Form I-RA/D 140/235 (Version A), Page 44
Bleed oil from
burner tee bleeder
for ten minutes.
Is stream of oil
perfectly solid and
continuous with no
sign of air?
Are the heat
exchanger tubes restricted
with ash?
Clean the combustion
chamber and heat
exchanger.
Is the fuel of a
type specified for this
heater?
Is the
overfire and flue
draft correct?
Is the CO2
adjustment correct?
Check the air supply
from the compressor to
the nozzle for leaks and
restrictions.
Check the end cone
for deterioration
and/or restrictions.
Check oil delivery
system. See Chart
No. 7.
Adjust for proper
CO2.
Adjust barometric
damper.
Change to a
suitable fuel.
Run vacuum
test on suction line to
check for air leaks. Did suction
line pass vacuum
test?
Repair suction line
leak.
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Chart No. 5 - Thermostat calling for heat.
Burner operation erratic/unstable flame pat
-
tern.
Refer to illustration on page 38.
Troubleshooting
Continued