background image

10

I-RIH (05-21) 131793-A

INSTALLATION

Pre-Installation Checklist

 

‰

Check for any damage that may have been incurred during shipment .

 

‰

If damage is found, document the damage with the transporting agency and immediately contact your distributor . 

If you are an authorized Distributor, follow the FOB freight policy procedures .

 

‰

Ensure that gas specifications and electrical characteristics of the unit are compatible with the gas and electric 

supplies at the installation site .

 

‰

Read this booklet and become familiar with the installation requirements of the unit .

 

‰

If you do not have knowledge of local requirements, check with the local gas company or any other local agencies 

who might have requirements concerning this installation .

 

‰

Before beginning, make preparations for necessary supplies, tools, and manpower .

 

‰

Before installing the unit, check the supporting structure to ensure that it has sufficient load-carrying capacity in 

accordance with 

Weights

 section .

 

‰

Mounting angle must be within the tolerance allowed .

Suspension Mounting

⚠ DANGER ⚠

The installer is responsible for suspension of the heater. Under no circumstances should either the 

gas supply line or electrical supply line to the unit be used to provide assistance in suspension. 

Do not run any gas or electric service lines above or below the heater or near the path of the flue 

products.

⚠ CAUTION ⚠

 

• If a heater is located in an aircraft hangar or near overhead doors, it should be rigidly mounted 

to prevent swinging.

 

• DO NOT ANGLE HEATERS MORE THAN 30 DEGREES OR LESS THAN 5 DEGREES. For proper 

operation, the heater must be level, whether angle-mounted at 5 or 30 degrees. The heater is NOT 

design-certified for use above 30 degrees (and voids the manufacturer’s warranty as well). A 

horizontal or zero-degree angle is not recommended because flue gases coming off the burner 

surface could potentially create an overheating condition for the gas controls. At a 5-degree 

angle, a natural upflow of flue gases safely exits the heater.

 

• All models must be installed with the gas manifold located on the low end.

 

• Check local codes for mounting requirements and for permission to use flexible gas connectors. 

Local codes may require rigid mounting. It is recommended that either the piping or the mounting 

be flexible to prevent fatigue failure from vibration and/or thermal expansion.

 

Suspend the heater with the gas manifold located on the low end using either 3/8-inch (10-mm) threaded rod for 

rigid mount or chain and S-hooks for chain mount (see 

Figure 3

, DETAIL A) . Chain with a 200-pound (91-kg) 

working load (1/0 Tenso) is recommended . S-hooks must be a minimum 1/4-inch (6 .3-mm) diameter wire and 

must be closed after installation .

 

As an exception, it is permissible to suspend the following single-burner models with the gas valve on the high end: 

RIHL unit size 050 and RIHN unit sizes 030 and 060 (see 

Figure 3

, DETAIL B) . Mount these units with the gas 

manifold (A) angled upward, the gas valve (B) toward the high side, and the mounting angle at 5- to 30-degrees .

 

If permissible by local code, it is recommended that the heater be suspended using chain and S-hooks (see 

Figure 

3

DETAIL C) . Suspend the heater as follows using either the chain and S-hooks provided in option UE1 or UE2 

or field-supplied chain and S-hooks:

a .  Securely connect one end of long chain to overhead building structure using S-hook A . Connect other end of 

long chain to back of heater using S-hook B .

Содержание RIHL

Страница 1: ...u la mort Read these instructions thoroughly before installing or servicing this equipment Lisez attentivement les instructions d installation de fonctionnement et d entretien avant de proc der l inst...

Страница 2: ...with 24VAC Direct Spark Ignition DSI Single Stage Controls 15 Wiring for Units with 24VAC Direct Spark Ignition DSI Two Stage Controls 16 FIELD INSTALLED OPTIONS 17 Thermostat Option CL34 17 Thermost...

Страница 3: ...ss DANGER A danger statement describes a potentially hazardous situation that if not avoided will result in severe personal injury or death and or property damage WARNING A warning statement describes...

Страница 4: ...micile intended for use by one or more persons and that includes one or more areas such as those used for cooking eating living sleeping or a sanitary facility A residential dwelling does not include...

