background image

0710RHC8-JLNLEN 

   

 

 

 

 

 

14

/

36

 

 

7.0  E

LECTRICAL 

E

QUIPMENT

 

 

 

Warning  :  Ensure  that  when  installing  electrical 

wiring  or  cables  no  contact  is  made  with  the 

burner, heat exchanger or flue arrangement. 

Cables  or  wires  must  be  securely  fixed  so  that 

they  cannot  move.    To  protect  supply  cables  as 

good as possible we recommend to install them 

at the left side of the control compartment. 

 

7.1.1  The RHC 8000(M) heating module has been 

fully tested prior to leaving the manufacturer. 

The  constructor  shall  not  make  changes  to 

the  wiring  supplied  with  the  module. 

Electrical  connections  may  only  be  made 

using  the  terminals  provided  and  strictly  in 

accordance  with  wiring  diagram  provided 

with the module. 

 

7.1.2  RHC  8000(M)  electrical  controls 

are

  phase 

sensitive  230V  1N  50  Hz.  The  appliance 

must  be 

earthed

  after  the  installation  has 

been  completed  and  earth  continuity  test 

must be carried out. 

 

7.1.3  The  electrical  equipment  of  the  module 

complies  with  the  requirements  of:  EN 

60335-1,  EN60730-1  and  EN61058-1  or  to 

relevant  amendments.  The  constructor  must 

also  comply  with  these  requirements  when 

fitting the module. 

 

7.1.4  The  protection  of  jacket  less  appliances 

conforms  to  protection  code  IP  20.  The 

constructor  must  ensure  that  protection 

accordingly  to  at  least  IP  45  is  fulfilled  and 

mark his data/rating plate accordingly. 

 

NOTE:  IP 45 provides:

 

a)  Personal  protection  against  contact  with 

electrical components within the construction; 

b)  Degree  of  protection  within  the  construction 

against ingress of water; 

 

 

7.1.5  The  constructor  shall  test  and  inspect  fully 

the  total  appliance  prior  to  supply  including 

the following: 

a)  Earth continuity (re: CENELEC 289) 

b)  Di-electric strain (re: CENELEC 289) 

c)  Function  of  all  electrical  components 

and 

securities 

and 

operational 

inspection 

d)  Heat  input  and  test  for  good  and  clean 

combustion 

e)  Auxiliary  equipment  to  be  supplied  as 

part of the appliance 

f)  Soundness of the total gas circuit

 

 

Attention : all passages for gas pipes, etc. to 

the control compartment must be completely 

sealed ! 

8.0  C

OMBUSTION SYSTEM 

RHC

 

 

8000(

M

)

 RJL 

OUTDOOR

’ 

 

 

8.1.1  Inlets  for  combustion  air  and  flue  outlets 

shall  be  so  designed  so  that  when  an 

appliance  is  finally  installed  their 

termination  shall  be  at  least  500mm 

above deck/ground level. 

 

8.1.2.  The heating modules are delivered with all 

parts necessary for the construction of the 

jacket so that combustion can take place 

safely and in line with the Gas Appliance 

Directive.

 

 

Included  with  the  heating  module  RHC  8000 

(except for 8075 15 & 8090 18) are : 

-

  Dia  100  terminal  outlet  (length  300mm)  

(PN°60 50712 300)

 

-

  90° elbow with sealing ring 

(dia 100)

 

  (PN 60 50733 100) 

-

  Flue outlet combustion sealing ring (dia 100) 

(PN 

06 22786 104)

 

-

  Combustion air inlet protection grill

 (PN 90 79050)

 

-  Gas tube sealing ring 

(PN 06 22783 125) 

 

Included with the heating module RHC 8075 15 

& 8090 18 are

 : 

-

  Dia  130  terminal  outlet  (length  282mm)  

(PN°60 50712 130282) 

 

-

  90° elbow with sealing ring 

(dia 130)

 

  (PN 60 50733 130) 

-

  Flue outlet combustion sealing ring (dia 130) 

(PN 06 22786 134)

 

-

  Combustion air inlet protection grill

 (PN 90 

79344 07 for 8075 15 & PN 90 79344 09 for 8090 

18))

 

-  Gas tube sealing ring 

(PN 06 22783 125) 

 

Included with the heating module RHC 8000M 

are

 : 

-

  Dia  130  terminal  outlet  (length  282mm)  

(PN°60 50712 130282) 

 

-

  90° elbow with sealing ring 

(dia 130)

 

  (PN 60 50733 130) 

-

  Flue outlet combustion sealing ring (dia 130) 

(PN 06 22786 134)

 

-

  Combustion air inlet protection grill

 (PNs 90 

79344 10 for 8125M, 90 79344 14 for 8150M, 90 

79344 12 for 8175M & 90 79344 08 for 8200M)

 

-  Gas tube sealing ring 

(PN 06 22783 054) 

Содержание RHC 8000 DJL

Страница 1: ...ndler or as part of an air handling system These appliances meet the following EC Directives Dir 2009 142 EC GAD Dir 2004 108 EC EMC Dir 2006 95 EC LVD Dir 2006 42 EC MD annexe ll sub B Subject to mod...

