Mounting the
Heater
Weights
Before suspending the unit, check the supporting structure to ensure
it has sufficient load-carrying capacity to support the weight of the
heater.
�����������������
�������������
����������������
��������������������
������������������
����������������
���������������
����������������
����������������������
�������������
������������������
Model
Net
Weight
lbs
kg
RA140
290
132
RA235
343
156
RAD140
352
160
RAD235
410
186
Use four 1/2”-13 diameter threaded rods. Lock each threaded rod
using a washer and nut as shown in the illustration below. Or, use
optional swivel connections (Option CK10) and field-provided 1”
threaded pipe. Lock swivel connections as shown in the illustration.
Remove the shipping crate bottom from the unit.
Remove the angle clips and re-insert the screws into the heater
cabinet.
WARNING: This heater must be supported level for
proper operation. Do not place or add additional
weight to the suspended heater.
Suspension