Form I-RA/D 140/235 (Version A), Page 8
Heater
Placement
Do not attempt to install this heater until you have read and
understand this manual!
Placement is critical to the efficient operation of this heater.
Measure all distances to comply with the specific code requirements
and minimum clearances listed below.
Refer to the section on Venting your heater for vent requirements
and recommendations.
Locate the heater so that suitable means shall be provided to facili-
tate regular cleaning and maintenance of the heater (i.e. permanent
platform, portable stairs, ladder, etc.).
WARNING: You must comply with all requirements
on distance from heater to combustibles.
Fan Models
Blower Models
RA140/235
RAD140/235
inches
mm
inches
mm
Top
2
51
6
152
Front
48
1219
48
1219
Side
(Burner)*
Canada
6
152
6
152
United
States
18
457
18
457
Side
(Opposite
Burner)*
Canada
6
152
6
152
United
States
18
457
18
457
Rear*
24
610
6
152
Bottom
6
152
6
152
Flue Pipe
Canada
9
229
9
229
United
States
18
457
18
457
*Allow for service access.
In Canada, for additional information on installation clearances, refer
to CAN/CSA-B139-M91, “Installation Code for Oil Burning Equipment,”
Clause 7.0 - Installation Clearances.
WARNING: Clearances apply to all combustibles.
Do not leave paper, rags, or any moveable combus
-
tibles near the heater or store gasoline or any other
flammable fluid near this appliance.
Minimum
Clearances
from