Страница 2: ...2 8200M 24 Are destined to be incorporated in other machines air handlers or to be combined with other machines air handling systems and are for this reason not entirely in compliance with the machine...

Страница 3: ...ON 13 7 ELECTRICAL EQUIPMENT 14 8 COMBUSTION CIRCUIT RHC 8000 M RJL 14 9 COMBUSTION CIRCUIT RHC 8000 M DJL 17 10 PRESSURE DROP INFORMATION 20 11 HEATING SECTION WITH BY PASS CHANNELS 23 12 INSTALLATIO...

Страница 4: ...apply to the models RHC 8000 M RJL DJL gas fired fan assisted warm air heaters 2 2 Models RHC 8000 M RJL are intended for use in appliances as outdoors roof top systems Models RHC 8000 M DJL are inte...

Страница 5: ...s Figure 1 Side view Figure 1a RHC 8000 DJL RJL not 8125 8150 8175 8200 n 59014_01 Figure 1b RHC 8125M 8150M 8175M DJL RJL Figure 1c RHC 8200M DJL RJL n 59710_01 n 59706_01 a 1 Gas connection 2 Flue o...

Страница 6: ...0710RHC8 JLNLEN 6 36 Figure 2 Top view Figure 2a RHC 8000 DJL RJL not 8125 8150 8175 8200 n 59014_02 Figure 2b RHC 8125M 8150M 8175M DJL RJL n 59710_02 Figure 2c RHC 8200M DJL RJL n 59706_02 a...

Страница 7: ...B C Y A1 A2 D A1 A2 D 8030 06 531 66 100 1244 65 466 100 65 466 100 8045 09 741 50 160 1244 85 656 130 160 581 100 8050 06 531 66 100 1844 85 446 130 65 466 100 8060 12 950 125 175 1244 85 865 130 160...

Страница 8: ...e view RHC 8200M DJL RJL Dimensions applicable to model RHC 8000M see fig 1b 1c 2b 2c 3b 3c RHC 8000 M DJL RJL Type A A1 A2 A3 A4 D 8125M 15 1272 183 1089 741 531 130 8150M 18 1481 183 1298 741 741 13...

Страница 9: ...70 400 400 400 8090 18 1369 1299 1244 1170 400 400 400 8100 12 950 880 1844 1170 400 400 400 8125M 15 1272 1202 1844 1770 400 460 420 8150M 18 1481 1411 1844 1770 400 460 420 8175M 21 1691 1621 1844 1...

Страница 10: ...8050 06 6200 7150 50 00 24 00 14 40 8060 12 7500 8750 60 50 28 60 17 10 8075 09 9300 10790 75 00 35 40 21 20 8075 15 9300 11900 74 98 35 27 35 27 8090 18 11200 14300 90 09 43 16 43 16 8100 12 12400 1...

Страница 11: ...in figure 6 Example expected minimum inlet temperature 5 C minimum required temperature rise shown on the chart 13 K Table 3 indicates the heat output kW of the different models The maximum allowable...

Страница 12: ...containing RHC 8000 M heating modules shall be so constructed that it is fully protected against the rigours of the environment in which it is intended to operate 5 1 2 When applied as an RJL roof top...

Страница 13: ...under normal operating conditions Viewing ports may be necessary Ensure no flammable substances are in the immediate environment of the heating module 6 0 GAS CONNECTION RC or RC 1 Attention All RHC 8...

Страница 14: ...ctric strain re CENELEC 289 c Function of all electrical components and securities and operational inspection d Heat input and test for good and clean combustion e Auxiliary equipment to be supplied a...

Страница 15: ...not obstructed Make sure the installation of the combustion inlet grill is securely fixed The outlet combustion sealing ring dia 100 PN 06 22786 104 dia 130 PN 06 22786 134 must be installed in the f...

Страница 16: ...RHC 8150M 322 225 1 405 2 RHC 8175M 322 225 1 405 2 RHC 8200M 322 580 1 minimum 2 maximum HOLE 112mm or 142mm REQUIRED TO RECEIVE SEALRING PN 06 22786 104 or 06 22786 134 HOLE 50mm or 67mm REQUIRED TO...

Страница 17: ...be via strain relief bushings It is recommended that sealing is accomplished by the use of the sealed ring type Connections between the burner module controls compartment must be effectively sealed fr...

Страница 18: ...sure within the compartment remains neutral 9 1 8 A viewing port for the purpose of ascertaining the operation of the burner should be included The viewing port may be located behind a door or panel p...

