0108X1DHGBEN
9
EURO-X..D
Model
Heat Input kW
Room
Volumes m
3
1025
30.28
142
1030
34.94
165
1035
43.26
203
1045
52.00
245
1055
64.67
304
1075
88.96
418
1095
118.70
558
FIGURE 6
AIR HANDLER APPLICATION RECOMMENDATIONS WHEN USING ELBOWS FOR APPLIANCE CONNECTIONS
Elbow with turning vanes from below
Square heel elbow from below
Round heel elbow from below
GOOD
BAD
BAD
Elbow with turning vanes from the side
Square heel elbow from the side
...
Round heel elbow from the side
GOOD
BAD
BAD
SECTION 4 AIR SUPPLY for COMBUSTION & VENTILATION
4.1 It is essential that sufficient fresh air is provided for
combustion and room ventilation. Most traditional
building constructions have a natural air change rate
of at least 0.5/h. Where it is known that the air
change rate is at least 0.5/h and where the volume
of the heated space is greater than 4.7m³ per kW of
total rated heat input, additional ventilation is not
required.
If the minima volumes stated above exist as table 4.
together with appropriate similar allowances for other
combustion plant that may be installed in the same
space or zone, then additional ventilation is not
required.
4.2
Table 4
.:
Building volume limits for Reznor EURO-X
Air Heaters based upon 4.7m
3
per kW of rated heat input
for one air heater only
.