Euro-C 4000 RJL-GBEN
21/26
8.2 Ignition Controller Lockout indicator Light Repeatedly Comes "ON"
WARNING
: Fault finding may only be carried out by appropriately qualified persons
no
yes
no
yes
no
no
yes
no
yes
yes
no
yes
no
no
Correct polarity
Does the inlet gas
pressure agree with the
data badge
Is polarity of mains
correct?
Remove corrosion
& scale from flame
sensing rod & clean
ceramic insulation
Wait 15" and press
reset button
Is a spark visible ?
Check flame signal. Is it
greater than 1,0 micro
Amps?
Check flame signal using
micro amp meter. Is signal
greater than 1,0 micro
Amps?
During 5" trial for ignition
is a flame visible in ths
view port?
correct the gas supply
pressure
During 5" trial for
ignition is a spark
visible?
Check electronic
ignition control
Check spark gap
and ceramic &
check spark wire &
connector
check
electronic
ignition
control
Place in normal
operation
check multi
functional
gas valve
Spark visible, still no
flame
Is there 220 to 240V
between terminals
5 & N
Check electronic
ignition control