Страница 19: ...ES WITHIN THE COMBUSTION CIRCUIT 1 Combustion air inlet pipe 2 Flue outlet pipe 3 Teflon sealing ring 4 90 bend 5 Gas passage grommet vinly Rc or Rc 1 PN 06 22783 125 or 06 22783 054 Not delivered wit...

Страница 20: ...0 PRESSURE LOSS THROUGH HEATING MODULE 10 1 The charts below indicate the pressure drop over the heating module versus the air flow volume through the heat exchanger enclosure see fig 4 and table 2 1...

Страница 21: ...6 17 18 19 20 21 22 23 25 27 T T 20100 m h 23300 m h 21500 m h 24000 m h 11 12 13 14 15 16 17 18 19 20 21 22 23 25 27 29 Pressure loss through a single RHC8000 module 9300 m h 11900 m h 11200 m h 1430...

Страница 22: ...12 13 14 15 16 17 18 19 20 21 22 23 24 24 23 22 21 20 19 18 17 16 15 14 13 12 11 T T 15600 m h 18200 m h 18000 m h 21000 m h Pre ss ure loss e s through RHC8000M m odule 0 25 50 75 100 125 150 175 16...

Страница 23: ...8000M models 11 2 1 This calculation is applicable for total airflow conditions above V2 table 7 11 2 2 Consequently the perforated inlet plate must NOT be installed and must not be applied in combina...

Страница 24: ...s x1 Recommended by pass dim A or C as calculated in section 11 1 x2 Applied by pass dim mm Then VHS air flow through heat exchanger enclosure can be calculated as As explained above the air flow VHS...

Страница 25: ...0710RHC8 JLNLEN 25 36 Figure 13a Figure 13b FRONT VIEW SIDE VIEW...

Страница 26: ...2 2 Maximum airflow through heat exchanger enclosure The recommendations as described in section 4 1 2 are applicable for RHC units when installed in series Checking the possibility of condensation f...

Страница 27: ...2x RHC8075 09 2x RHC8100 12 24 28 32 36 40 44 48 24 28 32 36 40 44 48 24 26 28 30 32 34 36 38 40 44 48 T 2xRHC8050 06 T 2xRHC8075 09 T 3xRHC8100 12 Pressure losses through 2 RHC8000 heating modules 3...

Страница 28: ...9 28 27 26 25 24 23 38 36 34 33 32 31 30 29 28 27 26 25 24 23 40 42 44 46 48 T 2x T 2x 15600 m h 18200 m h 18000 m h 21000 m h Pressure losses through 2 RHC 8000 heating modules in series 9300 m h 119...

Страница 29: ...38 36 51 49 47 45 43 41 39 37 T 3xRHC8050 06 T 3xRHC8075 09 T 3xRHC8100 12 Figure 14e PRESSURE DROP FOR 3 UNITS IN SERIES Figure 14f Pressure losses through 2 RHC8000M in series 0 50 100 150 200 250...

Страница 30: ...2 50 48 46 44 42 40 38 36 50 48 46 44 42 40 38 36 50 48 46 44 42 40 38 36 T 3xRHC8030 06 T 3xRHC8045 09 T 3xRHC8060 12 Pressure losses through 3 RHC 8000 heating modules in series 13000 m h 15800 m h...

Страница 31: ...0 36000 38000 40000 42000 44000 46000 48000 50000 52000 Airflow m h through heat exchanger enclosure Pressure loss Pa 3x RHC8125M 15 3x RHC8150M 18 3x RHC8175M 21 3x RHC8200M 24 34 36 38 40 42 44 46 4...

Страница 32: ...ximum by pass dimensions for a given air flow Vtot can be calculated as follows Vtot is the air flow expressed in m s FOR 2 UNITS IN SERIES a By pass besides heat exchanger Model dim B mm factor R1 fa...

Страница 33: ...lated in section 11 1 x2 Applied by pass dim mm Then VHS air flow through heat exchanger enclosure can be calculated as As explained above the air flow VHS through the heat exchanger enclosure must be...

Страница 34: ...properly install on the collar of the combustion ventilator outlet a pipe with dia 130mm and 200mm length and a 45 elbow both made of thick wall aluminium now unit 2 is ready for mounting the vertica...

Страница 35: ...40 74 98 10 14 6 43 0 282 35 27 35 27 8090 18 109 88 99 00 90 09 12 16 7 72 0 282 43 16 43 16 8100 12 120 00 108 40 100 00 13 32 8 57 0 153 46 60 28 00 Gas rate 3 Heat input Heat output G25 G31 Power...

Страница 36: ...00 300 2x 10 10 8150M 18 18 3 00 300 2x 10 90 8175M 21 21 3 00 300 2x 11 60 8200M 24 24 3 00 300 2x 12 00 Table 11 Injector size and burner pressure G31 propane inlet pressure 30mbar Injector size Mod...

Отзывы: