background image

Euro-C 4000-JLGBEN 

 

15/31

 

CAUTION 
 

Alterations to the burner and/or its controls, any 
other electrical apparatus supplied as part of the 
heating module or changing of the settings as 
supplied is strictly forbidden to do so is  in 
contravention of the E.C. gas appliance directive 
1990. 

 
 

5.1.6  Thermal insulation used in the 

construction of a heating module 
enclosure shall maintain its insulating 
properties under the influence of heat 
mechanical stress and ageing, it shall be 
non- combustible and resistant against 
vermin. Ensure that any insulation is 
securely fixed and will not obstruct 
combustion air pathways. 

Asbestos or materials containing 
asbestos may not be used. 
All materials used in association with 
EURO-C 4000 modules must be in 
accordance with the combustibility 
requirements of ISO 1182 1990. 
 

5.1.7  Where appliances containing EURO-C 

4000 modules are intended to be 
installed at a height of 1,8 m above floor 
level, doors, panels etc. intended to be 
removed for servicing shall be provided 
with hinges, or restraining devices to 
prevent falling from above during 
servicing. Access panels must be readily 
capable of correct and easy removal and 
assembly, this feature is particularly 
appropriate to square dimensioned 
elements. 
 

NOTE: 
Provision must be made to view the burner to 

ensure its operation under normal operating 
conditions. Viewing ports may be necessary. 
 
Ensure no flammable substances are in the 
immediate environment of the heating module. 

 
 

6.0  Gas Connection (3/4”) 

 

6.1 

National requirements and regulations for 
the installation of gas must be respected 
for all countries into which the appliance 
is delivered. Gas connections may only 
be carried out be appropriately qualified 
persons. 

 
6.1.2  Clearances around connections  shall be 

adequate so as to afford access to allow  

 

the use of tools to connect and 
disconnect the gas service connections. 

 
6.1.3  Threads use for gas pipes and fittings 

shall comply with ISO 7.1 1994. 
 

6.1.4  Copper pipes and fittings may not be 

used. Solder which has a melting point of 
less than 450

C neither solder or alloys 

containing cadmium shall not be used. 

 
6.1.5  All gas services to the heating module 

shall be equipped with an isolation tap 
which shall be of the 90

o

 turn type and 

shall be provided with a positive stop and 
it should be fitted adjacent to the heating 
module. Such taps when installed in a 
vertical position shall be so that in the 
event of a falling handle the valve will be 
in the closed condition, the open and 
closed positing shall be readily 
distinguishable. The valve shall be easy 
to operate when required. 

 
 

7.0  Electrical Equipment

 

 

7.1.0  The EURO-C 4000 heating module has 

been fully tested prior to leaving the 
manufacturer. The constructor shall not 
make changes to the wiring supplied with 
the  module. Electrical connections may 
only be made using the terminals 
provided and strictly in accordance with 
wiring diagram provided with the module. 

 
7.1.1  EURO-C 4000 electrical controls 

are

 

phase sensitive 230V 1N 50 Hz. The 
appliance must be 

earthed

 after the 

installation has been completed and earth 
continuity test must be carried out. 

 
7.1.2  The electrical equipment of the module 

complies with the requirements of: EN 
60335-1, EN60730-1 and EN61058-1 or 
to relevant amendments. The constructor 
must also comply with these 
requirements when fitting the module. 

 
7.1.3  The protection of jacket less appliances 

conforms to protection code IP 20. The 
constructor must ensure that protection 
to at least IP 45 is fulfilled and mark his 
data/rating plate accordingly.

 

Содержание EURO-C 4000 DJL

Страница 1: ...an air handler or as part of an air handling system These appliances meet the following EC Directives Dir CE 90 396 EEC GAD Dir CE 89 336 EEC EMC Dir CE 73 23 EEC LVD Dir CE 89 392 EEC MD annex ll su...

Страница 2: ...18 4024 4030 4047 4060 4072 4100 Are destined to be incorporated in other machines air handlers or to be combined with other machines air handling systems and is not entirely in compliance with the ma...

Страница 3: ...ICAL APPLICATION 11 4 0 LIMITATIONS FOR USE 12 5 0 BURNER CONTROLS SECTION 14 6 0 GAS CONNECTION 15 7 0 ELECTRICAL EQUIPMENT 15 8 0 COMBUSTION CIRCUIT EURO C RJL 16 9 0 COMBUSTION CIRCUIT EURO C DJL 2...

Страница 4: ...that the water vapour in the combustion products condenses out 2 Basic information 2 1 The instructions contained in this document apply to model EURO C 4000 RJL and or EURO C DJL gas fired fan assis...

Страница 5: ...Euro C 4000 JLGBEN 5 31 Figure 1 Dimensions EURO C 4011 15 RJL DJL Fig 1 A Fig 1 B...

Страница 6: ...Euro C 4000 JLGBEN 6 31 Fig 1 C...

Страница 7: ...Euro C 4000 JLGBEN 7 31 Figure 2 Dimensions EURO C 4018 72 RJL DJL Fig 2 A Fig 2 B...

Страница 8: ...Euro C 4000 JLGBEN 8 31 Fig 2 C...

Страница 9: ...Euro C 4000 JLGBEN 9 31 Figure 3 Dimensions EURO C 4100 RJL DJL Fig 3 A Fig 3 B...

Страница 10: ...Euro C 4000 JLGBEN 10 31 Fig 3 C...

Страница 11: ...ion Figure 4 Compartment dimensions key reference Table 1 For horizontal airflow For vertical airflow Table 1 Dimensions of enclosures duct channel for EURO C 4000 heating modules re fig 4 Dimension D...

Страница 12: ...h air heaters The minimum airflow duty through the heating section enclosure see fig 4 table 1 must be observed as indicated in table 2 Table 2 AIRFLOW DUTY MODEL Min air volume required through enclo...

Страница 13: ...ger In function of the expected minimum inlet air temperature the minimum required temperature rise to avoid condensation must be derived from the chart shown in figure 6 Example expected minimum inle...

Страница 14: ...RJL roof top outdoor unit the enclosure into which it is fitted must comply with protection grade IP 45 5 1 3 Access to compartments enclosing the burner and its controls must be provided with panels...

Страница 15: ...out be appropriately qualified persons 6 1 2 Clearances around connections shall be adequate so as to afford access to allow the use of tools to connect and disconnect the gas service connections 6 1...

Страница 16: ...r Consequently included with the heating module are 100 terminal outlet length 300mm PN 60 50712 300 90 elbow with sealing ring dia 100 PN 60 50733 100 Flue outlet combustion air inlet panel assembly...

Страница 17: ...Euro C 4000 JLGBEN 17 31 Figure 7 General arrangement combustion air inlet and flue products outlet Model 4011 72 Model 4100...

Страница 18: ...Euro C 4000 JLGBEN 18 31 Figure 8a models 4011 72 Figure 8b model 4100...

Страница 19: ...Euro C 4000 JLGBEN 19 31 Figure 8c all models Figure 9a models 4011 72...

Страница 20: ...the protection cap std length 300mm is 700mm 8 1 4 Attention must be given to properly seal the mounting flange of the heating module see figure 9 NOTE OTHER FLUE ARRANGEMENTS THAN THOSE DESCRIBED AND...

Страница 21: ...tube sealing ring PN 06 22783 125 2 teflon sealing rings PN 06 22786 084 dia 80 mod 4011 15 PN 06 22786 104 dia 100 mod 4018 24 30 PN 06 22786 134 dia 130 mod 4036 47 60 72 100 As shown in figure 10a...

Страница 22: ...Euro C 4000 JLGBEN 22 31 Figure 10b MODELS 4011 72 MODEL 4100...

Страница 23: ...g is also provided for the appliance for size R The hole size required for this seal ring in the casing is 50 mm diameter All cables and wires passing through the casing of the burner controls section...

Страница 24: ...Euro C 4000 JLGBEN 24 31 Figure 12 Models 4011 72 Model 4100...

Страница 25: ...is added to the application and for airflow conditions as indicated in figure 4 Figure 13 Pressure drop through RJL DJL 4011 15 18 24 30 heating module Figure 14 Pressure drop through RJL DJL 4036 47...

Страница 26: ...em the resulting air flow over the heating section will be equal to the minimal air duty as shown in table 2 In fact the recommended dimensions are maximal allowable dimensions for the by pass This ca...

Страница 27: ...section must be used in figures 13 to 19 to extract the correct pressure drop over the heat exchanger Example Application on Euro C 4011 RJL DJL By Pass 300 mm wide x 310 mm high Total Air Flow 1 m s...

Страница 28: ...by pass 11 2 1 This calculation is applicable for total airflow conditions above V table 7 A The by pass can either be mounted on top of the heat exchanger or besides the heat exchanger as shown in fi...

Страница 29: ...s Vtot Total air flow m s x1 Recommended by pass dim C or D as calculated in section 11 2 x2 Applied by pass dim mm Then VHS air flow through heat exchanger enclosure can be calculated as As explaine...

Страница 30: ...0 66 00 60 00 6 99 5 35 5 23 0 153 4072 87 90 79 15 72 00 8 39 6 42 6 28 0 153 4100 122 00 110 00 98 00 11 64 8 91 8 71 0 153 Notes to table 1 1 GCV Hs 2 NCV Hi 3 Natural gas G20 gross calorific value...

Страница 31: ...ze Burner pressure mbar 1 Model Quantity mm marking Butane Propane 4011 3 1 00 100 27 9 36 9 4015 4 1 00 100 27 8 36 8 4018 5 1 00 100 27 8 36 9 4024 5 1 20 120 28 7 36 5 4030 6 1 20 120 27 5 36 5 403...

Отзывы: