for making vent pipe joints The vent pipe drain connects into the heater condensate drain Refer to Paragraph 7 3 page 28 for condensate drain i...

Страница 15: ...cceptable alternate PVC piping arrangement for installations in the United States FIGURE 9B CANADIAN OR U S INSTALLATION Horizontal or Vertical Vent showing Where to Install the Condensate Drain Conne...

Страница 16: ...e move all burrs from the inside and outside diameter of the cut end of the pipe Chamfer bevel the end of the pipe 10 to 15 Use a clean dry cloth to remove surface dirt grease and moisture from the pi...

Страница 17: ...pe expansion when placing hangers Changes in pipe direction will allow for expansion Hangers must be placed to allow for some direction movement The slip joint at the concentric adapter is designed to...

Страница 18: ...nal vent combustion air kit is Option CC2 Heater Side View of the Concentric Adapter Box FIGURE 12 Concentric Adapter Box Dimensions 1 7 8 48mm 6 3 16 157mm 2 51mm 9 11 32 237mm 5 11 23 136mm 8 diamet...

Страница 19: ...Connections FIGURE 15 Is the Separated Combustion Vent Combustion Air System Horizontal or Vertical HORIZONTAL OR VERTICAL VENT TERMINAL Vertical Option CC2 instructions begin on page 24 Horizontal O...

Страница 20: ...ara graph 7 2 1 4 on page 16 Also read the Hazards of Chlorine on page 6 concerning location of the combustion air inlet In most applications the terminal will be on approximately the same level as th...

Страница 21: ...nd the runs close to the wall location selected in Step 1 above Provide 1 4 per foot 6mm per 305mm downward pitch of the vent pipe toward the heater for condensate to drain NOTE The vent pipe will ext...

Страница 22: ...g a drill that is a size smaller than the 3 4 long sheetmetal screw with the elbow pointing down drill a pilot hole through the top center of the elbow socket and the vent pipe Remove the elbow In the...

Страница 23: ...will have a slight downward slope to the outside The downward slope and the 1 2 drain hole Step 4b will prevent rain water from running through the pipe into the concentric adapter box Installation of...

Страница 24: ...for Vertical Vent Combustion Air Kit Option CC2 in compliance with requirements on pages 13 19 Parts in the Vertical Vent Terminal Combustion Air Package Option CC2 Components Required Factory and Fie...

Страница 25: ...bove the roof 4b Attach the combustion air pipe to the collar of the concentric adapter box with sheetmetal screws Seal joint and seam with tape or sealant 5 Attach the concentric adapter box to the u...

Страница 26: ...pipe and fasten the collar to the combustion air pipe with sheetmetal screws Seal the joint with tape or sealant See FIGURE 19 8b To prevent rain water leakage slide the rain collar over the end of th...

Страница 27: ...Separated Combustion Unit with a Vertical Vent Combustion Air Terminal Option CC2 Rear View Side View Installation of the vertical vent and combustion air system on your sepa rated combustion unit is...

Страница 28: ...since unit heaters are normally installed several feet above the floor If a gravity system is not possible a condensate pump may be installed There are a number of commercially available pumps made f...

Страница 29: ...2 or larger The trap requirements are the same for either type of drain connection NOTE In Canada all PVC vent pipe must be approved to ULC S636 FIGURE 21 Secondary Heat Exchanger Condensate Drain Tra...

Страница 30: ...inside on the bottom of the control compartment The circuit board is polarity sensitive It is advisable to check the electrical supply to be certain that the black wire is the hot wire and that the w...

Страница 31: ...ACK BK BROWN BR RED R ORANGE O YELLOW Y GREEN G BLUE BL PURPLE PR WHITE W Y W UEAS SERIES R W FUSE R DOOR INTERLOCK DISCONNECT SWITCH 14 GA BK 14 GA BK THERMOSTAT SEE NOTE 8 OPTIONAL SINGLE STAGE W FA...

Страница 32: ...stem resistance is reduced The Table below lists the approximate water column differential pressure readings and switch setpoints for sea level operating conditions for Model UEAS heaters 9 1 Thermost...

Страница 33: ...interrupt the electric supply to the gas valve If the vent temperature switch is activated identify and correct the cause before resetting the switch Refer to the Maintenance Section for information...

Страница 34: ...e venter remains energized If flame is sensed during the first 16 seconds the spark is de energized and the control proceeds to heat fan blower on delay If flame has not been sensed during the first 1...

Страница 35: ...er successful ignition the control will de energize the gas valve run the venter motor through post purge and run the fan blower motor on heat speed for the selected delay off time Ignition Retry If f...

Страница 36: ...e fan motor is energized after a 25 second delay NOTE This brief on delay is to allow the G terminal to energize slightly before Y and an external changeover relay to switch from G to W without causin...

Страница 37: ...Lockout 11 Operation 11 1 Check the Installation Prior to Startup Check to be sure that all screws used to hold shipping brackets were re installed in the heater cabinet Check the bottom panel Remove...

Страница 38: ...ian Force or attempted repair may result in a fire or explosion Should overheating occur or the gas supply fail to shut off turn off the manual gas valve to the appliance before shut ting off the elec...

Страница 39: ...essure for altitude Turn the unit off and on pausing two minutes between each cycle Observe for smooth ignition Place the packet of information containing the Limited Warranty this booklet and any con...

Страница 40: ...lly Check the burner for scale dust or lint accumulation Clean if needed Check gas valve to ensure that gas flow is being shutoff completely Check the vent combustion air system for soundness Clean op...

Страница 41: ...secondary air shield b Holding the venturi tube slide the entire burner assembly slightly to the right to disengage the burner from the supports on the left Then rotate the open end of the venturi tu...

Страница 42: ...with the same screws Check to be sure all wire connections are secure 4 Attach the Gas Train Slide the gas train so that the orifice adapter is through the bracket Fasten the gas train to the bracket...

Страница 43: ...10 and the Troubleshooting Flow Chart in Paragraph 12 3 FIGURE 29 DSI Integrated Control Module Circuit Board Only replaceable part is a Type ATC or ATO 3 amp fuse Color Code Violet P N 201685 Ignito...

Страница 44: ...12 2 Maintenance Procedures cont d 12 2 4 Ignition System cont d FIGURE 30 Ignitor showing required Spark Gap Measurement Dimension A Size inches mm 130 180 1 5 8 67 260 2 51 310 1 7 8 48 FIGURE 31 F...

Страница 45: ...ions for checking pressure settings are in Paragraph 7 1 3 FIGURE 33 Pressure Tap for Checking Gas Flow Shutoff Single Stage Valve Carefully remove external dirt accumulation and check wiring connec t...

Страница 46: ...authorized replacement part that is designed for the heater Always replace electrical box cover 12 2 10 Door Switch If it is determined that the door switch needs replacing use only a factory authoriz...

Страница 47: ...lights that indicate normal operation and various abnormal conditions If the heater fails to operate properly check this sig nal to determine the cause and or to eliminate certain causes LED is vis i...

Страница 48: ...ard is grounded to furnace chassis h Unit not properly grounded h Make certain unit is properly field grounded to earth ground and properly phased L1 to hot lead L2 to neutral i Integrated circuit boa...

Страница 49: ...amic is not cracked Replace as required 8 Cracked ceramic at sensor 8 Replace sensor 9 Incorrect polarity 9 Reverse line volt leads to integrated circuit board 10 Pin terminal loose on 9 pin plug 10 R...

Страница 50: ...8 A CSA ratings for altitudes to 2000 ft B Size shown is for gas connection to a single stage gas valve not supply line size C MOCP 2 25 x largest motor FLA smallest motor FLA Answer is rounded to the...

Страница 51: ...LS 2 Hazards of Chlorine 6 Normal Heat Cycle Operating Sequence 34 Heat Exchanger Maintenance 40 High Altitude 8 High Altitude Capacity 12 High Altitude Derate 11 Horizontal Vent Combustion Air Kit Op...

Страница 52: ...________________________ Phone _________________________________ Model No ______________ Serial No _____________________Date of Installation ____________ SPECIFIC INSTALLATION NOTES i e Location CFM H...

Отзывы: