background image

0108X1DHGBEN

10

EURO-X

Model

Heat input

kW

Low level

cm²

1025

30.28

140

1030

34.94

160

1035

43.26

200

60 kW

1045

52.00

240

1055

64.70

290

1075

88.95

340

60 kW

1095

118.70

410

4.3 Where it is known that the air change rate is less than

0.5/h or where the building volume is less than 4.7m³

per kW of heat input, ventilation grilles must be

provided at low level i.e. below the level of the

appliance flue connection. In cases where doubt

exists over the air change rate additional ventilation

must be provided.

For air heaters of heat input less than

60 kW the total minimum free area shall not be less

than 4.5 cm² per kW of total rated heat input as table

5 below.

For our heaters of heat input 60 kW or more the total

minimum free area shall not be less than 270 cm²

plus 2.25 cm² per kW in excess of the 60 kW rated

heat input.

4.4

Table 5. Air Supply Requirement for Combustion &

Ventilation.

Note :

 Ventilation grilles must be installed so that air

is drawn directly from outdoors. In the event that

communication from the space where the heater is

installed to outdoors is via another room then the

route to outdoors must be ducted through the

communication area.

The grille velocity for all air supply must not exceed

2.0 m/s.  Grilles should be sited where they cannot

easily be blocked or flooded. Notices should be

provided advising about the need to keep air supply

grilles unobstructed.

4.5 Where mechanical ventilation is used it shall be by

mechanical inlet with either mechanical or natural

extraction.  Automatic means of control such as

interlocks must be provided. 

The function of other ventilation plant in the zone

must be taken into account.  At no time should it be

possible to create a negative pressure in the zone as

this will lead to a hazardous situation whereby the air

heater flue will act as a pressure relief.

4.6 EURO-X 1000 D air heaters which are used in the free

blowing mode i.e. without discharge air ducting are

installed within the room to be heated If it is

necessary to install the air heater in a separate room

and blow the air into an adjoining room, then return

air should be ducted to the appliance.

EURO-X D air heaters may be used for fresh air and/or

return air as combined heating/ventilation appliances

within an air handling system.

Содержание EURO-X 1000 D

Страница 1: ...ue Gas Fan as Type B14 Appliances This document applies to EURO X 1000 D appliances with Thermoelectric or Hot Surface Ignition burner controls These appliances meet the following EC Directives Dir CE...

Страница 2: ...he country concerned Such instructions may be obtained upon request from your supplier 1 5 Check that the local distribution conditions of electricity supply type of gas and pressure and adjustment of...

Страница 3: ...g h 2 16 2 49 3 09 3 71 4 62 6 35 8 48 Gas service connection not supply line size Rc Electrical service protection class IP 20 230 240V 1 N 50 Hz Total electrical rating 4 kW Weight net kg Weight shi...

Страница 4: ...2 COMBUSTION CIRCUIT DEW POINT OCCURRENCE CHART Note If operation within the condensation zone is unavoidable due to by pass restrictions optional AISI 316 stainless steel combustion circuit componen...

Страница 5: ...Table 3 DIMENSIONS REFERENCE FIGURE 3 MODEL EURO X 1025D 1030D 1035D 1045D 1055D 1075D 1095D A1 Width overall 520 590 730 870 1080 1360 E Flue centres 290 325 395 465 570 710 Flue internal dia mm 130...

Страница 6: ...ement when ordering type D models Opposite handing of the appliances may be required Whilst the air may be passed through the appliance from either end provision for locating the thermal over heat lim...

Страница 7: ...0108X1DHGBEN 7 FIGURE 4 SUGGESTED ARRANGEMENTS FOR APPLYING MULTI HEATER COMBINATIONS...

Страница 8: ...d 5 3 Fastening through all members 5 4 Checking alignment and joint worthiness 5 5 Applying gasket seals to prevent air leakage 5 6 Sectional view of completed joint Legend Figure 5 5 1 Cut and assem...

Страница 9: ...4 1 It is essential that sufficient fresh air is provided for combustion and room ventilation Most traditional building constructions have a natural air change rate of at least 0 5 h Where it is know...

Страница 10: ...heater is installed to outdoors is via another room then the route to outdoors must be ducted through the communication area The grille velocity for all air supply must not exceed 2 0 m s Grilles sho...

