SECTION 11 GAS CONVERSION
11.1
Reznor EURO-X 1000 D air heaters are designed
to operate on natural, propane or butane gas
and will be supplied fitted for the gas type
ordered.
In the event of site conversion to a different
gas type it is be necessary to convert the gas
burner and burner controls.
To carry out the conversion refer to section 9
of this document which explains how to
remove and replace the burner assembly.
11.2
The following changes must be made:
a.
Change the main burner jets to the size
as given in 10.1;
b.
Change the ignition burner jet as given in
10.1;
c.
Set burner primary air shutter as appropriate
referring to figure 20;
d.
Adjust gas governor;
Natural gas to setting pressure as per data
plate supplied;
LPG gases to maximum pressure setting
adjuster screwed in to stop. Seal governor
after setting.
For LPG gases a governor blank off plate
may be used, remove governor and fix
plate;
e.
Affix new data plate and gas type over-
sticker
11.3
Upon completion of conversion re-commission the
air heater in accordance with section 8 of this
document.
Figure 20.
GAS CONVERSION DATA
Air shutter setting Natural gas
Air shutter setting Propane/Butane gas