14.0 I
NSTALLATION OF MULTIPLE
RHC….
DJL
UNITS WITH VERTICAL
FLUE OUTLET
(
not applicable for
RHC 8000M models
)
14.1
Attention : remove the 90° elbow (mounted on
the flue combustion ventilator). This applies
to
all
models.
14.2
Mounting possibilities
14.2.1 2 units in series
(see fig. 16, drw. 1, units 1 & 3)
The vertical flue can directly be mounted on
the collar of the combustion ventilator.
Refer to drw. 2, units 1 & 3 for the correct
positioning of the flue pipe passages with
sealing rings.
14.2.2. 2 units in parallel (one on top of the other)
Attention : this configuration can only be
realised with the units 8045 09/8075 09/8060
12 & 8100 12 installed as underframe.
* turn the combustion ventilator housing of
unit 2, with 45° to the right (see fig. 16,
drw. 1, units 1 & 2).
* remove motor and wheel of the
combustion fan.
* unscrew the 3 fixation screws fixing the
motor fixation plate with the venter
housing.
* turn the housing 45° to the right and use
the 3 remaining fixation holes in the blower
mounting plate to fix the housing properly.
* install on the collar of the combustion
ventilator outlet a pipe with dia 130mm and
200mm length and a 45° elbow, both made
of thick wall aluminium..
* now unit 2 is ready for mounting the
vertical flue pipe. For safety reasons it is
recommended to provide the vertical flue
pipe with proper insulation inside the
cabinet. We refer to drw. 2, units 1 and 2
for the positioning of the flue pipe
passages with sealing ring.
14.2.3 2 units in series & 2 units in parallel (4 units in
total)
*
units 1 & 3
: follow the same steps as
described in section 14.2.1
*
unit 2 :
follow the same steps as described
in section 14.2.2
*
unit 4
: proceed as follow (see drw 3):
Install on the collar of the combustion
ventilator outlet a 45° bend of thick wall
aluminium
Then, mount on this bend a thick wall alu
pipe with a length of 300mm and dia
130mm.
Install finally a thick wall alu elbow of 45°
on this pipe
* After carrying out the above-described
instructions, it becomes possible to
provide the 4 units with a vertical flue
pipe.
* Inside the cabinets, it is recommended to
provide the vertical flue pipes of the units
2 & 4 with proper insulation.
* We refer to drawing 2 for the positioning
of the flue pipe passages with sealing
rings
Figure 16
Drawing 1