Euro-C 4000 RJL-GBEN
3/26
When installed in Great Britain the total installation
must comply with the requirements and
recommendations of British Standard BS 6230
1991 “Installation of Gas Fired Forced Convection
Air Heaters for Commercial and Industrial Space
Heating". The installation must also be in
accordance with the relevant requirements of “The
Gas Safety (Installation and Use Regulations) and
“Amendment regulations 1990” and “Electrical
Regulations” (in GB the IEE Regulations). The
requirements of the “Local Building Standards
Office”, the premise “Insurance” undertaking and
the “Fire Office” must also be observed.
When the external control calls for heat, an
electronic control begins the ignition sequence to
provide for a safe start. Under normal conditions
the fan motor runs constantly and after a call for
heat it switches the heater on through a room or
duct stat. However, in some applications, about 30
seconds after the call for heat, the fan control relay
will activate the fan motor of the air handler. The
electronic control will supervise the flame during
the entire heating cycle to ensure safe operation.
When the required room temperature is reached,
the main burner will shut down leaving the fan
running to cool down the heat exchanger
After approximately 45 seconds, the fan delay relay
will turn off the fan (if wired).
1.2 Warranty
Warranty is void if:
a)
Model EURO-C 4000 RJL heaters are installed
in atmospheres containing flammable vapors
or atmospheres containing chlorinated or
halogenated hydrocarbons or atmospheres
containing any silicone, aluminum oxide, etc.,
that adheres to spark ignition flame sensing
probes.
b)
The installation is not in accordance with these
instructions.
c)
The maximum airflow through the heat
exchanger tubes is not respected (see§ 3.5).
d)
The minimum required air delivery is not
respected (see table 3a)
e)
The duct dimensions do not comply with the
prescribed dimensions (see table 3b)
f)
The inlet temperature (measured at the heat
exchanger inlet) is lower than the value stated
on the chart (see figure 5).
2.0 TECHNICAL DATA
2.1 Specifications
Table 1 - Model EURO-C 4000 RJL Specifications
Model
Heat input
Heat
output
Gas rate
3
Power
Consumption
G20
G30
G31
kW gros
1
kW net
2
kW
m³/h
kg/h
kg/h
kW
4011
13.20
11.91
10.8
1.26
0.96
0.94
0.153
4015
17.60
15.85
14.5
1.68
1.28
1.26
0.153
4018
22.00
19.81
18.0
2.10
1.61
1.57
0.153
4024
29.30
26.38
24.0
2.79
2.14
2.10
0.153
4030
36.60
33.00
29.8
3.49
2.67
2.61
0.153
4036
44.00
39.60
35.8
4.20
3.21
3.14
0.153
4047
56.60
51.00
46.4
5.40
4.13
4.04
0.153
4060
73.30
66.00
60.00
6.99
5.35
5.23
0.153
4072
87.90
79.15
72.00
8.39
6.42
6.28
0.153
4100
122.00
110.00
98.00
11.64
8.91
8.71
0.153
Notes to table 1:
1.
GCV (Hs)
2.
NCV (Hi)
3.
Natural gas G20 gross calorific value 10,48 kW m
3
@ 15 °C, 1013,25 mbar
Butane gas G30 gross calorific value 13,7 kW/kg
Propane gas G31 gross calorific vale 14,0 kW/kg