Страница 5: ...the area is within the clearance to combustible material as marked on the heater rating plate Both NFPA 409 latest edition and CAN CSA B149 1 latest edition specify a minimum clearance of 8 feet 2 5...

Страница 6: ...ater cannot operate unless the supply and exhaust system is operating Mechanical exhaust fans are typically located at high points of the building For flat roof areas a series of small exhausters shou...

Страница 7: ...learances between the combustion surface and combustibles The stated clearance to combustibles represents a surface temperature of 90 F 50 C above room temperature If the unit must be close to the roo...

Страница 8: ...8 68 1727 140 3556 180 4572 Propane RIHL 050 30 762 60 1524 80 2032 48 1219 34 864 110 2794 RIHVL 090 36 914 30 762 62 1575 105 2667 50 1270 38 965 135 3429 120 46 1168 33 838 64 1635 125 3175 58 1473...

Страница 9: ...24 5 6 6 7 5 160 25 0 28 5 7 7 8 7 22 5 25 5 6 9 7 8 200 27 0 31 0 8 2 9 4 24 5 28 0 7 5 8 5 Table 6 Recommended Distances for Units Mounted at 5 Degree Angle Model Unit Size Reflector Type Maximum Di...

Страница 10: ...d at 5 or 30 degrees The heater is NOT design certified for use above 30 degrees and voids the manufacturer s warranty as well A horizontal or zero degree angle is not recommended because flue gases c...

Страница 11: ...e Piping joint compound must be resistant to the action of liquefied petroleum gases DO NOT install any gas piping in heat zones CAUTION All piping must be installed according to local codes Use new c...

Страница 12: ...ion immediately upstream of the gas supply connection to the heater see Figure 4 Test all piping joints for leaks using a non corrosive leak detecting solution Do not subject gas pressure regulators f...

Страница 13: ...the Canadian Electrical Code CSA C22 1 latest edition Theelectricalsupplywiringtotheheatersusing120VACor24VACmustbeinstalledinaccordance with local codes or the National Electric Code ANSI NFPA 70 la...

Страница 14: ...ng a temperature rating of at least 302 F 150 C and a minimum size of 16 AWG 1 0 mm2 Si l un des c bles d origine fournis avec cet appareil doit tre remplac le remplacer par un c ble convenant pour un...

Страница 15: ...ol is polarity sensitive GND 24 GGS BL BL GGS VR SW MV LEGEND 24 24 VAC Supply Voltage GND Earth Ground MV Mechanical Ventilation VR Ventilation Relay SW Ventilation Interlock Switch normally opened G...

Страница 16: ...polarity sensitive Field wiring Thermostat cable 18 4 18AWG 0 8 mm2 4 conductor solid class 2 Minimum insulation temperature 140 F 60 C between thermostat and heater Maximum length 125 feet 38 meters...

Страница 17: ...its use The installer user owner employer must determine the specific safety requirements The specific safety requirements will vary depending on the location and operating procedures Therefore approp...

Страница 18: ...entrance of foreign objects This option is not for use with a parabolic reflector option DM2 If a protective screen is required with a parabolic reflector contact the factory Figure 13 Protective Scr...

Страница 19: ...itive Proper grounding and proper electrical polarity are essential to the operation of these heaters Light the heater as folows 1 Turn manual gas valve to OFF position 2 Turn electrical supply OFF 3...

Страница 20: ...seconds Shutdown To shutdown the heater for one week or less turn OFF electrical supply to heater for more than one week turn OFF electrical supply to heater and turn OFF gas supply at gas isolation...

Страница 21: ...re 15 DETAIL B 3 Check to ensure that there is spark gap clearance of 0 219 0 032 inches 5 6 mm from ceramic tile surface to the sparking tips of electrode direct spark assembly see Figure 15 DETAIL C...

Страница 22: ...r is applied Replace combination gas valve 7 Supply manifold gas pressure too low Adjust pressure in accordance with rating plate 8 Ignition detection control defective Replace ignition detection cont...

Страница 23: ...nturi obstructed by spider web Clean venturi using bottle brush 2 Foreign matter in venturi Check and clean in accordance with Annual Maintenance section 3 Orifice partially blocked 4 Supply gas press...

Страница 24: ...________________________________________ ________________________________________________________ Phone ________________________________________________________ Model ________________ Serial No ______...

Отзывы: