Euro-C 4000-JLGBEN
16/31
NOTE: IP 45 provides:
a) Personal protection against contact with
electrical components within the
construction;
b) Degree of protection within the construction
against ingress of water.
7.1.4 The constructor shall test and inspect
fully the total appliance prior to supply
including the following:
a) Earth continuity (re: CENELEC 289)
b) Dielectric strain (re: CENELEC 289)
c) Function of all electrical components
and securities and operational
inspection
d) Heat input and test for good and
clean combustion
e) Auxiliary equipment to be supplied
as part of the appliance
f)
Soundness of the total gas circuit
8.0 Combustion Circuit EURO-C
4000 RJL
8.1.1 Inlets for combustion air and flue outlets
shall be so designed so that when an
appliance is finally installed their
termination shall be at least 500mm
above deck/ground level.
8.1.2. The heating modules are delivered with
all parts necessary for the construction of
the jacket so that combustion can take
place in a full save manner.
Consequently included with the heating
module are :
-
Û
100 terminal outlet length 300mm
(PN°60 50712 300)
-
90° elbow with sealing ring
(dia 100)
(PN 60 50733 100)
-
Flue outlet combustion air inlet panel
assembly
(PN 81 74076)
-
Û
100 flue pipe (model 4100 only)
(PN
60 20124 500)
- Gas tube sealing ring
(PN 06 22783 125)
The 90° elbow, the terminal outlet and
the flue outlet panel assy must be
installed according to figure 7. All
sealing must be correctly placed in the
tubes to avoid flowing back of
combustion products to the burner. As
indicated, the flue outlet panel assy (PN
81 74076) must be integrated in the side
panel of the controls compartment. The
dimensions of the required opening in this
side panel and its position relative to the
mounting flange of the EURO-C 4000
RJL heating module are indicated in
figure 8a & 8b. It is recommended to
properly seal the flue outlet panel assy.
When installing, respect top and bottom
of the flue outlet/combustion air inlet.
The protection cap (PN 60 50712 300)
must be fitted in a horizontal plain.
Remark :
for model EURO-C 4100 RJL, the
position of the flue outlet terminal
(dimension 333,2mm) (fig. 8b) can be
adjusted by reducing the length of the
500mm long flue pipe (PN 60 20124
500).
Содержание EURO-C 4000 DJL
Страница 5: ...Euro C 4000 JLGBEN 5 31 Figure 1 Dimensions EURO C 4011 15 RJL DJL Fig 1 A Fig 1 B...
Страница 6: ...Euro C 4000 JLGBEN 6 31 Fig 1 C...
Страница 7: ...Euro C 4000 JLGBEN 7 31 Figure 2 Dimensions EURO C 4018 72 RJL DJL Fig 2 A Fig 2 B...
Страница 8: ...Euro C 4000 JLGBEN 8 31 Fig 2 C...
Страница 9: ...Euro C 4000 JLGBEN 9 31 Figure 3 Dimensions EURO C 4100 RJL DJL Fig 3 A Fig 3 B...
Страница 10: ...Euro C 4000 JLGBEN 10 31 Fig 3 C...
Страница 18: ...Euro C 4000 JLGBEN 18 31 Figure 8a models 4011 72 Figure 8b model 4100...
Страница 19: ...Euro C 4000 JLGBEN 19 31 Figure 8c all models Figure 9a models 4011 72...
Страница 22: ...Euro C 4000 JLGBEN 22 31 Figure 10b MODELS 4011 72 MODEL 4100...
Страница 24: ...Euro C 4000 JLGBEN 24 31 Figure 12 Models 4011 72 Model 4100...