Страница 11: ...e with the following formula Where D1 new flue size required D2 diameter of largest flue D3 diameter of additional flue Never connect an additional flue to a main stack at a 90 angle an inverted Y pie...

Страница 12: ...ird of vertical height Refer to clause 5 4 page 11 for formula NOTE FIGURES 7 8 9 DEPICT EURO X 1000 S AIR HEATERS SAME FLUE DATA APPLIES FOR EURO X 1000 D Figure 7 RECOMMENDED FLUE CONNECTION Figure...

Страница 13: ...y suitably qualified persons observing the rules in force 7 2 Check that the electrical specification is in accordance with the specified data on the air heater A unique appliance wiring diagram is su...

Страница 14: ...n knob to Flame position NOTE If ignition burner has not lit wait five minutes and repeat the lighting procedure Having established the ignition burner set control to Flame position appliance operatio...

Страница 15: ...er which time the gas valve s will open and the burner will be lit 8 7 5 If the burner has not lit within 5 seconds the electronic flame relay will switch off and lockout will occur This will cause th...

Страница 16: ...out Following this manual intervention is necessary to restart the air heater by relighting the ignition burner or resetting an automatic burner control after the air heater has cooled and the LC3 con...

Страница 17: ...upon completion of service and that motors fans and guards are fixed securely 9 5 Heat exchanger To be checked when carrying out burner and flue section work Inspect heat exchanger where visible insid...

Страница 18: ...damage valve bodies which are constructed from soft die cast aluminium It is necessary to remove the burner manifold from the burner ribbon tray assembly to unscrew the gas valve FIGURE 15 DRAUGHT DIV...

Страница 19: ...he ignition burner and its relationship to the flame proving thermocouple NOTE Location of the spacer rings when replacing a thermocouple Ensure that pilot flame plays on thermocouple hot tip only i e...

Страница 20: ...minals 5 Thermal overheat control LC3 6 Limit control LC1 plus LC2 on models 75 95 7 Thermal fan control 8 Ignition burner 9 Thermocouple 10 Burner ribbon 11 Burner manifold with gas jets 12 Burner ga...

Страница 21: ...terminals 4 Controls fuse 5 Automatic electronic burner control 6 Gas valve 7 Hot surface ignition 8 Burner ribbon 9 Burner manifold 10 Burner fail indicator 11 Burner gas pressure test point 12 Therm...

Страница 22: ...25801 140 1 40 mm 1095 LPG Thermocouple connector TE 03 25261 SIT 1025 1045 Thermocouple connector TE 03 25154 760 Honeywell 1055 1095 Thermocouple set TE 35 25087 Bul 18 ALL Olive fitting Valve end T...

Страница 23: ...e main burner jets to the size as given in 10 1 b Change the ignition burner jet as given in 10 1 c Set burner primary air shutter as appropriate referring to figure 20 d Adjust gas governor Natural g...

Страница 24: ...m thermostat in warm air flow check temperature around thermostat Room thermostat on vibrating surface check contacts chattering near set points Fan rotating slowly heater operating on thermal limit c...

Страница 25: ...cause irritation to the respiratory tract As with any dust pre existing respiratory condition and lung diseases may be aggravated Prolonged exposure for the purposes envisaged pertaining to this Rezn...

Страница 26: ...ombined combustion heat exchanger The gas burner is controlled by a gas valve which is switched via external controls i e a room thermostat and time switch EURO X 1000 D air heaters are available with...

Страница 27: ...Keep start button depressed 20 seconds after ignition burner has lit g Close burner compartment access door h Switch ON electricity supply to the air heater i Adjust room thermostat to desired tempera...

Страница 28: ...heater is not used for heating purposes e g in summer months a Switch ON mains electricity supply to the air heater b Switch ON the manual override switch on remote control panel 14 10 Important In t...

Страница 29: ...s recommended initially to ascertain routine service intervals Where local environmental circumstance change e g different processes being carried out in a factory the service interval should be recon...

Страница 30: ...znor OPTIONAL ELECTRONIC CONTROL PANELS SAVING ENERGY AND OPTIMISE THERMAL COMFORT Reznor Europe N V J M Sabbestraat 130 B8930 Menen Belgium Tel 32 0 56 52 95 11 Fax 32 0 56 52 95 33 e mail reznor_eur...

Отзывы: